Powerware UPS 1000 - 2200 user manual Battery

Page 24

Operating Temperature

 

 

10°C to 40°C

 

 

 

 

 

 

Optimal battery performance: 25°C

 

Storage Temperature

 

 

 

0°C to 25°C

 

 

 

Transit Temperature

 

 

-25°C to 55°C

 

 

 

Relative Humidity

 

 

5–95% noncondensing

 

Operating Altitude

Up to 3,000 meters above sea level

 

Transit Altitude

Up to 15,000 meters above sea level

 

Audible Noise

Less than 40 dBA Normal mode, typical load

 

Less than 55 dBA Battery mode

 

 

 

 

 

Surge Suppression

ANSI C62.41 Category B (formerly IEEE 587), IEC 61000-4-5

 

 

 

UL 1778, UL 497A (data line only);

 

Safety Conformance

 

 

CAN/CSA C22.2, No. 107.1;

 

 

 

 

 

EN 50091-1-1 and IEC 60950

 

Agency Markings

UL and cUL; CE, C-Tick, LGA/GS, DEMKO

 

EMC

 

 

EN 50091-2, FCC Part 15, ICES-003

 

Table 7. Environmental and Safety

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuration

1000 VA: (2) 24V, 9 Ah internal batteries

 

 

 

1500 VA: (4) 48V, 7 Ah internal batteries

 

 

 

 

 

 

 

 

 

 

 

 

2200 VA: (4) 48V, 12 Ah internal batteries

 

 

 

 

 

 

 

 

 

EBM Configuration

PW5125 EBM-24:

(8) 24V, 9 Ah batteries

 

 

 

 

 

 

PW5125 EBM-48:

(8) 48V, 9 Ah batteries

 

 

 

 

 

 

 

 

Type

 

 

Sealed, maintenance–free, valve–regulated, lead–acid

 

 

 

 

 

 

 

 

Internal battery: less than 3 hours to 90% usable capacity at

 

 

 

nominal line voltage after full load discharge

 

Charging

External battery: recharging at 80% load or less is

 

recommended; no more than 16x discharge time to 90% usable

 

 

 

 

 

 

capacity at nominal line voltage after full load discharge; an

 

 

 

external battery charger is recommended for faster recharge

 

 

 

times when using more than 2 EBMs.

 

 

 

 

 

Monitoring

Advanced monitoring for earlier failure detection and warning;

 

 

 

auto detection of additional EBMs

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 8. Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

Internal UPS Batteries

 

1 EBM

 

2 EBMs

 

3 EBMs

 

4 EBMs

 

 

 

 

 

 

 

 

 

 

 

1000 VA

 

5/14

 

45/60

 

95/170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1500 VA

 

6/17

 

33/79

 

63/146

 

92/174

 

120/201

 

 

 

 

 

 

 

 

 

 

 

2200 VA

 

6/14

 

26/60

 

55/170

 

81/198

 

106/224

 

 

 

 

 

 

 

 

NOTE

Battery times are approximate and vary depending on the load configuration and

battery charge.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 9. Battery Run Times (in Minutes at Full/Half Load)

 

 

 

24

1000 - 2000 VA

1019297

 

User’s Manual

Revision A

Image 24
Contents UPS 1000 2200 VA User’s Manual Page Powerware 5125 User’s Manual 1000-2200 VA Table of contentsCopyright Requesting a Declaration of Conformity Class a EMC Statements VA ModelsSpecial Symbols Powerware 5125 Introduction PowerwareInstallation Installing the UPSInspecting the Equipment Installation UPS Rear PanelsOperation and Configuration Operating ModesStandby Mode Normal ModeBuck and Double Boost Mode Battery Mode Sleep ModeUPS Configuration Starting the UPS on BatteryTurning the UPS Off Initiating the Self-TestCommunication Port Network Transient Protector Network Transient ProtectorLoad Segments VA and 1500 VA Load SegmentsUPS Maintenance UPS and Battery CareWhen to Replace Batteries Storing the UPS and BatteriesHow to Replace Extended Battery Modules Use the following procedure to replace internal batteries Testing New Batteries Troubleshooting Recycling the Used BatteryAudible Alarms and UPS Conditions Silencing an Audible Alarm Alarm or Condition Possible Cause Action100% Specifications Dimensions W x D x H WeightBattery