Turning the UPS Off

To turn off the UPS, press and hold the Off button until the long beep ceases (approximately five seconds). The indicator begins to flash and the UPS remains in Standby mode until you unplug the UPS from the power outlet.

Initiating the Self–Test

NOTE. The batteries must be fully charged to perform the self–test.

Press and hold the On button for three seconds to initiate the self–test. During the test, individual indicators illuminate as various parts of the UPS are checked. If the alarm beeps or a UPS alarm indicator stays on, see Table 2 on page 22.

Communication Port

The Powerware 5125 is factory-installed with a Single-Port Module.

To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.

When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.

The cable pins are identified in Figure 8 and the pin functions are described in Table 1.

Figure 8. Communication Port

Pin

Signal Name

Function

Direction from

Number

the UPS

 

 

1

Low Batt

Low Battery relay contact

Out

 

 

 

 

2

RxD

Transmit to external device

Out

 

 

 

 

3

TxD

Receive from external device

In

 

 

 

 

4

DTR

PnP (Plug and Play) from external device

In

(tied to Pin 6)

 

 

 

 

 

 

 

 

5

GND

Signal common (tied to chassis)

 

 

 

 

6

DSR

To external device (tied to Pin 4)

Out

 

 

 

 

7

RTS

PnP from external device

In / Out

 

 

 

 

8

AC Fail

AC Fail relay contact

Out

 

 

 

 

9

Power Source

+V (8 to 24 volts DC power)

Out

 

 

 

 

Table 1. Communication Port Pin Assignment

1019297

1000 - 2200 VA

13

Revision A

User’s Manual

 

Image 13 Contents
UPS 1000 2200 VA User’s Manual Page Table of contents Powerware 5125 User’s Manual 1000-2200 VACopyright Class a EMC Statements VA Models Requesting a Declaration of ConformitySpecial Symbols Powerware Powerware 5125 IntroductionInstalling the UPS InstallationInspecting the Equipment UPS Rear Panels InstallationOperating Modes Operation and ConfigurationNormal Mode Standby ModeBuck and Double Boost Mode Sleep Mode Battery ModeUPS Configuration Starting the UPS on BatteryInitiating the Self-Test Turning the UPS OffCommunication Port Network Transient Protector Network Transient ProtectorVA and 1500 VA Load Segments Load SegmentsUPS and Battery Care UPS MaintenanceWhen to Replace Batteries Storing the UPS and BatteriesHow to Replace Extended Battery Modules Use the following procedure to replace internal batteries Testing New Batteries Recycling the Used Battery TroubleshootingAudible Alarms and UPS Conditions Alarm or Condition Possible Cause Action Silencing an Audible Alarm100% Dimensions W x D x H Weight SpecificationsBattery