Powerware 9335 Table G. Customer Interface Inputs and Outputs, Terminal Name Description

Page 84

Table G. Customer Interface Inputs and Outputs

Terminal

Name

Description

X1

Emergency Power Off

X1 – 1 and X1 – 2 (no polarity)

X2

Generator On

X2 – 1 and X2 – 2 (no polarity)

X3

Battery temperature sensor

X3 – 1 and X3 – 2 (no polarity)

X4

Battery Shunt trip breaker control

X4 – 1 and X4 – 2 (+12V & com)

JD-1-1

Not Used

Not Used

JD-1-2

TXD

Input to UPS

JD-1-3

RXD

Output from UPS

JD-1-4

Not Used

Not Used

JD-1-5

Return

Common

JD-1-6

Not Used

Not Used

JD-1-7

Not Used

Not Used

JD-1-8

Not Used

Not Used

JD-1-9

Not Used

Not Used

JD-2-1

Utility Fail Alarm (NO)

Utility Fail Alarm

JD-2-2

Utility OK

Utility Present

JD-2-3

Common

Common

JD-2-4

Load on Inverter message (NO)

Load on inverter message

JD-2-5

Load on inverter message (NC)

Load not on inverter message

JD-2-6

Common

Common

JD-2-7

Battery Low Alarm (NO)

Battery voltage low alarm

JD-2-8

Battery OK

Battery voltage OK

JD-2-9

Common

Common

JD-2-10

Load on utility (bypass mode)

Load on utility/bypass

JD-2-11

Load on utility/bypass (NC)

Load not on utility/bypass

JD-2-12

Common

Common

JD-2-13

Common Alarm (NO)

Common alarm

JD-2-14

No alarm condition

No alarm

JD-2-15

Common

Common

JD-2-16

Not used

Not used

JD-2-17

Not used

Not used

JD-2-18

Not used

Not used

JD-2-19

Not used

Not used

JD-2-20

Not used

Not used

JD-2-21

Not used

Not used

JD-2-22

Ground

Ground

JD-2-23

+12 volts

+12 volts (Imax. = 100 ma.)

JD-2-24

Not used

Not used

JD-2-25

Not used

Not used

A-6

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

 

164201396 REV A 07/11/2003

Image 84 Contents
Uninterruptible Power Supply 80 kVA 120 kVA Page Important Safety Instructions Table of Contents Operational Controls and Features Using the Control PanelUnderstanding UPS Operation Product Specifications Appendix a Customer Information WarrantyUPS Operating Instructions Responding to System EventsList of Figures Main Elements of the UPS SystemList of Tables Introduction Basic System Configurations Conventions Used in This Manual Safety Considerations Getting HelpSection Installation This page left intentionally blank Installing the UPS Creating an Installation PlanGetting Started Preparing for Wiring the UPS System Preparing Your SiteEnvironmental Considerations Powerware 9335 80 kVA and 120 kVA UPS Packaging Inspecting and Unpacking Each CabinetDo not tilt cabinets more than ±10 degrees from vertical Installing the UPS System Preliminary Installation InformationUPS Cabinet Installation Installing External Battery Power Wiring Installing Customer Connections Battery Cabinet Installation Completing the Installation ChecklistInitial Startup Installation Checklist Installing and Connecting Batteries Important Safety InstructionsThis page left intentionally blank Installing a Remote EPO Control Installation ProceduresTo Install a Remote EPO Remote EPO Wire Terminations To Operate a Remote EPOSection Operation This page left intentionally blank Understanding UPS Operation Looking Inside the UPS SystemREV a Normal, Battery and Bypass Modes Normal Mode Normal ModePage Bypass Mode Static BypassPage Battery Mode Battery ModePage Maintenance Bypass Mode Maintenance Bypass ModeBatteries and Battery Charger Functional DescriptionInput Rectifier Boost ConverterMaintenance Bypass Static BypassOperational Controls and Features GeneralUPS Operational Controls Control PanelSystem and Load ON/OFF UPS Standard Features Options and Accessories Remote Emergency Power OFFBattery Cabinets CommunicationsSafety Considerations Symbols, Controls, and Indicators Protective Grounding TerminalUsing the Control Panel DescriptionUsing the Control Panel Power Management DisplayLED Indicators Pushbutton Functions 4 ON/OFF Startup and Shutdown PushbuttonsDescription of the LCD Screen Status ScreensLCD Display Structure and Navigation Load OFFMain Menu Screen Event Log ScreenMeasurements Screen Commands Screen UPS Data Set-Up UserSet-Up Service SET-UP Service PasswordOn Line Mode Inverter Mode OFF Line Mode Bypass or Economy ModePerating Modes Maintenance Bypass Mode Line INVParallel Isolator IA2 Start-Up Procedure for the UPS UPS Operating InstructionsOperation LED Indicator Color Complete Shutdown Procedure for the UPS Load Transfer to Maintenance Bypass Line OFF Bypass Inverter BatteryRed This page left intentionally blank Alarms Menu, Commands, Event Log, and MeasurementsResponding to System Events Fault Identification and Correction Alarm Condition Meaning Suggested SolutionCommunications10 Slot Communication ModulesX-Slot Location on Front of Powerware 9335 UPS Cabinet Single-Port Serial CardCommunication Port on the Single Port Serial Card 10-4 Options Generator on Facility11-2 Important Safety Instructions Maintaining the UPS SystemGeneral Performing Preventive Maintenance Perform the following checks DailyProduct Specifications System InformationUPS System Input Environmental Specifications UPS System OutputAppendix a Customer Information Powerware 9335 80 kVA Powerware 9335 120 kVA AC Input to Phase a #6-250 kcmils Cooper 42.4 375 Table E. Maximum Input Circuit Breaker Ratings Amperes Table F. Maximum Output Circuit Breaker Ratings AmperesTable G. Customer Interface Inputs and Outputs Terminal Name DescriptionAlarm MNS REV a 07/11/2003 Table J. Equipment Weight Ambient Temperature RangePowerware 9335 80kVA and 120 kVA Table K. System ClearancesElements Figure A-2. Powerware 9335 80 kVA and 120 kVA Label 1A, 1B, 1C, 1N 2A, 2B, 2C, 2N3A, 3B, 3C, 3N Electrical Diagram 120 kVA S06-0001ULA Powerware NW4007 Figure A-7. UPS Cabinet Dimensions Rear View 750 mm .6 inches 700 mm .6 inches 1800 mm Page Page Page Page Limited Factory Warranty for THREE-PHASE Powerware Products This page left intentionally blank