Powerware operation manual Powerware 9335 120 kVA

Page 81

Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9335 – 120 kVA

 

Ratings

Units

Rating 50/60 Hz

Basic unit ratings at

kVA

120

0.8 lagging PF load

kW

96

 

 

INPUT/OUTPUT

480

 

 

VOLTAGE

 

 

 

AC

AC Input to UPS Rectifier (0.95 min.PF)

Amps*

150

3 phase, 1 neutral, 1 ground

 

INPUT

Minimum conductor size *Max. amps

AWG or kcmil (ea)

4/0

A

include full load current plus battery

 

recharge current

 

 

 

AC Input to UPS Bypass - Full Load

Amps*

144

AC

Current 3 phase, 1 neutral, 1 ground

 

 

 

INPUT

Minimum conductor size (number/phase)

AWG or kcmil (ea)

4/0

B

 

 

 

 

DC Input from Ext. Battery source to

VDC (nominal)

+288 0 -288

DC

UPS

Amps*

176

INPUT

(1) positive, (1) negative, (1) mid-point

 

 

C

Minimum conductor size (number/pole)

AWG or kcmil (ea)

4/0

 

 

 

AC Output to Critical Load - Full Load

Amps*

144

AC

Current 3 phase, 1 neutral, 1 ground

 

 

 

OUTPUT

 

 

 

Minimum conductor size (number/phase)

AWG or kcmil (ea)

4/0

D

 

 

 

 

 

 

*Full

load, nominal voltage

 

Note: Refer to Figure A – 3 on system one line diagram for the bold letter callout locations.

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

A-3

164201396 REV A 07/11/2003

 

Image 81
Contents Uninterruptible Power Supply 80 kVA 120 kVA Page Important Safety Instructions Table of Contents Operational Controls and Features Using the Control PanelUnderstanding UPS Operation Appendix a Customer Information Warranty Product SpecificationsUPS Operating Instructions Responding to System EventsMain Elements of the UPS System List of FiguresList of Tables Introduction Basic System Configurations Conventions Used in This Manual Getting Help Safety ConsiderationsSection Installation This page left intentionally blank Installing the UPS Creating an Installation PlanGetting Started Preparing for Wiring the UPS System Preparing Your SiteEnvironmental Considerations Inspecting and Unpacking Each Cabinet Powerware 9335 80 kVA and 120 kVA UPS PackagingDo not tilt cabinets more than ±10 degrees from vertical Preliminary Installation Information Installing the UPS SystemUPS Cabinet Installation Installing External Battery Power Wiring Installing Customer Connections Battery Cabinet Installation Completing the Installation ChecklistInitial Startup Installation Checklist Important Safety Instructions Installing and Connecting BatteriesThis page left intentionally blank Installing a Remote EPO Control Installation ProceduresTo Install a Remote EPO To Operate a Remote EPO Remote EPO Wire TerminationsSection Operation This page left intentionally blank Looking Inside the UPS System Understanding UPS OperationREV a Normal, Battery and Bypass Modes Normal Mode Normal ModePage Static Bypass Bypass ModePage Battery Mode Battery ModePage Maintenance Bypass Mode Maintenance Bypass ModeFunctional Description Batteries and Battery ChargerInput Rectifier Boost ConverterStatic Bypass Maintenance BypassGeneral Operational Controls and FeaturesUPS Operational Controls Control PanelSystem and Load ON/OFF UPS Standard Features Remote Emergency Power OFF Options and AccessoriesBattery Cabinets CommunicationsSafety Considerations Protective Grounding Terminal Symbols, Controls, and IndicatorsDescription Using the Control PanelUsing the Control Panel Power Management DisplayLED Indicators 4 ON/OFF Startup and Shutdown Pushbuttons Pushbutton FunctionsStatus Screens Description of the LCD ScreenLoad OFF LCD Display Structure and NavigationMain Menu Screen Event Log ScreenMeasurements Screen Commands Screen Set-Up User UPS DataSET-UP Service Password Set-Up ServiceOn Line Mode Inverter Mode OFF Line Mode Bypass or Economy ModePerating Modes Line INV Maintenance Bypass ModeParallel Isolator IA2 Start-Up Procedure for the UPS UPS Operating InstructionsOperation LED Indicator Color Complete Shutdown Procedure for the UPS Line OFF Bypass Inverter Battery Load Transfer to Maintenance BypassRed This page left intentionally blank Alarms Menu, Commands, Event Log, and MeasurementsResponding to System Events Alarm Condition Meaning Suggested Solution Fault Identification and CorrectionSlot Communication Modules Communications10Single-Port Serial Card X-Slot Location on Front of Powerware 9335 UPS CabinetCommunication Port on the Single Port Serial Card 10-4 Generator on Facility Options11-2 Important Safety Instructions Maintaining the UPS SystemGeneral Perform the following checks Daily Performing Preventive MaintenanceProduct Specifications System InformationUPS System Input UPS System Output Environmental SpecificationsAppendix a Customer Information Powerware 9335 80 kVA Powerware 9335 120 kVA AC Input to Phase a #6-250 kcmils Cooper 42.4 375 Table F. Maximum Output Circuit Breaker Ratings Amperes Table E. Maximum Input Circuit Breaker Ratings AmperesTerminal Name Description Table G. Customer Interface Inputs and OutputsAlarm MNS REV a 07/11/2003 Ambient Temperature Range Table J. Equipment WeightPowerware 9335 80kVA and 120 kVA Table K. System ClearancesElements Figure A-2. Powerware 9335 80 kVA and 120 kVA Label 1A, 1B, 1C, 1N 2A, 2B, 2C, 2N3A, 3B, 3C, 3N Electrical Diagram 120 kVA S06-0001ULA Powerware NW4007 Figure A-7. UPS Cabinet Dimensions Rear View 750 mm .6 inches 700 mm .6 inches 1800 mm Page Page Page Page Limited Factory Warranty for THREE-PHASE Powerware Products This page left intentionally blank

9335 specifications

The Powerware 9335 is a robust and efficient uninterruptible power supply (UPS) designed to deliver reliable power protection for critical applications. Expanding upon Eaton's tradition of offering advanced power management solutions, the Powerware 9335 is tailored for environments that demand high availability and uptime.

One of the standout features of the Powerware 9335 is its double-conversion online topology, which ensures a continuous supply of clean and regulated power. This design operates without any transfer time to battery power, effectively protecting sensitive equipment from all types of power disturbances, including surges, sags, and outages.

The UPS is available in a range of power ratings, from 8 kVA to 40 kVA, making it versatile enough to support a variety of applications ranging from small server rooms to larger data centers. The modular architecture of the Powerware 9335 allows for seamless scalability, enabling users to add additional capacity or redundancy as their power needs evolve. This feature is particularly beneficial in dynamic environments where equipment and loads can frequently change.

Another significant characteristic of the Powerware 9335 is its high efficiency, often exceeding 94% in normal operation. This efficiency not only reduces energy costs but also minimizes heat generation, leading to lower cooling requirements. The UPS employs advanced technologies such as Intelligent Power Management and Smart APM (Adaptive Power Management) to optimize power usage, further enhancing its overall performance and reducing the total cost of ownership.

The user-friendly LCD display furnishes real-time data regarding UPS status, battery condition, and power settings, facilitating proactive management and monitoring. In addition, the unit can be monitored and managed remotely, ensuring that administrators can access critical information even when they are not on-site.

The Powerware 9335 also comes equipped with various connectivity options, including USB, serial, and SNMP for seamless integration into existing IT infrastructure. Additionally, advanced communication capabilities allow for integration with building management systems, ensuring comprehensive power management and reporting.

Safety is paramount, and the Powerware 9335 incorporates numerous features designed to protect both the UPS and connected equipment. This includes overload protection, battery health monitoring, and environmental monitoring, which collectively contribute to a resilient power protection strategy.

In summary, the Powerware 9335 is an exceptional UPS offering from Eaton, featuring high availability, scalability, efficiency, and robust management options. With its advanced technologies and features, it stands out as a premier choice for organizations seeking to safeguard their critical systems and data.