Powerware 30-160kVA operation manual Preparing the Site, Creating an Installation Plan

Page 10

Preparing the Site

For the MBM to operate at peak efficiency, the installation site should meet the environmental parameters outlined in the PowerwareÒ 9315 Operation manual provided with the UPS system. The operating environment must meet the size and weight requirements supplied in the PowerwareÒ 9315 Installation manual provided with the UPS system. If the MBM is to be operated at an altitude higher than 1500 meters (5000 feet), contact the local sales or service office for important information about high altitude operation.

The basic environmental requirements for operation of the MBM are:

Ambient Temperature Range

0---

40˚C (32---

104˚F)

Recommended Operating Range

20---

25˚C (68---

77˚F)

Maximum Relative Humidity

95%

 

The MBM uses convection cooling to regulate internal component temperature. Air inlets are in the front of the cabinet, and outlets are in the top. Clearance in front of and above each cabinet for proper air circulation is essential.

Creating an Installation Plan

Before beginning to install the MBM, read and understand how this manual applies to the system being installed. It is important to note that UPS module installation procedures are contained in the PowerwareÒ 9315 Installation manual provided with the UPS system. It is recommended to first understand how to install the UPS modules. The information in Chapter 2 of this manual is a guide for installation of the MBM to the UPS modules.

Environmental Considerations

The life of the maintenance bypass module is adversely affected if the installation does not meet the following guidelines:

1.The MBM must be installed on a sealed concrete pad or floor.

2.The MBM must be installed in a dust-free environment.

3.The MBM must be installed in a humidity-controlled environment.

Preparing for Wiring the Maintenance Bypass Module

See Tables A-1 through A-6 in Appendix A of this manual for wiring requirements. The power wiring for this equipment is rated at 90_C. If wire is run in an ambient temperature greater than 30_C, higher temperature rating and/or larger size wire may be necessary. Wiring should be installed through the bottom or top entry of the module. For UPS external wiring requirements, including minimum AWG size of external wiring, see the PowerwareÒ 9315 Installation manual provided with the UPS system.

NOTE: Material and labor for external wiring are to be provided by designated personnel.

6

Powerware 9315 Maintenance Bypass Module 30-160kVA

 

164201177 Rev. C 041500

Image 10
Contents Maintenance Bypass Module 30-160kVA Important Safety Instructions Table of Contents Typical Power Wiring Terminations of UPS Module List of FiguresIntroduction Using This Manual Conventions Used in This ManualFor More Information Getting HelpThis Page Intentionally Left Blank Getting Started Preparing the Site Creating an Installation PlanPreparing for Wiring the Maintenance Bypass Module Environmental ConsiderationsInspecting and Unpacking the Maintenance Bypass Module MBM as Shipped, with Outer Packaging and PalletDo not tilt unit more than 10 degrees from vertical Unloading the MBM from the Pallet Detail of Shipping Supports Installing and Wiring Maintenance Bypass Module Maintenance Bypass Module UPS Module 30-160kVA UPS Shown Line and Load Wiring This Page Intentionally Left Blank Maintenance Bypass Module Operation Maintenance Bypass Module OperationFrom UPS Bypass to Maintenance Bypass MBM Operation Without Kirk Key InterlocksKirk Key Solenoid Release Unit Skru MBM Operation With Kirk Key Interlocks OptionalMBM Transfer Sequences From Maintenance Bypass to UPS Bypass Refer to -- Maintaining the UPS System of the Powerware MaintenanceMaintenance Bypass Module Diagrams Short CircuitsThis Page Intentionally Left Blank Appendix a --- Customer Information Basic unit rating at Lagging PF loadMBM 30---160kVA, 480480VAC/600600VAC Installation Notes MBM 30---160kVA, 208208VACMBM 50---160KVA, 380380VAC, 400400VAC, 415415VAC Table B. Circuit Breaker Requirements for Powerware 480208VAC, 600208VAC, 208208VAC, 480480VAC80KVA Table C-- 1. Power Cable Terminations MBMTwisted Pair See Fi g164201177---2 Description Typical MBM Cabinet Interior ComponentsTOP View Bottom View 30---160kVA UPS System with MBM Description Typical UPS System with MBMOneline -- 30-160kVA, RT, 480480VAC 600600VAC, 400400VACOneline -- 30-160kVA, RT 480208VAC, 600208VACDescription Oneline -- 30-160kVA, RT, 208208VAC Oneline -- 30-160kVA, PARALLEL, 480480VAC 164201177---7Oneline -- 30-160kVA, Parallel Oneline -- 30-160kVA, PARALLEL, 208208VAC Line UP and Match Arrangement #1 Description Line UP and Match Arrangement #1Line UP and Match Arrangement #2 Description Line UP and Match Arrangement #2Description Line UP and Match Arrangement #3 Line UP and Match Arrangment Notes This Page Intentionally Left Blank

30-160kVA specifications

The Powerware 30-160kVA is an advanced uninterruptible power supply (UPS) designed to meet the demands of medium to large-scale facilities requiring reliable power protection. This UPS series is celebrated for its robust performance, comprehensive features, and innovative technologies, making it a standout choice for businesses looking to ensure continuous operation without power disruptions.

One of the defining characteristics of the Powerware 30-160kVA series is its high efficiency. The UPS provides exceptional energy savings and operates at up to 96% efficiency in double conversion mode and even higher in ECO mode. This efficiency translates to reduced operational costs and a smaller carbon footprint, which is increasingly important in today's environmentally conscious business landscape.

Another key feature of this UPS is its modular architecture, allowing for flexible scalability. Users can easily configure the system to meet their specific power requirements and can scale up or down as per their needs. This modularity minimizes downtime and provides an adaptable solution that grows alongside the business.

The Powerware 30-160kVA also utilizes advanced battery management technology. This feature enhances battery life and ensures the highest level of redundancy. The smart battery management system performs regular self-tests, identifying weaker cells and optimizing charging and discharging cycles. This helps to guarantee that the UPS is always ready to provide backup power when needed.

Moreover, this UPS series has a user-friendly interface, making monitoring and control straightforward. The LCD display provides real-time information regarding operational status, alarms, and system performance, empowering users to quickly respond to any anomalies.

In terms of connectivity and integration, the Powerware 30-160kVA supports multiple communication protocols. This includes options for SNMP and Modbus, facilitating easy integration with existing infrastructure and allowing for remote management.

In summary, the Powerware 30-160kVA series is designed for businesses seeking reliability, efficiency, and flexibility in power management. Its advanced technology, high efficiency, modular design, and user-friendly features make it an ideal choice for data centers, telecommunications, and various critical applications where uptime and power quality are paramount. This UPS not only safeguards equipment but also contributes to energy cost savings, making it an essential investment for organizations focused on operational resilience.