Installation instructions

Horizontal venting systems only:

An optional stainless concentric vent/air intake termina- tion can be used to provide only one penetration point through the exterior wall (see Fig. 8, 9 & 10). The con- centric vent/air intake kit can be ordered from your local wholesaler. (Part# ESHCK). Note: Vent piping and terminal used with concentric vent/air intake kit must be from the same vent pipe manufacturer. The appliance can also be installed with separate air intake and exhaust piping (see Fig. 15 ).

6720608782-09.1Av

Fig. 8 Concentric kit part # ESHCK

6720608782-10.1Av

Fig. 9 Concentric kit vent assembly

12"

Min. 3 Feet

3” stainless steel pipe

3.3.2Venting Specifications

Install appliance as close to point of vent termination as possible. The exhaust piping must vent directly to the outside of the structure.

Horizontal sections of vent must pitch upward towards termination ¼" for every foot of horizontal length, to prevent the pooling of condensate, and be supported at 4 foot intervals with overhead hangers.

Exception: horizontal run between last elbow and termination must pitch down to termination 1/4" per foot. Note: For horizontal terminations, venting must terminate once it penetrates to the outside of the structure. There must be no sections of vent pipe exposed to the outdoors other than the termination. Note: Listed thimbles or collars are necessary where venting passes through wall and ceiling partitions. If the vent system passes through combustible areas where the vent clearance requirements cannot be maintained, it is permissible to chase straight sections of sea led 3 inch single wall vent through 4 inch (or greater) T ype-B vent. The distance to combustibles using this chase technique is 1 inch 1). Note: Type-B vent must never be used as the actual exhaust vent system for the appliance, as it is not gas tight and illegal for use with this appliance. This will create a serious health hazard and void the warranty.

3”

Z flex

Protech

Heat Fab

 

VENTING

 

 

 

 

 

 

 

 

 

 

 

 

 

3 or 4"

2SVEEWCF0390

FSELB9003

9314

 

90° elbow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3”

 

 

 

 

 

 

Horizontal

2SVSTB03

FSTB3

9390 TEE

 

 

 

 

 

 

 

Terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

3” Vertical

2SVSRCF03

FSRC3

5300CI

 

Terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3 Terminator Part Numbers

 

 

 

 

 

 

 

 

 

Fittings or Piping

 

Equivalent

 

 

 

 

 

 

 

 

 

 

 

feet

 

m

 

 

 

 

 

 

 

 

45 degree elbow

 

1.25

 

0.38

 

 

 

 

 

 

 

90 degree elbow

 

2.5

 

0.76

 

 

 

 

 

 

 

pipe per foot

 

1

 

0.30

 

 

 

 

 

 

 

 

Table 4 Friction Loss Equivalent in piping and fittings

For specific questions concerning vent material, speci- fications, usage or installation, please contact the vent manufacturer directly.

6720608782-11.1Av

Fig. 10 Concentric kit installation

Company

Contact info

 

 

Z-flex

www.z-flex.com

 

800-654-5600

 

 

ProTech Industries

www.protechinfo.com

 

800-766-3473

 

 

Heat-Fab

www.heatfab.com

 

800-772-0739

 

 

Table 5 Vent manufacturers