Powerware UPS 1000 - 2200 Battery Mode, Sleep Mode, UPS Configuration, Turning the UPS On

Page 12

Battery Mode

When the UPS is operating during a power outage, the alarm beeps once every four

seconds and the indicator illuminates. When the utility power returns, the UPS switches to Normal mode operation while the battery recharges.

If battery capacity becomes low while in Battery mode, the indicator flashes and the alarm beeps twice every two seconds. Immediately complete and save your work to prevent data loss and similar difficulties. When utility power is restored after the UPS shuts down, the UPS automatically restarts.

Sleep Mode

If the UPS is on battery for approximately five minutes and supporting a small electrical load (≤ 10%), the UPS shuts down the load. After three minutes in Sleep mode, the UPS initiates a shutdown warning (two beeps every two seconds). This feature conserves battery power. To enable this feature, contact your service representative.

UPS Configuration

Your PW5125 UPS can be configured by using a configuration software that can be find on web (www.emea.powerware.com/product/PW5125.htm). This software is a DOS based program that can be executed from either a DOS box, from a Windows shortcut, or from the Windows Start, Run dialog box.

UPS setting that can be changed are as follow:

1.Voltage setting 220/230/240 V (230 V is factory default)

2.Enable/disable sleep mode (disable as factory default)

3.Enable/disable audible alarm, so that when disable no audible alarms will be given (Enable as factory default)

4.Enable/disable site wiring detection (not supported on European model)

Turning the UPS On

After the UPS is connected to a power outlet, it conducts a self–test and enters Standby mode. To turn on the UPS, press and hold the On button until you hear the UPS beep (approximately one second). The indicator stops flashing and the bar graph indicators display the percentage of load being applied to the UPS.

Starting the UPS on Battery

NOTE Before using this feature, the UPS must have been powered by utility power at least once.

To turn on the UPS without using utility power, press and hold the On button for at least four seconds. The UPS supplies power to your equipment and goes into Battery mode.

12

1000 - 2000 VA

1019297

 

User’s Manual

Revision A

Image 12
Contents UPS 1000 2200 VA User’s Manual Page Powerware 5125 User’s Manual 1000-2200 VA Table of contentsCopyright Requesting a Declaration of Conformity Class a EMC Statements VA ModelsSpecial Symbols Powerware 5125 Introduction PowerwareInstallation Installing the UPSInspecting the Equipment Installation UPS Rear PanelsOperation and Configuration Operating ModesStandby Mode Normal ModeBuck and Double Boost Mode Battery Mode Sleep ModeUPS Configuration Starting the UPS on BatteryTurning the UPS Off Initiating the Self-TestCommunication Port Network Transient Protector Network Transient ProtectorLoad Segments VA and 1500 VA Load SegmentsUPS Maintenance UPS and Battery CareWhen to Replace Batteries Storing the UPS and BatteriesHow to Replace Extended Battery Modules Use the following procedure to replace internal batteries Testing New Batteries Troubleshooting Recycling the Used BatteryAudible Alarms and UPS Conditions Silencing an Audible Alarm Alarm or Condition Possible Cause Action100% Specifications Dimensions W x D x H WeightBattery