Low Voltage Wiring

Low Voltage Wiring for Field Provided Thermostats/Zone Sensors

Ensure that the AC control wiring be- tween the controls and the unit’s ter- mination point does not exceed three

(3)ohms/conductor for the length of the run.

Note: Resistance in excess of 3-ohms per conductor may cause component failure due to insufficient AC voltage supply.

Check all loads and conductors for grounds, shorts, and mis-wiring.

Use copper conductors unless other- wise specified.

Do not run the AC low voltage wiring in the same conduit with the high volt- age power wiring.

Table 3: 24V AC conductors

Distance

Recommended

from unit to Control

Wire Size

 

 

000-460 feet

18 gauge

 

 

461-732 feet

16 gauge

 

 

733-1000 feet

14 gauge

 

 

Thermostat Location

Location of the room thermostat/zone sensor cis an important element of effec- tive room control.

Areas where the thermostat or zone sensor should not be located include : be- hind doors, or corners; Near hot or cold air ducts; Near radiant heat (heat emitted from appliances or the sun); Near concealed pipes or chimneys; On outside walls or other non conditioned surfaces; In airflows from adjacent zones or other units (Figure 7).

Figure 7: Thermostat/sensor location