Server Technology BL20P manual Minimum Rack, Requirements, Rack Airflow

Page 15

QuickSpecs

HP ProLiant BL20p p-Class Server Blade

Standard Features

Minimum Rack

Mounts in Compaq/HP, Telco racks and Third Party racks that meet the following criteria:

Requirements

Compatible with 19-inch Standard EIA rail sets

 

 

EIA rail-to-rail depth is 29 - 30"

 

Cabinet depth must be at least 36-inch deep overall (Additional min. 3.5-inch clearance from

 

rear RETMA rail to rear door, inclusive in the 36-inch overall depth)

 

Ample room for top and bottom cable egress (approximately 8 square inches for full rack

 

configuration with patch panel)

 

Must be capable of supporting 1600 lb (for full rack configuration)

 

Perforated front and rear doors to accommodate front-to-back cooling

 

Must have 65% open perforation on server blade enclosure doors to support airflow

 

requirements

 

Optimized for use with the HP 10000 Series racks

 

NOTE: If using HP 7000 Series rack, Rack Extension Kit and High Air Flow Rack Door options are

 

required.

 

 

 

Rack Airflow

Rack 9000 and 10000 series Cabinets

Requirements

The increasing power of new high-performance processor technology requires increased

 

cooling efficiency for rack-mounted servers. The 9000 Series and the 10000 Series Racks

 

provide enhanced airflow for maximum cooling, allowing these racks to be fully loaded with

 

servers using the latest processors.

 

Rack 7000 series Cabinets

 

When installing a server with processors running at speeds of 550 MHz or greater in Rack

 

7000 series racks with glass doors (165753-001 (42U), and 163747-001 (22U)), the new

 

processor technology requires the installation of the High Airflow Rack Door Inserts

 

(327281-B21 (42U), 327281-B22 (42U 6 pack), or 157847-B21 (22U)) to promote enhanced

 

airflow for maximum cooling.

 

CAUTION: If a third-party rack is used, observe the following additional requirements to ensure

 

adequate airflow and to prevent damage to the equipment:

 

Front and rear doors: If your 42U server rack includes closing front and rear doors,

 

you must allow 830 square inches (5,350 sq cm) of hole evenly distributed from top to

 

bottom to permit adequate airflow (equivalent to the required 64 percent open area for

 

ventilation).

 

Side: The clearance between the installed rack component and the side panels of the

 

rack must be a minimum of 2.75 inches (7 cm).

 

CAUTION: Always use blanking panels to fill all remaining empty front panel U-spaces in the rack.

 

This arrangement ensures proper airflow. Using a rack without blanking panels results in improper

 

cooling that can lead to thermal damage.

 

NOTE: For additional information, refer to the Setup and Installation Guide or the Documentation

 

CD provided with the server, or to the server documentation located in the Support section at the

 

following URL: http://wwss1pro.compaq.com/support/home/index.asp

 

 

 

DA - 11411 Worldwide QuickSpecs — Version 24 — 9.24.2004

Page 15

Image 15
Contents Overview 42U Rack with ProLiant BL p-Class System InstalledProLiant BL p-Class Server Blade Enclosure ProLiant BL p-Class Power EnclosureProLiant BL p-Class Power Distribution ProLiant BL20p Server Blade includesQuickSpecs QuickSpecs Configuration Steps QuickSpecs Standard Features Server Blade ProLiant BL p-Class Server Blade Enclosure and Interconnects ProLiant BL p-Class Interconnect Switch Option Standard Features Server Blade Enclosure and InterconnectsCabling Required NetworkStandard Features Power System and Rack Information Standard Features SmartStart OS SupportIntelligent Security AvailabilityMinimum Rack RequirementsRack Airflow QuickSpecs Models Options OptionsCommunications Storage ControllersBlade Enclosures BL p-Class ServerUSB Options BL p-Class Power OptionsPower Distribution Diagnostic OptionsHP Rack 10000 Series Custom BuilderOptions/index.html Rack Options for HP Rack 10000 SeriesCountry Code Keyfor 1U Rack Keyboard & Drawer PN Service and Support Offerings HP CareInstallation & Start-up Services Memory Standard Memory Plus Optional MemoryStandard Memory Replaced with Optional Memory Technical Specifications Power Requirements Operating DimensionsSpecifications for RJ ConnectorNon-condensing SafetyForwarding table age Input requirements WeightsSpecifications Ambient TemperatureRated operating Power Enclosures WeightsSupported enclosures Dimensions RangeAt minimum voltage Max total powerMax current per power Supported Total max input current 69.44 a at -43.2VDCQuickSpecs