Powerware 30-160kVA operation manual Line and Load Wiring

Page 17

The recommended location, for the Maintenance Bypass Module, is as close to the installed UPS module as possible. Refer to the tables in Appendix A for wire rating and sizing information

The MBM is packaged in a module similar to the UPS modules (same height, width, depth). The MBM is designed as a standard line-up-and-match accessory for the 30---160 KVA rated modules.

Wiring harness assemblies for connecting the UPS module bypass input and output to the MBP are provided in separate shipping containers, if applicable. The wiring harness assemblies are passed through the 3-inch wiring feed-through hole located at the lower right side of the MBM cabinet, for connecting to the UPS input and output terminals. Refer to Appendix A for UPS module to MBM wiring terminal locations.

Line up and match connection (cables sold separately by Powerware)

·From the UPS to the MBM, the power cables are connected by mechanical pressure lugs.

·From the UPS to the MBM, the control cables are connected to terminal blocks.

Remote connection (cables, lugs, and hardware supplied by others)

·All cables are terminated to MBM mechanical pressure lugs.

Line and Load Wiring

The Maintenance Bypass Module provides a means to manually transfer the Critical load from the UPS module via the UPS Module Bypass to a Maintenance Bypass Module as may be necessary for shutting down the UPS Module for maintenance or testing. The proper operation of the transfer is accomplished without interrupting the load power.

The UPS Module Bypass AC Input and the Maintenance Bypass AC Input must be from the same or synchronized AC sources. The UPS Module Bypass Input is connected through the MBP cabinet via an optional Bypass Input Breaker (BIB), if installed. The Maintenance Bypass Breaker (MBP) is placed in the secondary of the stepdown transformer (480:208 VAC or 600:208 VAC) or connected directly to the Maintenance Bypass source if the Isolation Transformer is not required.

UPS Module AC output connects through the MBM cabinet via isolation breaker MIS. Critical Load terminals are located on the load side of breakers MBP and MIS.

The Critical Load may be transferred in a Make-Before-Break transfer sequence between the UPS Bypass Source and the Maintenance Bypass source after UPS output has been transferred from the UPS module and UPS bypass operating mode. The MBP must first be closed to prevent power interruption and MIS opened to provide UPS isolation from the Critical Load bus. Refer to the Transfer Sequence placard affixed to the front of the MBM cabinet.

 

 

 

Powerware 9315 Maintenance Bypass Module 30---160kVA

13

164201177 Rev. C 041500

 

 

Image 17
Contents Maintenance Bypass Module 30-160kVA Important Safety Instructions Table of Contents List of Figures Typical Power Wiring Terminations of UPS ModuleIntroduction Conventions Used in This Manual Using This ManualGetting Help For More InformationThis Page Intentionally Left Blank Getting Started Preparing for Wiring the Maintenance Bypass Module Creating an Installation PlanPreparing the Site Environmental ConsiderationsMBM as Shipped, with Outer Packaging and Pallet Inspecting and Unpacking the Maintenance Bypass ModuleDo not tilt unit more than 10 degrees from vertical Unloading the MBM from the Pallet Detail of Shipping Supports Installing and Wiring Maintenance Bypass Module Maintenance Bypass Module UPS Module 30-160kVA UPS Shown Line and Load Wiring This Page Intentionally Left Blank Maintenance Bypass Module Operation Maintenance Bypass Module OperationMBM Operation Without Kirk Key Interlocks From UPS Bypass to Maintenance BypassMBM Transfer Sequences MBM Operation With Kirk Key Interlocks OptionalKirk Key Solenoid Release Unit Skru From Maintenance Bypass to UPS Bypass Maintenance Bypass Module Diagrams MaintenanceRefer to -- Maintaining the UPS System of the Powerware Short CircuitsThis Page Intentionally Left Blank Appendix a --- Customer Information Lagging PF load Basic unit rating atMBM 30---160kVA, 480480VAC/600600VAC MBM 30---160kVA, 208208VAC Installation NotesMBM 50---160KVA, 380380VAC, 400400VAC, 415415VAC 480208VAC, 600208VAC, 208208VAC, 480480VAC Table B. Circuit Breaker Requirements for Powerware80KVA MBM Table C-- 1. Power Cable TerminationsSee Fi g Twisted Pair164201177---2 Interior Components Description Typical MBM CabinetTOP View Bottom View Description Typical UPS System with MBM 30---160kVA UPS System with MBM600600VAC, 400400VAC Oneline -- 30-160kVA, RT, 480480VAC480208VAC, 600208VAC Oneline -- 30-160kVA, RTDescription Oneline -- 30-160kVA, RT, 208208VAC 164201177---7 Oneline -- 30-160kVA, PARALLEL, 480480VACOneline -- 30-160kVA, Parallel Oneline -- 30-160kVA, PARALLEL, 208208VAC Description Line UP and Match Arrangement #1 Line UP and Match Arrangement #1Description Line UP and Match Arrangement #2 Line UP and Match Arrangement #2Description Line UP and Match Arrangement #3 Line UP and Match Arrangment Notes This Page Intentionally Left Blank

30-160kVA specifications

The Powerware 30-160kVA is an advanced uninterruptible power supply (UPS) designed to meet the demands of medium to large-scale facilities requiring reliable power protection. This UPS series is celebrated for its robust performance, comprehensive features, and innovative technologies, making it a standout choice for businesses looking to ensure continuous operation without power disruptions.

One of the defining characteristics of the Powerware 30-160kVA series is its high efficiency. The UPS provides exceptional energy savings and operates at up to 96% efficiency in double conversion mode and even higher in ECO mode. This efficiency translates to reduced operational costs and a smaller carbon footprint, which is increasingly important in today's environmentally conscious business landscape.

Another key feature of this UPS is its modular architecture, allowing for flexible scalability. Users can easily configure the system to meet their specific power requirements and can scale up or down as per their needs. This modularity minimizes downtime and provides an adaptable solution that grows alongside the business.

The Powerware 30-160kVA also utilizes advanced battery management technology. This feature enhances battery life and ensures the highest level of redundancy. The smart battery management system performs regular self-tests, identifying weaker cells and optimizing charging and discharging cycles. This helps to guarantee that the UPS is always ready to provide backup power when needed.

Moreover, this UPS series has a user-friendly interface, making monitoring and control straightforward. The LCD display provides real-time information regarding operational status, alarms, and system performance, empowering users to quickly respond to any anomalies.

In terms of connectivity and integration, the Powerware 30-160kVA supports multiple communication protocols. This includes options for SNMP and Modbus, facilitating easy integration with existing infrastructure and allowing for remote management.

In summary, the Powerware 30-160kVA series is designed for businesses seeking reliability, efficiency, and flexibility in power management. Its advanced technology, high efficiency, modular design, and user-friendly features make it an ideal choice for data centers, telecommunications, and various critical applications where uptime and power quality are paramount. This UPS not only safeguards equipment but also contributes to energy cost savings, making it an essential investment for organizations focused on operational resilience.