Installation instructions

 

 

 

Natural Gas

Liquid propane

 

 

 

 

 

 

 

Altitude

Total

Minimum

Maximum

Maximum

 

(above sea

equivalent

power fan

power fan speed

power fan speed

 

level)

vent length1)

speed (P2)

(P1)

(P1)

 

0 - 2000 ft

5.5 - 32 ft

7

No

No

 

 

 

 

(0 - 610 m)

 

 

modification required

modification required

 

33 - 57 ft

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For operation at elevations

 

5.5 - 32 ft

8*

48*

47*

2000 - 4500 ft

above 2,000 ft (610 m) the

 

 

 

 

equipment ratings shall be

(610 - 1372 m)

 

 

 

 

reduced at the rate of 4% for

33 - 57 ft

8*

49*

48*

 

each 1,000 ft (305 m) above sea

 

 

 

 

 

level

4500 - 8000 ft

5.5 - 32 ft

9*

49*

48*

 

 

 

 

 

 

(1372 - 2439 m)

 

 

 

 

 

33 - 57 ft

9*

50*

49*

 

 

 

 

 

 

 

 

 

* Above 2000 ft, CO2 levels must be checked with a combustion gas analyzer, see section 6.4 for instructions.

Table 12 Fan speed adjustment

1)Full equivalent length (inlet + outlet piping + fittings)

Adjusting minimum power fan speed (P2)

To select fan speed:

BPress ON/OFF button into OFF.

BPress and hold "Program" button and press ON/OFF button to turn appliance ON.

Adjusting maximum power fan speed (P1)

To select fan speed:

BPress ON/OFF button into OFF.

BPress and hold "Program" button and press ON/OFF button to turn appliance ON.

Fig. 22

B As soon as '188' is displayed, release "Program"

button , and the display should read P2.

BPress or to choose the fan speed suitable with your installation, see Table 12.

BPress and hold (± 5 sec.) “Program” button until the display flashes, then the selected value is memo- rized.

Fig. 23

B As soon as '188' is displayed, release "Program" but-

ton

, and the display reads P2.

 

B Press the minus button

to display P1.

 

B Press “Program” button

to enter P1 adjustment.

The current setting will appear on the display.

 

B Press

or

to choose the fan speed suitable

with your installation, see Table 12.

 

B Press and hold (± 5 sec.) “Program” button

until

i

Do not set P2 to greater then 9.

the display flashes, then the selected value is memo-

rized.

Proceed directly to Section 6.4 to confirm

iCO2 values are within range.

18

6 720 608 542

Page 18
Image 18
Bosch Appliances GWH 2700 ES LP, ESVVT, GWH 2700 ES NG Level Vent length1 Speed P2, Adjusting minimum power fan speed P2