General Information

Unit Nameplate

The unit nameplate is located at the front of the unit. It includes the unit model number, serial number, electri- cal characteristics, refrigerant charge, and other pertinent unit data.

Compressor Nameplate

The nameplate for the compressors are located on the compressor shell.

Unit Description

Before shipment, each unit is leak test- ed, dehydrated, charged with refriger- ant and run tested for proper control operation.

Water-to-Refrigerant Coils

The co-axial water-to-refrigerant heat exchanger for the 1 1/2-ton through 6- ton equipment is constructed of cop- per or cupro-nickel (option) for the wa- ter section and stainless steel for the refrigeration section.

The heat exchanger is leak tested to assure there is no cross leakage be- tween the water and refrigerant gas.

Water Connections

Water connections are located at the unit front for both the WPVJ and WPHF units. They are clearly labled for supply/return connection. Sizes are as follows.

Dia.

Type

 

 

3/4"

WPHF 021-027 - Water in/out

 

 

1"

WPHF 030-072 - Water in/out

 

 

1"

WPVJ - Water in/out

 

 

3/4"

Drain

 

 

1/2"

Desuperheater

 

 

Blower/Motor

The blower and motor is located inside the unit cabinet. The motor may be easily removed for service through the equipment blower access panel.

Controls

The control system offered to control the unit is a Basic 24 volt control, Basic 24 volt control, or TracerTM ZN510 control. A 50 VA transformer is factory supplied on the Basic 24V control con- figurations. A 75 VA transformer is fac-

tory supplied on the ZN510 (digital) control configurations.

ZN510 Controls

(WPVJ and WPHF option)

Units incorporating the ZN510 control option design will include a digital LonTalkTM certified control board. The control board will support such op- tions as: random start delay, heating/ cooling status, occupied/unoccupied mode and fan/filter status.

Power wiring is made at the contactor. See manual WSHP-IOP-2 for diagnos- tic information.

Schrader Connections

Connections for the low and high side of the refrigeration system are located conveniently at the equipments front panel. Sheet metal removal is not re- quired for positive connection to the high and low schrader connections.

WSHP-SVX04A-EN

5

Page 5
Image 5
Trane WPVJ, WPHF manual General Information