Powerware 9335 operation manual UPS Cabinet Installation

Page 20

2.2UPS Cabinet Installation

To install an UPS cabinet, perform the procedures in the following paragraphs.

2.2.1Unloading the Powerware 9335 (80 kVA and 120 kVA) UPS Cabinet from the Pallet

The UPS cabinet is bolted to a wooden shipping base using two steel angles. To remove the shipping material, perform the following procedure.

WARNING:

The UPS cabinet is heavy. Refer to Table J in Appendix A for weight of cabinets. If unloading instructions are not closely followed, the cabinet may cause serious injury.

CAUTION:

Do not tilt cabinets more than ±10 degrees from vertical. Do not cut the outside protective cardboard packing box open. Damage to the enclosed cabinet may occur.

CAUTION:

Carefully open top of outer package and remove accessory installation kit before removing outer packaging. Approximate weight is 25 lbs. (11 kg.)

1.Remove accessory installation kit located at the top of the unit (see figure 1.1) by opening top of outer box. Remove the 4 jacking bolts from the accessory pack. Use a forklift or other material handling equipment to move the cabinet to the installation area. Insert the forklift forks under the unit and keep the unit elevated approximately 3 inches above the ground.

2.Remove the outer stretch wrapping. The two steel angles which connect the UPS cabinet to the wooden shipping base contain 2 threaded holes for inserting jacking bolts..

3.Unbolt the wooden cross members on the shipping base by removing the four nuts

(10 mm) which fasten the wooden pallet to the steel brackets. Remove the wooden cross members from the steel brackets. Insert the jacking bolts into the holes and lower them to the ground, in order for the weight of the unit to be supported by the 4 bolts. Place small metal plates under the jacking bolts to prevent floor damage. Ensure the unit does not tilt more than specified in the caution note above. Remove the forklift or pallet jack once the unit is supported on the jacking bolts. Slowly lower the UPS by alternating between the four jacking bolts, until the steel brackets are on the floor. Remove the jacking bolts. Detach the UPS cabinet from the angle steel by removing all of the M5 Phillips-head machine screws that fasten them, using a #3 Phillips head screwdriver. Tilt the unit slightly to enable the steel bracket to be removed from beneath two legs. Lower the unit down to the floor.

4.Repeat the process for the other side by tilting the unit and removing the steel bracket. (See illustrated procedure packed on the outside of the shipping carton.)

5.The UPS cabinet may now be moved to its final position for installation.

2-2

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

 

164201396 REV A 071103

Image 20
Contents Uninterruptible Power Supply 80 kVA 120 kVA Page Important Safety Instructions Table of Contents Understanding UPS Operation Operational Controls and FeaturesUsing the Control Panel Product Specifications Appendix a Customer Information WarrantyUPS Operating Instructions Responding to System EventsList of Figures Main Elements of the UPS SystemList of Tables Introduction Basic System Configurations Conventions Used in This Manual Safety Considerations Getting HelpSection Installation This page left intentionally blank Getting Started Installing the UPSCreating an Installation Plan Environmental Considerations Preparing for Wiring the UPS SystemPreparing Your Site Powerware 9335 80 kVA and 120 kVA UPS Packaging Inspecting and Unpacking Each CabinetDo not tilt cabinets more than ±10 degrees from vertical Installing the UPS System Preliminary Installation InformationUPS Cabinet Installation Installing External Battery Power Wiring Installing Customer Connections Initial Startup Battery Cabinet InstallationCompleting the Installation Checklist Installation Checklist Installing and Connecting Batteries Important Safety InstructionsThis page left intentionally blank To Install a Remote EPO Installing a Remote EPO ControlInstallation Procedures Remote EPO Wire Terminations To Operate a Remote EPOSection Operation This page left intentionally blank Understanding UPS Operation Looking Inside the UPS SystemREV a Normal, Battery and Bypass Modes Normal Mode Normal ModePage Bypass Mode Static BypassPage Battery Mode Battery ModePage Maintenance Bypass Mode Maintenance Bypass ModeBatteries and Battery Charger Functional DescriptionInput Rectifier Boost ConverterMaintenance Bypass Static BypassOperational Controls and Features GeneralSystem and Load ON/OFF UPS Operational ControlsControl Panel UPS Standard Features Options and Accessories Remote Emergency Power OFFBattery Cabinets CommunicationsSafety Considerations Symbols, Controls, and Indicators Protective Grounding TerminalUsing the Control Panel DescriptionLED Indicators Using the Control PanelPower Management Display Pushbutton Functions 4 ON/OFF Startup and Shutdown PushbuttonsDescription of the LCD Screen Status ScreensLCD Display Structure and Navigation Load OFFMeasurements Screen Main Menu ScreenEvent Log Screen Commands Screen UPS Data Set-Up UserSet-Up Service SET-UP Service PasswordPerating Modes On Line Mode Inverter ModeOFF Line Mode Bypass or Economy Mode Maintenance Bypass Mode Line INVParallel Isolator IA2 Operation Start-Up Procedure for the UPSUPS Operating Instructions LED Indicator Color Complete Shutdown Procedure for the UPS Load Transfer to Maintenance Bypass Line OFF Bypass Inverter BatteryRed This page left intentionally blank Responding to System Events AlarmsMenu, Commands, Event Log, and Measurements Fault Identification and Correction Alarm Condition Meaning Suggested SolutionCommunications10 Slot Communication ModulesX-Slot Location on Front of Powerware 9335 UPS Cabinet Single-Port Serial CardCommunication Port on the Single Port Serial Card 10-4 Options Generator on Facility11-2 General Important Safety InstructionsMaintaining the UPS System Performing Preventive Maintenance Perform the following checks DailyUPS System Input Product SpecificationsSystem Information Environmental Specifications UPS System OutputAppendix a Customer Information Powerware 9335 80 kVA Powerware 9335 120 kVA AC Input to Phase a #6-250 kcmils Cooper 42.4 375 Table E. Maximum Input Circuit Breaker Ratings Amperes Table F. Maximum Output Circuit Breaker Ratings AmperesTable G. Customer Interface Inputs and Outputs Terminal Name DescriptionAlarm MNS REV a 07/11/2003 Table J. Equipment Weight Ambient Temperature RangePowerware 9335 80kVA and 120 kVA Table K. System ClearancesElements Figure A-2. Powerware 9335 80 kVA and 120 kVA Label 3A, 3B, 3C, 3N 1A, 1B, 1C, 1N2A, 2B, 2C, 2N Electrical Diagram 120 kVA S06-0001ULA Powerware NW4007 Figure A-7. UPS Cabinet Dimensions Rear View 750 mm .6 inches 700 mm .6 inches 1800 mm Page Page Page Page Limited Factory Warranty for THREE-PHASE Powerware Products This page left intentionally blank

9335 specifications

The Powerware 9335 is a robust and efficient uninterruptible power supply (UPS) designed to deliver reliable power protection for critical applications. Expanding upon Eaton's tradition of offering advanced power management solutions, the Powerware 9335 is tailored for environments that demand high availability and uptime.

One of the standout features of the Powerware 9335 is its double-conversion online topology, which ensures a continuous supply of clean and regulated power. This design operates without any transfer time to battery power, effectively protecting sensitive equipment from all types of power disturbances, including surges, sags, and outages.

The UPS is available in a range of power ratings, from 8 kVA to 40 kVA, making it versatile enough to support a variety of applications ranging from small server rooms to larger data centers. The modular architecture of the Powerware 9335 allows for seamless scalability, enabling users to add additional capacity or redundancy as their power needs evolve. This feature is particularly beneficial in dynamic environments where equipment and loads can frequently change.

Another significant characteristic of the Powerware 9335 is its high efficiency, often exceeding 94% in normal operation. This efficiency not only reduces energy costs but also minimizes heat generation, leading to lower cooling requirements. The UPS employs advanced technologies such as Intelligent Power Management and Smart APM (Adaptive Power Management) to optimize power usage, further enhancing its overall performance and reducing the total cost of ownership.

The user-friendly LCD display furnishes real-time data regarding UPS status, battery condition, and power settings, facilitating proactive management and monitoring. In addition, the unit can be monitored and managed remotely, ensuring that administrators can access critical information even when they are not on-site.

The Powerware 9335 also comes equipped with various connectivity options, including USB, serial, and SNMP for seamless integration into existing IT infrastructure. Additionally, advanced communication capabilities allow for integration with building management systems, ensuring comprehensive power management and reporting.

Safety is paramount, and the Powerware 9335 incorporates numerous features designed to protect both the UPS and connected equipment. This includes overload protection, battery health monitoring, and environmental monitoring, which collectively contribute to a resilient power protection strategy.

In summary, the Powerware 9335 is an exceptional UPS offering from Eaton, featuring high availability, scalability, efficiency, and robust management options. With its advanced technologies and features, it stands out as a premier choice for organizations seeking to safeguard their critical systems and data.