Powerware 30-160kVA operation manual From Maintenance Bypass to UPS Bypass

Page 22

From Maintenance Bypass to UPS Bypass:

1.Confirm BIBs, if installed, are closed.

2.Transfer UPS to Bypass mode (see UPS Operation manual).

NOTE: For Parallel Redundant systems, transfer both UPS modules to Bypass mode.

3.Depress pushbutton on the Solenoid Key Release Unit (SKRU). Turn and remove key “A”.

4.Insert key “A” into MIS lock, retract bolt, close MIS breaker. Remove key “B”.

CAUTION:

Failure to close MBP breaker results in loss of power to the critical load.

5.Insert key “B” into MBP lock, open MBP breaker, extend bolt. Remove key “A”.

6.Insert key “A” into solenoid and turn key to LOCK position.

7.See UPS Operation manual to place UPS in Normal mode.

WARNING:

Dangerous and potentially lethal voltages are present within the UPS enclosure. When maintenance or repair activities are to be performed, the UPS and the UPS Bypass power sources should be deenergized and verified with a meter before working in the required area.

WARNING:

UPS equipment has power feeds that are derived from two or more power sources.

18

Powerware 9315 Maintenance Bypass Module 30-160kVA

 

 

164201177 Rev. C 041500

Image 22
Contents Maintenance Bypass Module 30-160kVA Important Safety Instructions Table of Contents Typical Power Wiring Terminations of UPS Module List of FiguresIntroduction Using This Manual Conventions Used in This ManualFor More Information Getting HelpThis Page Intentionally Left Blank Getting Started Preparing the Site Creating an Installation PlanPreparing for Wiring the Maintenance Bypass Module Environmental ConsiderationsInspecting and Unpacking the Maintenance Bypass Module MBM as Shipped, with Outer Packaging and PalletDo not tilt unit more than 10 degrees from vertical Unloading the MBM from the Pallet Detail of Shipping Supports Installing and Wiring Maintenance Bypass Module Maintenance Bypass Module UPS Module 30-160kVA UPS Shown Line and Load Wiring This Page Intentionally Left Blank Maintenance Bypass Module Operation Maintenance Bypass Module OperationFrom UPS Bypass to Maintenance Bypass MBM Operation Without Kirk Key InterlocksKirk Key Solenoid Release Unit Skru MBM Operation With Kirk Key Interlocks OptionalMBM Transfer Sequences From Maintenance Bypass to UPS Bypass Refer to -- Maintaining the UPS System of the Powerware MaintenanceMaintenance Bypass Module Diagrams Short CircuitsThis Page Intentionally Left Blank Appendix a --- Customer Information Basic unit rating at Lagging PF loadMBM 30---160kVA, 480480VAC/600600VAC Installation Notes MBM 30---160kVA, 208208VACMBM 50---160KVA, 380380VAC, 400400VAC, 415415VAC Table B. Circuit Breaker Requirements for Powerware 480208VAC, 600208VAC, 208208VAC, 480480VAC80KVA Table C-- 1. Power Cable Terminations MBMTwisted Pair See Fi g164201177---2 Description Typical MBM Cabinet Interior ComponentsTOP View Bottom View 30---160kVA UPS System with MBM Description Typical UPS System with MBMOneline -- 30-160kVA, RT, 480480VAC 600600VAC, 400400VACOneline -- 30-160kVA, RT 480208VAC, 600208VACDescription Oneline -- 30-160kVA, RT, 208208VAC Oneline -- 30-160kVA, PARALLEL, 480480VAC 164201177---7Oneline -- 30-160kVA, Parallel Oneline -- 30-160kVA, PARALLEL, 208208VAC Line UP and Match Arrangement #1 Description Line UP and Match Arrangement #1Line UP and Match Arrangement #2 Description Line UP and Match Arrangement #2Description Line UP and Match Arrangement #3 Line UP and Match Arrangment Notes This Page Intentionally Left Blank