QuickSpecs
HP ProLiant BL20p
Technical Specifications
| Max total power |
| 3000 W | 9000 W | 15,000 W |
| supported |
|
|
|
|
| Total max input current69.44 A at | 208.32 A at | |||
| at minimum voltage |
|
|
| (equivalent of 175A |
|
|
|
|
| per feed) |
| Total max input current62.5 A at | 187.5 A at | 312.5 A at | ||
| at nominal voltage |
|
|
| (equivalent of 175A |
|
|
|
|
| per feed) |
| Max current per power | 70A | 210A | 210A | |
| feed |
|
|
|
|
| Max local ambient |
| 149° F (65° C) | 149° F (65° C) |
|
| temperature |
|
|
|
|
| NOTE: All systems support redundant A & B feeds. Scalable bus bar supports dual A and dual B | ||||
| feeds. |
|
|
|
|
|
|
|
|
| |
Operating and | Voltage | Nominalinput voltage |
| ||
Performance |
| Operating voltage range | |||
Specifications for |
| Max input voltage slew | 0.5V/uS |
| |
Facility DC |
|
| |||
| rate |
|
|
| |
|
|
|
|
| |
|
| Redundant feed voltages* | *A and B feeds must differ by no more than | ||
|
|
|
| 5VDC during steady state operation | |
|
| Ripple/Noise | 480 mV PARD** |
| |
|
| Overshoot | Must remain within regulation limits on all | ||
|
|
|
| feeds during startup or shutdown | |
|
| Voltage Transients | Must not exceed | ||
| Current | Max steady state input | 62.5A per server blade enclosure installed at | ||
|
| current |
| ||
|
| Max steady state current |
|
| |
|
| per feed/total |
|
| |
|
|
| Power bus boxes | 70 A/70A |
|
|
|
| Mini bus bars | 210 A/210A |
|
|
|
| Scalable bus bars | 210 A/350A or equivalent of 175A per feed* | |
|
| Must support up to 2X the maximum operating current per server blade | |||
|
| enclosure (125 A) for up to 1.0 mS |
| ||
| Input | Customer provided fusing for facility DC feeds that protects the system | |||
|
| from catastrophic | |||
|
| rush and operating currents. |
| ||
| Max Input Current | 1A/uS |
|
| |
| Slew Rate |
|
|
|
|
Max Input Curent Slew 3000W per server blade enclosure
Rate
Connection and Cables
HP provided facility DC cable connection kit:
The facility DC connection kit supports the connection of up to four
The power cable assemblies consist of 1/0AWG,
NOTE: *All systems support redundant A and B feeds. Scalable bus bars support dual A and dual B feeds.
** Periodic and random noise (PARD). Maximum allowable
DA - 11411 Worldwide QuickSpecs — Version 24 — 9.24.2004 | Page 33 |