Display | Alarm | Fault | Meaning | Corrective Actions | |
|
|
| DC Bus Fuse Open | • Check the motor and the motor cables for | |
PUF |
| | The fuse in the main circuit is blown. | short circuits or insulation failures (phase- | |
| Warning: | ||||
DC Bus Fuse Open |
| ||||
|
| PG (encoder) pulses have not been received for | • Replace the inverter after correcting the | ||
|
|
| |||
|
|
| a time longer than the setting in | fault. | |
|
|
|
|
| |
RR |
| | Dynamic Braking Transistor | • Cycle power to the inverter. | |
DynBrk Transistr |
|
| The | • Replace the inverter. | |
|
|
| The DC bus voltage is below the Undervoltage | • Check the input voltage. | |
| |
| Detection Level | • Check the wiring of the input terminals. | |
UV1 | (only in |
| • Check the input voltage and the wiring of | ||
| 200V class: 190 VDC | the input terminals. | |||
stop | |||||
DC Bus Undervolt | |||||
condi- |
| 400 V class: 380 VDC | • Extend the settings in | ||
|
| ||||
| tio) |
|
|
| |
|
| Main Circuit MC Operation Failure | Replace the Inverter. | ||
|
|
| No MC response during Inverter operation. | ||
|
|
|
| ||
|
|
|
|
| |
UV2 |
| | Control Power Supply Undervoltage | • Remove all connection to the control termi- | |
| Undervoltage of the control circuit while the | nals and cycle the power to the Inverter. | |||
CTL PS Undervolt |
| ||||
|
| Inverter was running. | • Replace the Inverter. | ||
|
|
| |||
|
|
|
|
|
Operator Programming Errors
An Operator Programming Error (OPE) occurs when two or more parameter related to each other are set inappropriately or an individual parameter setting is incorrect. The Inverter does not operate until the parameter setting is corrected; however, no other alarm or fault output will occur. If an OPE occurs, change the related parameter by checking the cause shown in the table below. When an OPE error is displayed, press the ENTER key to see
Display | Meaning | Corrective Actions | |
OPE01 | Inverter kVA Setting Error | Enter the correct kVA setting in | |
kVA Selection | |||
|
| ||
|
|
| |
OPE02 | Parameter setting is out of its range | Verify the parameter settings. | |
Limit | |||
|
| ||
|
|
| |
| One of the following errors has been made in the multi- |
| |
| function input |
| |
| • Duplicate functions were selected. |
| |
| • UP/DOWN Command(10 and 11) were not selected |
| |
| simultaneously. |
| |
| • The up/down commands (10 and 11) and Accel/ |
| |
| Decel Ramp Hold (A) were selected at the same |
| |
| time. |
| |
| • More than one of the Speed Search inputs (61, 62, |
| |
OPE03 | 64) were set simultaneously. | Verify the parameter settings in | |
Terminal | • External Baseblock NO (8) and External Baseblock | ||
| |||
| NC (9) were selected at the same time. |
| |
| • The up/down commands (10 and 11) were selected |
| |
| while PID Control was enabled. |
| |
| • The Emergency Stop Command NO (15) and NC(17) |
| |
| are set simultaneously. |
| |
| • PID is enabled and UP and/or DOWN (10 / 11) com- |
| |
| mand are set. |
| |
| • HSB (68) and KEB (65/66) command are set simulta- |
| |
| neously. |
| |
|
|
| |
| RUN/Reference Command Selection Error | • Verify that the board is installed. Remove the power | |
OPE05 | The Reference Source Selection | ||
Sequence Select | Source Selection parameter | supply and | |
• Recheck the setting of | |||
| board) but no option board is installed. |
| |
| Control Method Selection Error |
| |
OPE06 | One of the control methods needing a PG feedback | Verify the control method selection in parameter | |
PG Opt Missing | was selected | and/or the installation of the PG option board. | |
| not installed. |
| |
|
|
|