Installation instructions
Fig. 17 Vertical venting installation (twin pipe penetra- tion)
| RAINCAP |
10'MIN. | STORMCOLLAR |
2'MIN. | FLASHING |
| |
3'MIN. | SILICONESEAL |
| |
CHIMNEY |
|
MAY BEINSULATED |
|
IFNECESSARY |
|
HORIZONTAL RUN |
|
1/4"RISE/FT |
|
HANGERSTRAP |
|
| MORTAR |
ELBOW | ELBOW |
| |
HOSE |
|
CLAMP |
|
CONDENSATE |
|
DRAIN |
|
APPLIANCE |
|
|
Fig. 18 Vertical venting installation - Masonry Chim- ney (combustion air piping not shown)
3.3.4Vent connections
BAttach the flue gas exhaust accessory (8 705 504
162)to the top of the unit (position 1) using the 4 screws and gasket provided. Fully insert stainless steel vent pipe 1.5” minimum into the accessory and tighten the clamp (position 2).
NOTE: Vent pipe must be completely ver-
itical when inserting or gasket inside ex- haust accessory can become displaced. Exhaust accessory can be removed with vent pipe attached to check gasket posi- tion.
Fig. 19
B Attach the combustion air inlet accessory (8 705 504 116) to the top of the unit (position 3) using the 3 screws and gasket provided, and install air intake pipe over the accessory. NOTE: The appliance has the option to mount the combustion air inlet acces- sory on the top right or on the top left side of the heater. The combustion air inlet that is not used must be kept sealed.
Fig. 20
BEnsure that exhaust vent pipe is fully inserted in collar to enable proper connection.
Exhaust venting must be 3" or 4" sealed
isingle wall stainless steel