Installation
Field Installed Power Wiring
Power wiring to the equipment must conform to National and Local Electric Codes (NEC) by a professional electri- cian.
WARNING
Live Electrical
Components!
During installation, testing, ser- vicing and troubleshooting of this product, it may be necessary to work with live electrical compo- nents. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical compo- nents perform these tasks. Failure to follow all electrical safety pre- cautions when exposed to live electrical components could re- sult in death or serious injury.
Verify that the power supply available is compatible with the unit’s name- plate. Use only copper conductors to connect the power supply to the unit.
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conduc- tors. Failure to use copper con- ductors may result in equipment damage.
Main Unit Power Wiring
A field supplied disconnect switch must be installed at or near the unit in accordance with the National Electric Code (NEC latest edition).
Location of the applicable electric ser- vice entrance for HIGH (line voltage) may be found on the unit submittals (pages 7 to 13).
1The high voltage connection is made at the 1K1 contactor inside of the unit control box. Refer to the
connection diagram that is shipped with the unit for specific termina- tion points.
2Provide proper grounding for the unit in accordance with the local and national codes.
Control Power Transformer
The
WARNING
Hazardous Voltage!
Disconnect all electric power, in- cluding remote disconnects be- fore servicing. Follow proper lockout/tagout procedures to en- sure the power can not be inad- vertently energized. Failure to disconnect power before servic- ing could result in death or seri- ous injury.
The transformer is located in the unit’s control box.
18 |