Powerware 30-160kVA MBM Operation With Kirk Key Interlocks Optional, MBM Transfer Sequences

Page 21

MBM Operation With Kirk Key Interlocks (Optional)

The following transfer sequence is the recommended procedure for the step-by-step load transfer from and back to the UPS when required. This information is provided on a label located on the deadfront panel behind the right front door of the MBM.

Kirk Key Solenoid Release Unit (SKRU)

The 120 VAC operating power for the Kirk Key Solenoid Release Unit (SKRU) is derived from the Maintenance Bypass source.

The Kirk Key SKRU is provided to prevent access to the key, which is necessary to initiate the transfer sequence. The operator must observe the instructions on the Transfer Sequence nameplate mounted on the MBP Panelboard.

Electrical interlocks inhibit key release until UPS is in the Bypass mode.

MBM Transfer Sequences

From UPS Bypass to Maintenance Bypass:

1.Confirm BIBs, if installed, are closed.

2.Transfer UPS from Normal to Bypass mode (see UPS Operation manual). NOTE: For Parallel Redundant systems, transfer both UPS modules to

Bypass mode.

3.Depress pushbutton on the solenoid key release unit (SKRU). Turn and remove key “A”. Key “A” may be removed when UPS system is in Bypass mode as indicated by illuminated pilot light.

4.Insert key “A” into MBP lock, retract bolt, close MBP breaker. Remove key “B”.

CAUTION:

Failure to close MBP breaker results in loss of power to the critical load.

5.Insert key “B’ into MIS lock, open MIS breaker, extend bolt. Remove key “A”.

6.Insert key “A” into solenoid and turn key to LOCK position.

7.Deenergize UPS before servicing (see UPS Operation manual).

CAUTION:

For UPS electrical isolation, BIB breaker (if applicable) must be opened.

 

 

 

Powerware 9315 Maintenance Bypass Module 30---160kVA

17

164201177 Rev. C 041500

 

 

Image 21
Contents Maintenance Bypass Module 30-160kVA Important Safety Instructions Table of Contents List of Figures Typical Power Wiring Terminations of UPS ModuleIntroduction Conventions Used in This Manual Using This ManualGetting Help For More InformationThis Page Intentionally Left Blank Getting Started Preparing for Wiring the Maintenance Bypass Module Creating an Installation PlanPreparing the Site Environmental ConsiderationsMBM as Shipped, with Outer Packaging and Pallet Inspecting and Unpacking the Maintenance Bypass ModuleDo not tilt unit more than 10 degrees from vertical Unloading the MBM from the Pallet Detail of Shipping Supports Installing and Wiring Maintenance Bypass Module Maintenance Bypass Module UPS Module 30-160kVA UPS Shown Line and Load Wiring This Page Intentionally Left Blank Maintenance Bypass Module Operation Maintenance Bypass Module OperationMBM Operation Without Kirk Key Interlocks From UPS Bypass to Maintenance BypassMBM Operation With Kirk Key Interlocks Optional Kirk Key Solenoid Release Unit SkruMBM Transfer Sequences From Maintenance Bypass to UPS Bypass Maintenance Bypass Module Diagrams MaintenanceRefer to -- Maintaining the UPS System of the Powerware Short CircuitsThis Page Intentionally Left Blank Appendix a --- Customer Information Lagging PF load Basic unit rating atMBM 30---160kVA, 480480VAC/600600VAC MBM 30---160kVA, 208208VAC Installation NotesMBM 50---160KVA, 380380VAC, 400400VAC, 415415VAC 480208VAC, 600208VAC, 208208VAC, 480480VAC Table B. Circuit Breaker Requirements for Powerware80KVA MBM Table C-- 1. Power Cable TerminationsSee Fi g Twisted Pair164201177---2 Interior Components Description Typical MBM CabinetTOP View Bottom View Description Typical UPS System with MBM 30---160kVA UPS System with MBM600600VAC, 400400VAC Oneline -- 30-160kVA, RT, 480480VAC480208VAC, 600208VAC Oneline -- 30-160kVA, RTDescription Oneline -- 30-160kVA, RT, 208208VAC 164201177---7 Oneline -- 30-160kVA, PARALLEL, 480480VACOneline -- 30-160kVA, Parallel Oneline -- 30-160kVA, PARALLEL, 208208VAC Description Line UP and Match Arrangement #1 Line UP and Match Arrangement #1Description Line UP and Match Arrangement #2 Line UP and Match Arrangement #2Description Line UP and Match Arrangement #3 Line UP and Match Arrangment Notes This Page Intentionally Left Blank

30-160kVA specifications

The Powerware 30-160kVA is an advanced uninterruptible power supply (UPS) designed to meet the demands of medium to large-scale facilities requiring reliable power protection. This UPS series is celebrated for its robust performance, comprehensive features, and innovative technologies, making it a standout choice for businesses looking to ensure continuous operation without power disruptions.

One of the defining characteristics of the Powerware 30-160kVA series is its high efficiency. The UPS provides exceptional energy savings and operates at up to 96% efficiency in double conversion mode and even higher in ECO mode. This efficiency translates to reduced operational costs and a smaller carbon footprint, which is increasingly important in today's environmentally conscious business landscape.

Another key feature of this UPS is its modular architecture, allowing for flexible scalability. Users can easily configure the system to meet their specific power requirements and can scale up or down as per their needs. This modularity minimizes downtime and provides an adaptable solution that grows alongside the business.

The Powerware 30-160kVA also utilizes advanced battery management technology. This feature enhances battery life and ensures the highest level of redundancy. The smart battery management system performs regular self-tests, identifying weaker cells and optimizing charging and discharging cycles. This helps to guarantee that the UPS is always ready to provide backup power when needed.

Moreover, this UPS series has a user-friendly interface, making monitoring and control straightforward. The LCD display provides real-time information regarding operational status, alarms, and system performance, empowering users to quickly respond to any anomalies.

In terms of connectivity and integration, the Powerware 30-160kVA supports multiple communication protocols. This includes options for SNMP and Modbus, facilitating easy integration with existing infrastructure and allowing for remote management.

In summary, the Powerware 30-160kVA series is designed for businesses seeking reliability, efficiency, and flexibility in power management. Its advanced technology, high efficiency, modular design, and user-friendly features make it an ideal choice for data centers, telecommunications, and various critical applications where uptime and power quality are paramount. This UPS not only safeguards equipment but also contributes to energy cost savings, making it an essential investment for organizations focused on operational resilience.