WARNING:
The Powerware 9335 UPS requires a neutral input power connection for proper operation. Internal input and output neutrals are permanently connected inside the cabinet.
WARNING:
An insulated grounding conductor must be provided per NEC.
4.If the installation is for a single utility feed with common rectifier and bypass input, proceed to step 7. For a separate bypass and rectifier input, proceed to step 5.
5.Remove the single feed bus bar jumper connections from between X6 and X7, Phase A, B, and C and discard them. They will not be used again.
6.Connect ground, phase A, B, C, and Neutral mains input power wiring from the source to the Mains input terminals (1A, 1B, 1C) on the In/Out Terminal Block. Phase A input connects to input terminal 1A, phase B to input terminal 1B and phase C to input terminal 1C. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information. Note wiring connections for dual feed systems.
7.Connect ground, phase A, B, C, and Neutral power wiring from the output terminals (3A, 3B, 3C) on the In/Out Terminal Block to the critical load. Output terminal 3A connects to phase A of the load, output 3B to phase B and output 3C to phase C, respectively. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information.
8.Secure the UPS by reinstalling the safety shield panels, and closing the front cabinet door, latching the cabinet door with the removable door handle.
2.2.4Installing Customer Connections
See Chapter 10, “Communications”
2.2.5Prepare for Installing Optional Accessories
NOTE: If you are installing accessories, including the Remote Emergency Power Off (REPO) switch, you must install conduit between each device and the UPS cabinet for wiring these options.
1.Be sure the UPS system is turned off and all power sources are removed. (See the operation section of this manual for shutdown instructions.)
2-4 | Powerware 9335 (80 kVA and 120 kVA) Installation and Operation |
| 164201396 REV A 071103 |
Uninterruptible Power Supply 80 kVA 120 kVA
Page
Important Safety Instructions
Table of Contents
Using the Control Panel
Operational Controls and Features
Understanding UPS Operation
UPS Operating Instructions
Product Specifications
Appendix a Customer Information Warranty
Responding to System Events
List of Figures
Main Elements of the UPS System
List of Tables
Introduction
Basic System Configurations
Conventions Used in This Manual
Safety Considerations
Getting Help
Section Installation
This page left intentionally blank
Creating an Installation Plan
Installing the UPS
Getting Started
Preparing Your Site
Preparing for Wiring the UPS System
Environmental Considerations
Powerware 9335 80 kVA and 120 kVA UPS Packaging
Inspecting and Unpacking Each Cabinet
Do not tilt cabinets more than ±10 degrees from vertical
Installing the UPS System
Preliminary Installation Information
UPS Cabinet Installation
Installing External Battery Power Wiring
Installing Customer Connections
Completing the Installation Checklist
Battery Cabinet Installation
Initial Startup
Installation Checklist
Installing and Connecting Batteries
Important Safety Instructions
This page left intentionally blank
Installation Procedures
Installing a Remote EPO Control
To Install a Remote EPO
Remote EPO Wire Terminations
To Operate a Remote EPO
Section Operation
This page left intentionally blank
Understanding UPS Operation
Looking Inside the UPS System
REV a
Normal, Battery and Bypass Modes
Normal Mode
Normal Mode
Page
Bypass Mode
Static Bypass
Page
Battery Mode
Battery Mode
Page
Maintenance Bypass Mode
Maintenance Bypass Mode
Input Rectifier
Batteries and Battery Charger
Functional Description
Boost Converter
Maintenance Bypass
Static Bypass
Operational Controls and Features
General
Control Panel
UPS Operational Controls
System and Load ON/OFF
UPS Standard Features
Battery Cabinets
Options and Accessories
Remote Emergency Power OFF
Communications
Safety Considerations
Symbols, Controls, and Indicators
Protective Grounding Terminal
Using the Control Panel
Description
Power Management Display
Using the Control Panel
LED Indicators
Pushbutton Functions
4 ON/OFF Startup and Shutdown Pushbuttons
Description of the LCD Screen
Status Screens
LCD Display Structure and Navigation
Load OFF
Event Log Screen
Main Menu Screen
Measurements Screen
Commands Screen
UPS Data
Set-Up User
Set-Up Service
SET-UP Service Password
OFF Line Mode Bypass or Economy Mode
On Line Mode Inverter Mode
Perating Modes
Maintenance Bypass Mode
Line INV
Parallel Isolator IA2
UPS Operating Instructions
Start-Up Procedure for the UPS
Operation
LED Indicator Color
Complete Shutdown Procedure for the UPS
Load Transfer to Maintenance Bypass
Line OFF Bypass Inverter Battery
Red
This page left intentionally blank
Menu, Commands, Event Log, and Measurements
Alarms
Responding to System Events
Fault Identification and Correction
Alarm Condition Meaning Suggested Solution
Communications10
Slot Communication Modules
X-Slot Location on Front of Powerware 9335 UPS Cabinet
Single-Port Serial Card
Communication Port on the Single Port Serial Card
10-4
Options
Generator on Facility
11-2
Maintaining the UPS System
Important Safety Instructions
General
Performing Preventive Maintenance
Perform the following checks Daily
System Information
Product Specifications
UPS System Input
Environmental Specifications
UPS System Output
Appendix a Customer Information
Powerware 9335 80 kVA
Powerware 9335 120 kVA
AC Input to Phase a #6-250 kcmils Cooper 42.4 375
Table E. Maximum Input Circuit Breaker Ratings Amperes
Table F. Maximum Output Circuit Breaker Ratings Amperes
Table G. Customer Interface Inputs and Outputs
Terminal Name Description
Alarm MNS
REV a 07/11/2003
Powerware 9335 80kVA and 120 kVA
Table J. Equipment Weight
Ambient Temperature Range
Table K. System Clearances
Elements
Figure A-2. Powerware 9335 80 kVA and 120 kVA Label
2A, 2B, 2C, 2N
1A, 1B, 1C, 1N
3A, 3B, 3C, 3N
Electrical Diagram 120 kVA S06-0001ULA Powerware
NW4007
Figure A-7. UPS Cabinet Dimensions Rear View
750 mm .6 inches 700 mm .6 inches 1800 mm
Page
Page
Page
Page
Limited Factory Warranty for THREE-PHASE Powerware Products
This page left intentionally blank