Requirements

Table E3: WPHF Electrical Performance (Standard Static Blower Option-continued)

 

 

Blower Motor

Blower Motor

Compr.

Compr.

Compr.

Minimum Cir-

UL Max Fuse

CSA

CASE

Model No.

Volts/Hz/Ph

HP

FLA

RLA

MCC

LRA

cuit Amps

or HACR

Max. Fuse

Max.

 

 

 

 

 

 

 

 

 

Size

Circuit Brkr

WPHF057

208/60/1

1/2

4.1

22.3

34.8

122

32.0

50

60

50

WPHF057

230/60/1

1/2

4.1

22.3

34.8

122

32.0

50

60

50

WPHF057

208/60/3

1/2

4.1

14.4

25.5

101

22.1

35

50

45

WPHF057

230/60/3

1/2

4.1

14.4

25.5

101

22.1

35

50

45

WPHF057

460/60/3

1/2

1.8

7.1

11.1

51

10.7

15

20

20

Table E4: WPHF Electrical Performance (High Static Blower Option)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower Motor

Blower Motor

Compr.

Compr.

Compr.

Minimum Cir-

UL Max Fuse

CSA

CASE

Model No.

Volts/Hz/Ph

HP

FLA

RLA

MCC

LRA

cuit Amps

or HACR

Max. Fuse

Max.

 

 

 

 

 

 

 

 

 

Size

Circuit Brkr

WPHF047

208/60/1

1/2

4.6

14.6

22.8

92

22.9

35

50

40

WPHF047

230/60/1

1/2

4.6

14.6

22.8

92

22.9

35

50

40

WPHF047

208/60/3

1/2

4.6

10.6

16.5

101

17.9

25

50

45

WPHF047

230/60/3

1/2

4.6

10.6

16.5

101

17.9

25

50

45

WPHF047

460/60/3

1/2

2.2

4.2

6.6

51

7.5

15

25

20

WPHF057

208/60/1

1/2

4.6

22.3

34.8

122

32.5

50

60

50

WPHF057

230/60/1

1/2

4.6

22.3

34.8

122

32.5

50

60

50

WPHF057

208/60/3

1/2

4.6

14.4

22.5

101

22.6

35

50

45

WPHF057

230/60/3

1/2

4.6

14.4

22.5

101

22.6

35

50

45

WPHF057

460/60/3

1/2

2.2

7.1

11.1

51

11.1

15

25

20