Server Technology BL20P Power Enclosures Weights, Range, Supported enclosures Dimensions, Voltage

Page 32

QuickSpecs

HP ProLiant BL20p p-Class Server Blade

Technical Specifications

Operating and

Dimensions

Height

5.25 in (13.34 cm)

5.25 in (13.34 cm)

Performance

 

Width

17.60 in (44.7 cm)

17.60 in (44.7 cm)

Specifications for

 

Depth

27.15 in (68.96 cm)

27.15 in (68.96 cm)

Power Enclosures

 

Weights

No hot-plug power

47.5 lb (21.55 kg)

47.5 lb (21.55 kg)

(International)

 

 

supplies

 

 

 

 

all hot-plug power

99.5 lb (45.13 kg)

125.5 lb (56.93 kg)

 

 

supplies

 

 

 

Input requirements

Rated input voltage

200 VAC to 240 VAC

6.25 A at -48 VDC

 

 

 

 

200 VAC to 240 VAC

 

 

 

 

line to neutral

 

 

Rated input Frequency

50 Hz to 60 Hz

50 Hz to 60 Hz

 

 

Rated input current

24A

20A per phase

 

 

Rated input power

5760 W

10,552 W

 

 

Powercord

1 IEC 309 3-pin, 32A

1 IEC 309 5-pin, 32A

 

 

 

per side

per side

 

Output Voltage

Related output voltage

-48.8 VDC to -54 VDC

-48.8 VDC to -54 VDC

 

Specifications

Related output current

99A

180A

 

 

Related output power

4798 W

8790 W

 

 

Nominal power

4598 W at 208 VAC

8790 W at 230 VAC L-

 

 

 

 

N

 

Ambient Temperature

Operating

50° to 95° F

50° to 95° F

 

Range

 

(10° to 35° C)

(10° to 35° C)

 

 

Non-operating

-22° to 140° F

-22° to 140° F

 

 

 

(-30° to 60° C)

(-30° to 60° C)

 

Relative Humidity

Operating

20% to 80%

20% to 80%

 

(non-condensing)

Non-operating

5% to 95%

5% to 95%

 

Maximum Wet Bulb

Operating

82.4° F (28° C)

82.4° F (28° C)

 

Temperature

Non-operating

101.7° F (38.7° C)

101.7° F (38.7° C)

NOTE: Operating temperature has an altitude derating of 34° F per 1,000 ft (1° C per 304.8 m). No direct sunlight. Upper operating limit is 10,000 ft or 70Kpa (3,048 m or 10.1 psia). Upper non- operating limit is 30,000 ft or 30.3 KPa (9,144 m or 4.4 psia). Storage maximum humidity of 95% is based on a maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.

Operating and

 

Power Bus Box

Mini Bus Bar

Scalable Bus Bar

Performance

Power enclosure or

1

1

2

Specifications for

facility DC supported

 

 

 

Power Distribution

(3U each)

 

 

 

Devices

Server blade

1

3

6

 

 

enclosures

 

 

 

 

Total rack height of

9U

21U

36U

 

supported enclosures

 

 

 

 

Dimensions

 

 

 

 

Height

5.1 in (12.95 cm)

19.45 in (49.40 cm)

48.57 in (123.37 cm)

 

Width

3.6 in (9.14 cm) each

19.74 in (50.14 cm)

19.74 in (50.14 cm)

 

Depth

3.25 in (8.26 cm)

2.2 in (5.59 cm)

2.2 in (5.59 cm)

 

Weight

3.62 lb (1.64 kg )

13.2 lb (5.9 kg)

26 lb (11.79 kg)

 

Rated operating

-43.2 VDC to -54 VDC

43.2 VDC to -54 VDC

-43.2 VDC to -54 VDC

 

voltage

 

 

 

DA - 11411 Worldwide QuickSpecs — Version 24 — 9.24.2004

Page 32

Image 32
Contents 42U Rack with ProLiant BL p-Class System Installed OverviewProLiant BL p-Class Power Enclosure ProLiant BL p-Class Power DistributionProLiant BL20p Server Blade includes ProLiant BL p-Class Server Blade EnclosureQuickSpecs QuickSpecs Configuration Steps QuickSpecs Standard Features Server Blade ProLiant BL p-Class Server Blade Enclosure and Interconnects Standard Features Server Blade Enclosure and Interconnects ProLiant BL p-Class Interconnect Switch OptionRequired Network CablingStandard Features Power System and Rack Information Standard Features Intelligent SmartStartOS Support Availability SecurityRack Airflow Minimum RackRequirements QuickSpecs Models Options OptionsStorage Controllers CommunicationsBL p-Class Server Blade EnclosuresBL p-Class Power Options Power DistributionDiagnostic Options USB OptionsCustom Builder HP Rack 10000 SeriesRack Options for HP Rack 10000 Series Options/index.htmlService and Support Offerings HP Care Country Code Keyfor 1U Rack Keyboard & Drawer PNInstallation & Start-up Services Standard Memory Replaced with Optional Memory MemoryStandard Memory Plus Optional Memory Technical Specifications Operating Dimensions Specifications for RJConnector Power RequirementsSafety Non-condensingForwarding table age Weights SpecificationsAmbient Temperature Input requirementsPower Enclosures Weights Supported enclosures DimensionsRange Rated operatingMax total power Max current per powerSupported Total max input current 69.44 a at -43.2VDC At minimum voltageQuickSpecs