Technical Specifications

NOTE: Operating temperature has an altitude derating of 34° F per 1,000 ft (1° C per 304.8 m). No direct sunlight. Upper operating limit is 10,000 ft or 70Kpa (3,048 m or 10.1 psia). Upper non- operating limit is 30,000 ft or 30.3 KPa (9,144 m or 4.4 psia). Storage maximum humidity of 95% is based on a maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.

Operating and

Performance Specifications for Power Enclosures (North America/Japan)

 

 

Single-Phase Model

Three-Phase Model

Dimensions

Height

5.25 in (13.34 cm)

5.25 in (13.34 cm)

 

Width

17.60 in (44.7 cm)

17.60 in (44.7 cm)

 

Depth

27.15 in (68.96 cm)

27.15 in (68.96 cm)

Weights

No hot-plug power

47.5 lb (21.55 kg)

47.5 lb (21.55 kg)

 

supplies

 

 

 

All hot-plug power

99.5 lb (45.13 kg)

125.5 lb (56.93 kg)

 

supplies

 

 

Input requirements

Rated input voltage

200 VAC to 240 VAC

200 VAC to 240 VAC

 

 

 

line to line

 

Rated input frequency

50 Hz to 60 Hz

50 Hz to 60 Hz

 

Rated input current per

24A

24A per phase

 

side

 

 

 

Rated input power per

5760 W

9976 W

 

side

 

 

 

Power cord

1 IEC 309 3-pin, 32A

1 IEC 309 5-pin, 32A

 

 

per side

per side

Output voltage

Rated output voltage

-48.8 VDC to -54 VDC

-48.8 VDC to -54 VDC

specifications

Rated output current

99A

170A

 

Rated output power

4298 W

8310 W

 

Nominal Power

4158 W at 208 VAC

7202 W at 208 VAC

Ambient Temperature

Operating

50° to 95° F

50° to 95° F

Range (see NOTE)

 

(10° to 35° C)

(10° to 35° C)

 

Shipping

-22° to 140° F

-22° to 140° F

 

 

(-30° to 60° C)

(-30° to 60° C)

Relative Humidity non- Operating

20% to 80%

20% to 80%

condensing (see NOTE) Non-operating

5% to 95%

5% to 95%

Wet Bulb Temperature Operating

82.4° F (28° C)

82.4° F (28° C)

 

Non-operating

101.7° F (38.7° C)

101.7° F (38.7° C)

NOTE: Operating temperature has an altitude derating of 34° F per 1,000 ft (1° C per 304.8 m). No direct sunlight. Upper operating limit is 10,000 ft or 70Kpa (3,048 m or 10.1 psia). Upper non- operating limit is 30,000 ft or 30.3 KPa (9,144 m or 4.4 psia). Storage maximum humidity of 95% is based on a maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.

DA - 11411 Worldwide QuickSpecs — Version 24 — 9.24.2004

Page 31

Image 31
Contents Overview 42U Rack with ProLiant BL p-Class System InstalledProLiant BL p-Class Server Blade Enclosure ProLiant BL p-Class Power EnclosureProLiant BL p-Class Power Distribution ProLiant BL20p Server Blade includesQuickSpecs QuickSpecs Configuration Steps QuickSpecs Standard Features Server Blade ProLiant BL p-Class Server Blade Enclosure and Interconnects ProLiant BL p-Class Interconnect Switch Option Standard Features Server Blade Enclosure and InterconnectsCabling Required NetworkStandard Features Power System and Rack Information Standard Features OS Support SmartStartIntelligent Security AvailabilityRequirements Minimum RackRack Airflow QuickSpecs Models Options OptionsCommunications Storage ControllersBlade Enclosures BL p-Class ServerUSB Options BL p-Class Power OptionsPower Distribution Diagnostic OptionsHP Rack 10000 Series Custom BuilderOptions/index.html Rack Options for HP Rack 10000 SeriesCountry Code Keyfor 1U Rack Keyboard & Drawer PN Service and Support Offerings HP CareInstallation & Start-up Services Standard Memory Plus Optional Memory MemoryStandard Memory Replaced with Optional Memory Technical Specifications Power Requirements Operating DimensionsSpecifications for RJ ConnectorNon-condensing SafetyForwarding table age Input requirements WeightsSpecifications Ambient TemperatureRated operating Power Enclosures WeightsSupported enclosures Dimensions RangeAt minimum voltage Max total powerMax current per power Supported Total max input current 69.44 a at -43.2VDCQuickSpecs