Powerware 30-160kVA operation manual MBM 50---160KVA, 380380VAC, 400400VAC, 415415VAC

Page 29

Table A-- 4. Rating and External Wiring Requirements for Powerware 9315

MBM 50---160KVA, 380:380VAC, 400:400VAC, 415:415VAC

RATING AND EXTERNAL WIRING REQUIREMENT

UNITS

 

 

 

RATING 50/60 HZ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BASIC UNIT RATING AT

KVA

160

130

100

 

80

65

 

50

40

 

30

0.8 LAGGING PF LOAD

KW

128

104

80

 

64

52

 

40

32

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS INPUT VOLTAGE

VOLTS

 

 

 

380/400/415

 

 

 

 

 

BYPASS INPUT/UPS OUTPUT VOLTAGE

VOLTS

 

 

 

380/400/415

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC INPUT TO MAINTENANCE BYPASS

AMPS

231

188

146

 

115

97

 

74

60

 

45

A

(3) PHASES, (1) GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDUCTOR SIZE

AWG/MCM

300

300

300

 

300

300

 

1

1

 

1

 

NUMBER PER PHASE

(each)

(1)

(1)

(1)

 

(1)

(1)

 

(1)

(1)

 

(1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC INPUT TO UPS BYPASS

AMPS

231

188

146

 

115

97

 

74

60

 

45

B

(3) PHASES, (1) GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDUCTOR SIZE

AWG/MCM

300

300

300

 

300

300

 

1

1

 

1

 

NUMBER PER PHASE

(each)

(1)

(1)

(1)

 

(1)

(1)

 

(1)

(1)

 

(1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC OUTPUT TO CRITICAL LOAD

AMPS

231

188

146

 

115

97

 

74

60

 

45

C

(3) PHASES, (1) NEUTRAL, (1) GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDUCTOR SIZE

AWG/MCM

300

300

300

 

300

300

 

1

1

 

1

 

NUMBER PER PHASE

(each)

(1)

(1)

(1)

 

(1)

(1)

 

(1)

(1)

 

(1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS/PTC OUTPUT TO MBM CABINET (MIS)

AMPS

231

188

146

 

115

97

 

74

60

 

45

D

(3) PHASE, (1) NEUTRAL, (1) GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDUCTOR SIZE

AWG/MCM

300

300

300

 

300

300

 

1

1

 

1

 

NUMBER PER PHASE

(each)

(1)

(1)

(1)

 

(1)

(1)

 

(1)

(1)

 

(1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

CONTROL WIRING TO UPS

VOLTS

120

120

120

 

120

120

 

120

120

 

120

(2) CONDUCTORS

AMPS

1

1

1

 

1

1

 

1

1

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

Callout letters A, B, C, D, and E map to drawing 164201177--- 4 (Reverse Transfer Connection) and

 

 

 

164201177--- 7 (Parallel Connection). Read and understand the notes on drawings when planning your installation.

 

 

 

 

DESCRIPTION:

INSTALLATION NOTES

 

 

 

 

 

 

DRAWING NO:

164201177---1

 

SHEET: 4 of 4

 

 

 

 

 

 

REVISION: C

 

DATE:

041500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware 9315 Maintenance Bypass Module 30---160kVA

 

 

 

 

 

A---5

164201177 Rev. C 041500

 

 

 

 

 

 

 

Image 29
Contents Maintenance Bypass Module 30-160kVA Important Safety Instructions Table of Contents List of Figures Typical Power Wiring Terminations of UPS ModuleIntroduction Conventions Used in This Manual Using This ManualGetting Help For More InformationThis Page Intentionally Left Blank Getting Started Preparing for Wiring the Maintenance Bypass Module Creating an Installation PlanPreparing the Site Environmental ConsiderationsMBM as Shipped, with Outer Packaging and Pallet Inspecting and Unpacking the Maintenance Bypass ModuleDo not tilt unit more than 10 degrees from vertical Unloading the MBM from the Pallet Detail of Shipping Supports Installing and Wiring Maintenance Bypass Module Maintenance Bypass Module UPS Module 30-160kVA UPS Shown Line and Load Wiring This Page Intentionally Left Blank Maintenance Bypass Module Operation Maintenance Bypass Module OperationMBM Operation Without Kirk Key Interlocks From UPS Bypass to Maintenance BypassMBM Transfer Sequences MBM Operation With Kirk Key Interlocks OptionalKirk Key Solenoid Release Unit Skru From Maintenance Bypass to UPS Bypass Maintenance Bypass Module Diagrams MaintenanceRefer to -- Maintaining the UPS System of the Powerware Short CircuitsThis Page Intentionally Left Blank Appendix a --- Customer Information Lagging PF load Basic unit rating atMBM 30---160kVA, 480480VAC/600600VAC MBM 30---160kVA, 208208VAC Installation NotesMBM 50---160KVA, 380380VAC, 400400VAC, 415415VAC 480208VAC, 600208VAC, 208208VAC, 480480VAC Table B. Circuit Breaker Requirements for Powerware80KVA MBM Table C-- 1. Power Cable TerminationsSee Fi g Twisted Pair164201177---2 Interior Components Description Typical MBM CabinetTOP View Bottom View Description Typical UPS System with MBM 30---160kVA UPS System with MBM600600VAC, 400400VAC Oneline -- 30-160kVA, RT, 480480VAC480208VAC, 600208VAC Oneline -- 30-160kVA, RTDescription Oneline -- 30-160kVA, RT, 208208VAC 164201177---7 Oneline -- 30-160kVA, PARALLEL, 480480VACOneline -- 30-160kVA, Parallel Oneline -- 30-160kVA, PARALLEL, 208208VAC Description Line UP and Match Arrangement #1 Line UP and Match Arrangement #1Description Line UP and Match Arrangement #2 Line UP and Match Arrangement #2Description Line UP and Match Arrangement #3 Line UP and Match Arrangment Notes This Page Intentionally Left Blank

30-160kVA specifications

The Powerware 30-160kVA is an advanced uninterruptible power supply (UPS) designed to meet the demands of medium to large-scale facilities requiring reliable power protection. This UPS series is celebrated for its robust performance, comprehensive features, and innovative technologies, making it a standout choice for businesses looking to ensure continuous operation without power disruptions.

One of the defining characteristics of the Powerware 30-160kVA series is its high efficiency. The UPS provides exceptional energy savings and operates at up to 96% efficiency in double conversion mode and even higher in ECO mode. This efficiency translates to reduced operational costs and a smaller carbon footprint, which is increasingly important in today's environmentally conscious business landscape.

Another key feature of this UPS is its modular architecture, allowing for flexible scalability. Users can easily configure the system to meet their specific power requirements and can scale up or down as per their needs. This modularity minimizes downtime and provides an adaptable solution that grows alongside the business.

The Powerware 30-160kVA also utilizes advanced battery management technology. This feature enhances battery life and ensures the highest level of redundancy. The smart battery management system performs regular self-tests, identifying weaker cells and optimizing charging and discharging cycles. This helps to guarantee that the UPS is always ready to provide backup power when needed.

Moreover, this UPS series has a user-friendly interface, making monitoring and control straightforward. The LCD display provides real-time information regarding operational status, alarms, and system performance, empowering users to quickly respond to any anomalies.

In terms of connectivity and integration, the Powerware 30-160kVA supports multiple communication protocols. This includes options for SNMP and Modbus, facilitating easy integration with existing infrastructure and allowing for remote management.

In summary, the Powerware 30-160kVA series is designed for businesses seeking reliability, efficiency, and flexibility in power management. Its advanced technology, high efficiency, modular design, and user-friendly features make it an ideal choice for data centers, telecommunications, and various critical applications where uptime and power quality are paramount. This UPS not only safeguards equipment but also contributes to energy cost savings, making it an essential investment for organizations focused on operational resilience.