Omron Healthcare VARISPEEDF7 specifications EN-22, OH1, OL1, OL2, Pgo

Page 23

Display

Alarm

Fault

Meaning

 

Corrective Actions

 

 

 

 

Remove the motor and run the Inverter

 

 

 

 

 

without the motor.

OC

 



Over Current

Check the motor for a phase-to-phase

 

The Inverter’s output current exceeded the over-

 

short.

Over Current

 

 

 

 

current detection level.

Verify the accel/decel times (C1-††).

 

 

 

 

 

 

 

Check the Inverter for a phase-to-phase

 

 

 

 

 

short at the output.

 

 

 

 

 

 

 

 

 

Heatsink Overheat

Check for dirt build-up on the fans or heat-

 

 



L8-03 = 0,1 or 2 and the temperature of the

 

 

 

sink.

OH

 

Inverter's cooling fin exceeded the L8-02 value.

 

 

 

 

Reduce the ambient temperature around

 

 

Inverter's Cooling Fan Stopped

Heatsnk Overtemp

 

 

 

the drive.

 

 

 

 

 

 

L8-03 = 3 or 4 and the temperature of the

 

 



 

Replace the cooling fan(s).

 

 

Inverter's cooling fin exceeded the L8-02 value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heatsink Overheat

Check for dirt build-up on the fans or heat-

OH1

 



The temperature of the Inverter’s heatsink

 

sink.

 

exceeded 105 °C.

Reduce the ambient temperature around

Heatsink Max Temp

 

 

 

 

 

the drive.

 

 

 

Inverter’s Cooling Fan Stopped

 

 

 

 

Replace the cooling fan(s).

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Overload

 

 

 

 

 

Detected when L1-01 is set to 1,2 or 3 and the

Recheck the cycle time and the size of the

 

 

 

Inverter’s I²t value exceeded the motor overload

 

load as well as the accel/decel times (C1-

 

 

 

curve.

 

OL1

 



 

††).

 

The overload curve is adjustable using parame-

Motor Overload

 

 

ter

Check the V/f characteristics (E1-††).

 

 

 

Check the setting of Motor Rated Current

 

 

 

E2-01 (Motor Rated Current), L1-01 (Motor Pro-

 

 

 

tection Selection) and L2-02 (Motor Protection

 

Setting (E2-01).

 

 

 

 

 

 

 

 

Time Constant)

 

 

 

 

 

 

 

 

 

 

 

 

Recheck the cycle time and the size of the

 

 

 

Inverter Overload

 

load as well as the accel/decel times (C1-

OL2

 



 

††).

 

The Inverter output current exceeded the Invert-

Inv Overload

 

 

ers’s overload capability

Check the V/f Characteristics (E1-††).

 

 

 

Check if the inverter rated current matches

 

 

 

 

 

 

 

 

 

the motor rated current.

 

 

 

 

 

 

 

 

 

F1-03 = 0, 1 or 2 and A1-02 = 1 or 3

 

 

 

 



The motor speed feedback (U1-05) exceeded

 

 

 

 

the setting in F1-08 for a time longer than the

Adjust the ASR settings in the C5 parame-

 

 

 

setting of

 

 

 

 

ter groupt

OS

 

 

F1-09

 

 

 

Check the reference circuit and reference

Overspeed Det.

 

 

 

 

 

F1-03 = 3 and A1-02 = 1 or 3

 

 

 

gain.

 

 

 

The motor speed feedback (U1-05) exceeded

 

 



 

Check the settings in F1-08 and F1-09

 

 

the setting in F1-08 for a time longer than the

 

 

 

 

 

 

 

setting of

 

 

 

 

 

F1-09

 

 

 

 

 

 

 

 

 



 

The DC bus voltage has exceeded the overvolt-

Increase the deceleration time (C1-02/04)

 

 

age detection level.

 

or connect a braking option.

OV

(only in



Check the power supply and decrease the

stop

Default detection levels are:

DC Bus Overvolt

 

voltage to meet the inverter’s specifica-

condi-

 

200 V class: 410 VDC

 

 

 

 

tions.

 

tio)

 

400 V class: 820 VDC

 

 

 

Check the braking chopper / resistor.

 

 

 

 

 

 

 

 

 

 

PF

 



Input Phase Loss

Tighten the input terminal screws

 

Too big DC bus voltage ripple.

Input Phase Loss

 

Check the power supply voltage

 

 

Only detected when L8-05=1 (enabled)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PG Disconnection

 

 

 

 

 

Detected when F1-02 = 0, 1 or 2 and A1-02 = 1

 

 

 

 



or 3.

Fix the broken/disconnected wiring.

 

 

 

Detected when no PG (encoder) pulses have

Supply power to the PG properly.

PGO

 

 

been received for a time longer than the setting

PG Open

 

 

in F1-14.

Check the sequence and if the brake is

 

 

 

opened when the inverter starts to increase

 

 

 

 

 

 

 

 

PG Disconnection

 

 

 

 

 

the speed.

 

 

 

Detected when F1-02 = 3 and A1-02 = 1 or 3.

 

 



 

 

 

 

 

PG (encoder) pulses have not been received for

 

 

 

 

 

 

 

 

 

 

a time longer than the setting in F1-14.

 

 

 

 

 

 

 

 

EN-22

Image 23
Contents VARISPEED F7 F7Z Quick Start Guide Table of Contents EN-2 EN-3 ‹ Safety Precautions and Instructions„ Notes EN-4‹ EMC Compatibility „ Electrical ConnectionEarthing the cable shield with metal clips EN-5„ Laying Cables „ Unpacking the Inverter ‹ Mechanical Installation„ Checking the Installation Site EN-6EN-7 „ Installation Orientation„ Installation of Inverters and EMC filters EN-8 ‹ Electrical Connection „Wiring the InverterWiring Diagram „Control Circuit Terminals EN-9„Main Circuit Terminals Flywheel Diode Connection EN-10During run no Closed during Run Function EN-11 „ Sinking/Sourcing Mode NPN/PNP SelectionSinking / Sourcing Mode and Input Signals External Power Source Sinking Mode NPNInput Fuse Selection ‹ Wiring Main Circuit InputsEN-12 EN-13 „Wiring the Output Side of the Main Circuit„Control Circuit Wiring Precautions Ground Wiring„Digital Operator Keys EN-14‹ Digital Operator Display optional EN-15 ‹ Start Up Procedure„ Setting the Autotuning Mode ‹ Before Power Up‹ Display after Power Up ‹ AutotuningEN-17 „Other Alarms and Faults During AutotuningEN-18 User ParameterVbase EN-19Fmax VmaxLimit only OLV and CLV EN-20EN-21 ‹ General Faults and AlarmsOL2 EN-22OH1 OL1EN-23 ‹ Operator Programming ErrorsOPE08 ‹ Autotuning FaultsEN-24

VARISPEEDF7 specifications

The Omron Healthcare VARISPEEDF7 is an innovative and advanced medical device designed to provide effective therapy for various health conditions. This cutting-edge device is part of Omron’s commitment to enhancing healthcare solutions and promoting patient well-being through technology. The VARISPEEDF7 is particularly notable for its versatility and effectiveness in various therapeutic applications.

One of the main features of the VARISPEEDF7 is its adjustable speed settings. This allows healthcare professionals to customize the therapy according to the specific needs of each patient. The ability to vary speed enhances treatment effectiveness, as different conditions may require different intensities. The device is designed to accommodate a wide range of therapeutic needs, making it a valuable tool in clinical and home healthcare settings alike.

The VARISPEEDF7 integrates several advanced technologies, including its proprietary motor control system. This system provides smooth and consistent operation, minimizing disruptions during therapy sessions. The technology ensures precise speed control, enabling healthcare providers to maintain optimal conditions for therapy.

In addition to its speed control, the VARISPEEDF7 is equipped with a user-friendly interface. The display provides clear information about settings and progress, making it easy for both healthcare professionals and patients to monitor treatment sessions. The intuitive design reduces the learning curve and enhances the overall user experience.

Another significant characteristic of the VARISPEEDF7 is its portability. The compact design allows for easy transport and storage, making it ideal for patients who require therapy at home or on the go. This feature is particularly beneficial for individuals with mobility issues or those who enjoy an active lifestyle.

Durability is also a hallmark of the VARISPEEDF7. It is built with high-quality materials that ensure longevity and reliability, even with frequent use. This commitment to durability highlights Omron’s dedication to providing healthcare solutions that practitioners and patients can trust.

In summary, the Omron Healthcare VARISPEEDF7 represents a significant advancement in therapeutic technology. With its adjustable speed settings, advanced motor control system, user-friendly interface, portability, and durability, the VARISPEEDF7 is designed to meet the diverse needs of patients and healthcare providers. It stands out as a versatile solution that enhances patient care and promotes effective treatment outcomes. As healthcare continues to evolve, the VARISPEEDF7 exemplifies how innovative technologies can make a substantial impact on health and well-being.