Read and understand the following notes while planning your installation:

1.Refer to national and local electric codes for acceptable external wiring practices.

2.Material and labor for external wiring requirements are to be provided by others.

3.For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A-2 and A-4. The power wiring for this equipment is rated at 90 degrees Celsius.

4.The output of the UPS is not a separately derived source. Output neutral is not bonded to equipment ground through the main bonding jumper. Refer to NEC and local codes for proper grounding practices.

5.The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full load input current in Table A-2 and A-4.

6.The Bypass three-phase feeds should be symmetrical about ground.

7.Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.

8.Control wiring must be installed in separate conduit from the power wiring.

9.Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with an optional (extra cost) mechanical interlock if required.

10.Refer to UPS Installation Manual for proper Bypass terminating lugs at UPS cabinet or input transformer cabinet.

11.Refer to Table C-2 for control wiring connections.

12.A Maintenance Bypass neutral feeder must be supplied when the MBM output neutral is used. If no Maintenance Bypass neutral is supplied, the MBM output neutral is not to be used. In neither case shall the MBM output neutral be bonded to ground.

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

MIS:

MAINTENANCE ISOLATION BREAKER

 

 

 

 

 

 

 

 

 

 

 

MBP:

MAINTENANCE BYPASS BREAKER

DESCRIPTION:

 

 

 

 

 

 

 

 

 

 

BIB:

BYPASS INPUT BREAKER

ONELINE -- 30-160kVA, RT, 480:480VAC,

 

 

 

 

SKRU:

SOLENOID KEY RELEASE UNIT

 

600:600VAC, 400:400VAC

 

 

 

 

 

(MECHANICAL INTERLOCK)

 

 

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

 

164201177---4

 

SHEET: 1 of 1

 

 

 

 

 

RT:

REVERSE TRANSFER

 

 

 

 

 

 

 

110100057 D3

REVISION:

A

 

DATE:

080498

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A---14

 

Powerware 9315 Maintenance Bypass Module 30-160kVA

 

 

 

 

 

 

 

 

164201177 Rev. C 041500

Image 38
Contents Maintenance Bypass Module 30-160kVA Important Safety Instructions Table of Contents Typical Power Wiring Terminations of UPS Module List of FiguresIntroduction Using This Manual Conventions Used in This ManualFor More Information Getting HelpThis Page Intentionally Left Blank Getting Started Preparing the Site Creating an Installation PlanPreparing for Wiring the Maintenance Bypass Module Environmental ConsiderationsInspecting and Unpacking the Maintenance Bypass Module MBM as Shipped, with Outer Packaging and PalletDo not tilt unit more than 10 degrees from vertical Unloading the MBM from the Pallet Detail of Shipping Supports Installing and Wiring Maintenance Bypass Module Maintenance Bypass Module UPS Module 30-160kVA UPS Shown Line and Load Wiring This Page Intentionally Left Blank Maintenance Bypass Module Operation Maintenance Bypass Module OperationFrom UPS Bypass to Maintenance Bypass MBM Operation Without Kirk Key InterlocksMBM Transfer Sequences MBM Operation With Kirk Key Interlocks OptionalKirk Key Solenoid Release Unit Skru From Maintenance Bypass to UPS Bypass Refer to -- Maintaining the UPS System of the Powerware MaintenanceMaintenance Bypass Module Diagrams Short CircuitsThis Page Intentionally Left Blank Appendix a --- Customer Information Basic unit rating at Lagging PF loadMBM 30---160kVA, 480480VAC/600600VAC Installation Notes MBM 30---160kVA, 208208VACMBM 50---160KVA, 380380VAC, 400400VAC, 415415VAC Table B. Circuit Breaker Requirements for Powerware 480208VAC, 600208VAC, 208208VAC, 480480VAC80KVA Table C-- 1. Power Cable Terminations MBMTwisted Pair See Fi g164201177---2 Description Typical MBM Cabinet Interior ComponentsTOP View Bottom View 30---160kVA UPS System with MBM Description Typical UPS System with MBMOneline -- 30-160kVA, RT, 480480VAC 600600VAC, 400400VACOneline -- 30-160kVA, RT 480208VAC, 600208VACDescription Oneline -- 30-160kVA, RT, 208208VAC Oneline -- 30-160kVA, PARALLEL, 480480VAC 164201177---7Oneline -- 30-160kVA, Parallel Oneline -- 30-160kVA, PARALLEL, 208208VAC Line UP and Match Arrangement #1 Description Line UP and Match Arrangement #1Line UP and Match Arrangement #2 Description Line UP and Match Arrangement #2Description Line UP and Match Arrangement #3 Line UP and Match Arrangment Notes This Page Intentionally Left Blank

30-160kVA specifications

The Powerware 30-160kVA is an advanced uninterruptible power supply (UPS) designed to meet the demands of medium to large-scale facilities requiring reliable power protection. This UPS series is celebrated for its robust performance, comprehensive features, and innovative technologies, making it a standout choice for businesses looking to ensure continuous operation without power disruptions.

One of the defining characteristics of the Powerware 30-160kVA series is its high efficiency. The UPS provides exceptional energy savings and operates at up to 96% efficiency in double conversion mode and even higher in ECO mode. This efficiency translates to reduced operational costs and a smaller carbon footprint, which is increasingly important in today's environmentally conscious business landscape.

Another key feature of this UPS is its modular architecture, allowing for flexible scalability. Users can easily configure the system to meet their specific power requirements and can scale up or down as per their needs. This modularity minimizes downtime and provides an adaptable solution that grows alongside the business.

The Powerware 30-160kVA also utilizes advanced battery management technology. This feature enhances battery life and ensures the highest level of redundancy. The smart battery management system performs regular self-tests, identifying weaker cells and optimizing charging and discharging cycles. This helps to guarantee that the UPS is always ready to provide backup power when needed.

Moreover, this UPS series has a user-friendly interface, making monitoring and control straightforward. The LCD display provides real-time information regarding operational status, alarms, and system performance, empowering users to quickly respond to any anomalies.

In terms of connectivity and integration, the Powerware 30-160kVA supports multiple communication protocols. This includes options for SNMP and Modbus, facilitating easy integration with existing infrastructure and allowing for remote management.

In summary, the Powerware 30-160kVA series is designed for businesses seeking reliability, efficiency, and flexibility in power management. Its advanced technology, high efficiency, modular design, and user-friendly features make it an ideal choice for data centers, telecommunications, and various critical applications where uptime and power quality are paramount. This UPS not only safeguards equipment but also contributes to energy cost savings, making it an essential investment for organizations focused on operational resilience.