Troubleshooting

Troubleshooting

Hazardous Service WARNING

Hazardous Service

Procedures!

The maintenance and trouble shooting procedures recommend- ed in this section of the manual could result in exposure to electri- cal, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concern- ing these procedures. When possi- ble, disconnect all electrical power including remote discon- nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be in- advertently energized. When nec- essary to work with live electrical components, have a qualified li- censed electrician or other indi- vidual who has been trained in handling live electrical compo- nents per these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.

Preliminary Trouble Inspection If operational difficulties are encoun- tered, be sure to perform the prelimi- nary checks before referring to the troubleshooting chart on page 34.

Verify that the unit is receiving elec- tric supply power.

Ensure that the fuses in the fused disconnect are intact.

After completing the preliminary checks, inspect the unit for other obvi- ous problems such as leaking connec- tion, broken or disconnected wires, etc. If everything appears to be in or- der, but the unit still fails to operate properly, refer to the troubleshooting chart on page 34.

General Operation

The standard model is designed for in- door installation. When the unit is in- stalled in an unconditioned space, the unit may not start in cool weather (ap- proximately 45°F). It may then be nec- essary to start the unit in the cooling mode for three to five minutes. The unit may then be shut-off (there will be a two minute time-out of the unit), and restarted in the heating mode.

Like any other type of mechanical equipment, the unit performs best when it is well maintained.

Operation with a Conventional Thermostat

The unit is equipped with safety con- trols, including high pressure control and low pressure control to shut off the compressor under abnormal pres- sure conditions. If the safeties shut off the compressor, a lockout relay pre- vents short cycling from the abnormal condition. When conditions are cor- rected, the lockout control can be reset by setting the thermostat system switch to OFF wait a few minutes for the system pressure to equalize, and then return to HEAT or COOL. If the condition continues, an authorized service person should check out the unit.