6.2 UPS Operational Controls
The UPS has many standard features that provide cost effective and consistently reliable power protection.
6.2.1 Control Panel
The Control Panel on the front of the UPS, pictured in Fig. 6–2, contains a LCD screen to display the current status of the UPS system. You can view a statistical history and log of system events and display a real-time representation of power flow through the system components. LED status indicators show the operating mode of the UPS and alert you to system events. Panel push buttons provide navigation through the information and control screens. The load ON/OFF pushbuttons are located at the right of the control panel. Both must be pressed simultaneously to activate the LOAD ON/OFF function. Below the LCD screen are the user control pushbuttons, RESET, UP, DOWN, and ENTER, which provide access to the control and measurement functions of the UPS. The control panel is described in detail in chapter 7, “Using the Control Panel”.
Display and Operation Push Buttons
Figure 6–2. Powerware 9335 (80 kVA and 120 kVA) Control Panel
6.2.2 System and Load ON/OFF
Two load ON/OFF pushbuttons are located on the right side of the LCD display. Activating both pushbuttons simultaneously will effect immediate system shutoff. This feature prevents accidental system shutdown if one of the pushbuttons is inadvertently depressed. System turn on is achieved in the same manner, by simultaneously depressing both buttons. Operation of the system ON/OFF pushbuttons is described in detail in Chapter 7, “Using the Control Panel” and Chapter 8, “UPS Operating Instructions.”
6-2 | Powerware 9335 (80 kVA and 120 kVA) Installation and Operation |
| 164201396 REV A 071103 |
Uninterruptible Power Supply 80 kVA 120 kVA
Page
Important Safety Instructions
Table of Contents
Understanding UPS Operation
Operational Controls and Features
Using the Control Panel
Product Specifications
Appendix a Customer Information Warranty
UPS Operating Instructions
Responding to System Events
List of Figures
Main Elements of the UPS System
List of Tables
Introduction
Basic System Configurations
Conventions Used in This Manual
Safety Considerations
Getting Help
Section Installation
This page left intentionally blank
Getting Started
Installing the UPS
Creating an Installation Plan
Environmental Considerations
Preparing for Wiring the UPS System
Preparing Your Site
Powerware 9335 80 kVA and 120 kVA UPS Packaging
Inspecting and Unpacking Each Cabinet
Do not tilt cabinets more than ±10 degrees from vertical
Installing the UPS System
Preliminary Installation Information
UPS Cabinet Installation
Installing External Battery Power Wiring
Installing Customer Connections
Initial Startup
Battery Cabinet Installation
Completing the Installation Checklist
Installation Checklist
Installing and Connecting Batteries
Important Safety Instructions
This page left intentionally blank
To Install a Remote EPO
Installing a Remote EPO Control
Installation Procedures
Remote EPO Wire Terminations
To Operate a Remote EPO
Section Operation
This page left intentionally blank
Understanding UPS Operation
Looking Inside the UPS System
REV a
Normal, Battery and Bypass Modes
Normal Mode
Normal Mode
Page
Bypass Mode
Static Bypass
Page
Battery Mode
Battery Mode
Page
Maintenance Bypass Mode
Maintenance Bypass Mode
Batteries and Battery Charger
Functional Description
Input Rectifier
Boost Converter
Maintenance Bypass
Static Bypass
Operational Controls and Features
General
System and Load ON/OFF
UPS Operational Controls
Control Panel
UPS Standard Features
Options and Accessories
Remote Emergency Power OFF
Battery Cabinets
Communications
Safety Considerations
Symbols, Controls, and Indicators
Protective Grounding Terminal
Using the Control Panel
Description
LED Indicators
Using the Control Panel
Power Management Display
Pushbutton Functions
4 ON/OFF Startup and Shutdown Pushbuttons
Description of the LCD Screen
Status Screens
LCD Display Structure and Navigation
Load OFF
Measurements Screen
Main Menu Screen
Event Log Screen
Commands Screen
UPS Data
Set-Up User
Set-Up Service
SET-UP Service Password
Perating Modes
On Line Mode Inverter Mode
OFF Line Mode Bypass or Economy Mode
Maintenance Bypass Mode
Line INV
Parallel Isolator IA2
Operation
Start-Up Procedure for the UPS
UPS Operating Instructions
LED Indicator Color
Complete Shutdown Procedure for the UPS
Load Transfer to Maintenance Bypass
Line OFF Bypass Inverter Battery
Red
This page left intentionally blank
Responding to System Events
Alarms
Menu, Commands, Event Log, and Measurements
Fault Identification and Correction
Alarm Condition Meaning Suggested Solution
Communications10
Slot Communication Modules
X-Slot Location on Front of Powerware 9335 UPS Cabinet
Single-Port Serial Card
Communication Port on the Single Port Serial Card
10-4
Options
Generator on Facility
11-2
General
Important Safety Instructions
Maintaining the UPS System
Performing Preventive Maintenance
Perform the following checks Daily
UPS System Input
Product Specifications
System Information
Environmental Specifications
UPS System Output
Appendix a Customer Information
Powerware 9335 80 kVA
Powerware 9335 120 kVA
AC Input to Phase a #6-250 kcmils Cooper 42.4 375
Table E. Maximum Input Circuit Breaker Ratings Amperes
Table F. Maximum Output Circuit Breaker Ratings Amperes
Table G. Customer Interface Inputs and Outputs
Terminal Name Description
Alarm MNS
REV a 07/11/2003
Table J. Equipment Weight
Ambient Temperature Range
Powerware 9335 80kVA and 120 kVA
Table K. System Clearances
Elements
Figure A-2. Powerware 9335 80 kVA and 120 kVA Label
3A, 3B, 3C, 3N
1A, 1B, 1C, 1N
2A, 2B, 2C, 2N
Electrical Diagram 120 kVA S06-0001ULA Powerware
NW4007
Figure A-7. UPS Cabinet Dimensions Rear View
750 mm .6 inches 700 mm .6 inches 1800 mm
Page
Page
Page
Page
Limited Factory Warranty for THREE-PHASE Powerware Products
This page left intentionally blank