Powerware 9335 operation manual Installing Customer Connections

Page 22

WARNING:

The Powerware 9335 UPS requires a neutral input power connection for proper operation. Internal input and output neutrals are permanently connected inside the cabinet.

WARNING:

An insulated grounding conductor must be provided per NEC.

4.If the installation is for a single utility feed with common rectifier and bypass input, proceed to step 7. For a separate bypass and rectifier input, proceed to step 5.

5.Remove the single feed bus bar jumper connections from between X6 and X7, Phase A, B, and C and discard them. They will not be used again.

6.Connect ground, phase A, B, C, and Neutral mains input power wiring from the source to the Mains input terminals (1A, 1B, 1C) on the In/Out Terminal Block. Phase A input connects to input terminal 1A, phase B to input terminal 1B and phase C to input terminal 1C. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information. Note wiring connections for dual feed systems.

7.Connect ground, phase A, B, C, and Neutral power wiring from the output terminals (3A, 3B, 3C) on the In/Out Terminal Block to the critical load. Output terminal 3A connects to phase A of the load, output 3B to phase B and output 3C to phase C, respectively. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information.

8.Secure the UPS by reinstalling the safety shield panels, and closing the front cabinet door, latching the cabinet door with the removable door handle.

2.2.4Installing Customer Connections

See Chapter 10, “Communications”

2.2.5Prepare for Installing Optional Accessories

NOTE: If you are installing accessories, including the Remote Emergency Power Off (REPO) switch, you must install conduit between each device and the UPS cabinet for wiring these options.

1.Be sure the UPS system is turned off and all power sources are removed. (See the operation section of this manual for shutdown instructions.)

2-4

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

 

164201396 REV A 071103

Image 22 Contents
Uninterruptible Power Supply 80 kVA 120 kVA Page Important Safety Instructions Table of Contents Using the Control Panel Operational Controls and FeaturesUnderstanding UPS Operation UPS Operating Instructions Product SpecificationsAppendix a Customer Information Warranty Responding to System EventsList of Figures Main Elements of the UPS SystemList of Tables Introduction Basic System Configurations Conventions Used in This Manual Safety Considerations Getting HelpSection Installation This page left intentionally blank Creating an Installation Plan Installing the UPSGetting Started Preparing Your Site Preparing for Wiring the UPS SystemEnvironmental Considerations Powerware 9335 80 kVA and 120 kVA UPS Packaging Inspecting and Unpacking Each Cabinet Do not tilt cabinets more than ±10 degrees from vertical Installing the UPS System Preliminary Installation InformationUPS Cabinet Installation Installing External Battery Power Wiring Installing Customer Connections Completing the Installation Checklist Battery Cabinet InstallationInitial Startup Installation Checklist Installing and Connecting Batteries Important Safety InstructionsThis page left intentionally blank Installation Procedures Installing a Remote EPO ControlTo Install a Remote EPO Remote EPO Wire Terminations To Operate a Remote EPOSection Operation This page left intentionally blank Understanding UPS Operation Looking Inside the UPS SystemREV a Normal, Battery and Bypass Modes Normal Mode Normal ModePage Bypass Mode Static BypassPage Battery Mode Battery ModePage Maintenance Bypass Mode Maintenance Bypass ModeInput Rectifier Batteries and Battery ChargerFunctional Description Boost ConverterMaintenance Bypass Static BypassOperational Controls and Features GeneralControl Panel UPS Operational ControlsSystem and Load ON/OFF UPS Standard Features Battery Cabinets Options and AccessoriesRemote Emergency Power OFF CommunicationsSafety Considerations Symbols, Controls, and Indicators Protective Grounding TerminalUsing the Control Panel DescriptionPower Management Display Using the Control PanelLED Indicators Pushbutton Functions 4 ON/OFF Startup and Shutdown PushbuttonsDescription of the LCD Screen Status ScreensLCD Display Structure and Navigation Load OFFEvent Log Screen Main Menu ScreenMeasurements Screen Commands Screen UPS Data Set-Up UserSet-Up Service SET-UP Service PasswordOFF Line Mode Bypass or Economy Mode On Line Mode Inverter ModePerating Modes Maintenance Bypass Mode Line INVParallel Isolator IA2 UPS Operating Instructions Start-Up Procedure for the UPSOperation LED Indicator Color Complete Shutdown Procedure for the UPS Load Transfer to Maintenance Bypass Line OFF Bypass Inverter BatteryRed This page left intentionally blank Menu, Commands, Event Log, and Measurements AlarmsResponding to System Events Fault Identification and Correction Alarm Condition Meaning Suggested SolutionCommunications10 Slot Communication ModulesX-Slot Location on Front of Powerware 9335 UPS Cabinet Single-Port Serial CardCommunication Port on the Single Port Serial Card 10-4 Options Generator on Facility11-2 Maintaining the UPS System Important Safety InstructionsGeneral Performing Preventive Maintenance Perform the following checks DailySystem Information Product SpecificationsUPS System Input Environmental Specifications UPS System OutputAppendix a Customer Information Powerware 9335 80 kVA Powerware 9335 120 kVA AC Input to Phase a #6-250 kcmils Cooper 42.4 375 Table E. Maximum Input Circuit Breaker Ratings Amperes Table F. Maximum Output Circuit Breaker Ratings AmperesTable G. Customer Interface Inputs and Outputs Terminal Name DescriptionAlarm MNS REV a 07/11/2003 Powerware 9335 80kVA and 120 kVA Table J. Equipment WeightAmbient Temperature Range Table K. System ClearancesElements Figure A-2. Powerware 9335 80 kVA and 120 kVA Label 2A, 2B, 2C, 2N 1A, 1B, 1C, 1N3A, 3B, 3C, 3N Electrical Diagram 120 kVA S06-0001ULA Powerware NW4007 Figure A-7. UPS Cabinet Dimensions Rear View 750 mm .6 inches 700 mm .6 inches 1800 mm Page Page Page Page Limited Factory Warranty for THREE-PHASE Powerware Products This page left intentionally blank