Page 25

Display

Meaning

Corrective Actions

 

Function Selection Error

 

OPE08

A setting has been made that is applicable with the cur-

 

rent control method.

Verify the control method and the function.

Constant Selection

 

Example: A function used only with open loop vector

 

 

control was selected for V/f control.

 

 

 

 

OPE010

V/f Parameter Setting Error

Check parameters (E1-††). A frequency/voltage value

V/f Ptrn Setting

may be set higher than the maximum frequency/voltage.

 

 

 

 

‹Autotuning Faults

Autotuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and the motor coasts to stop. No fault or alarm outputs will be operated.

Display

Meaning

Corrective Actions

 

 

• Check the input data.

Er-01

Motor data fault

• Check the Inverter and motor capacity.

Fault

• Check the motor rated current and no-load current set-

 

 

 

ting.

 

 

 

Er-02

 

• Check the input data.

Alarm

• Check wiring and the machine.

Minor Fault

 

• Check the load.

 

 

 

 

 

Er-03

STOP key input

-

STOP key

 

 

 

 

 

Er-04

Line-to-Line Resistance Fault

 

Autotuning result is outside the parameter setting

 

Resistance

 

range.

• Check the input data.

 

Er-05

No-Load Current Fault

• Check the motor wiring.

Autotuning result is outside the parameter setting

• If the motor is connected to the machine, disconnect it.

No-Load Current

 

range.

• If the setting of T1-03 is higher than the Inverter input

 

 

power supply voltage (E1-01), change the input data.

Er-08

Rated Slip Fault

Autotuning result is outside the parameter setting

 

Rated slip

 

range.

 

 

 

 

 

 

Er-09

Acceleration Fault (Rotating autotuning only)

• Increase C1-01(Acceleration time)

The motor did not accelerate in the specified time

• Increase L7-01 and L7-02 (Torque limits)

Accelerate

(C1-10+10sec.)

• If the motor is connected to the machine, disconnect it.

 

 

 

 

 

Motor Speed Fault (Rotating autotuning only)

• If the motor is connected to the machine, disconnect it.

Er-11

The torque reference exceeded 100% during accel-

• Increase C1-01

Motor Speed

eration. Deteceted only when A1-02 = 2 or 3 (Vector

• Check the input data (particularly the number of PG

 

control modes).

pulses and the number of motor poles)

 

 

 

Er-12

Current Detection Fault

 

• The current exceeded the motor rated current.

Check wiring of the Inverter and the mounting.

I-det. Circuit

• Any of U/T1, V/T2 and W/T3 has open-phase.

 

 

 

 

 

 

Er-13

Leakage Inductance Fault

 

Leakage Induc-

Autotuning result is outside the parameter setting

Check motor wiring.

tance Fault

range.

 

 

 

 

 

Rated Current Setting Alarm

 

End-1

Displayed after auto-tuning is complete

Check the motor rated current value.

V/f Over Setting

During auto-tuning, the measured value of motor

 

 

rated current (E2-01) was higher than the set value.

 

 

 

 

End-2

Motor Core Saturation Alarm

• Check the input data

• Check the motor wiring.

Saturation

(only for rotating autotuning)

• If the motor is connected to the machine, disconnect it.

 

 

 

 

 

End-3

Rated Current Setting Alarm

 

During autotuning the measured value of motor rated

Check the motor rated current value

Rated FLA Alm

current (E2-01) was greater than the set value.

 

 

 

 

 

 

EN-24

Image 25
Contents VARISPEED F7 F7Z Quick Start Guide Table of Contents EN-2 EN-3 ‹ Safety Precautions and Instructions‹ EMC Compatibility EN-4„ Electrical Connection „ Notes„ Laying Cables EN-5Earthing the cable shield with metal clips „ Checking the Installation Site ‹ Mechanical InstallationEN-6 „ Unpacking the Inverter„ Installation of Inverters and EMC filters „ Installation OrientationEN-7 Wiring Diagram ‹ Electrical Connection „Wiring the InverterEN-8 „Main Circuit Terminals EN-9„Control Circuit Terminals During run no Closed during Run Function EN-10Flywheel Diode Connection Sinking / Sourcing Mode and Input Signals „ Sinking/Sourcing Mode NPN/PNP SelectionExternal Power Source Sinking Mode NPN EN-11EN-12 ‹ Wiring Main Circuit InputsInput Fuse Selection „Control Circuit Wiring Precautions „Wiring the Output Side of the Main CircuitGround Wiring EN-13‹ Digital Operator Display optional EN-14„Digital Operator Keys EN-15 ‹ Start Up Procedure‹ Display after Power Up ‹ Before Power Up‹ Autotuning „ Setting the Autotuning ModeEN-17 „Other Alarms and Faults During AutotuningEN-18 User ParameterFmax EN-19Vmax VbaseLimit only OLV and CLV EN-20EN-21 ‹ General Faults and AlarmsOH1 EN-22OL1 OL2EN-23 ‹ Operator Programming ErrorsEN-24 ‹ Autotuning FaultsOPE08

VARISPEEDF7 specifications

The Omron Healthcare VARISPEEDF7 is an innovative and advanced medical device designed to provide effective therapy for various health conditions. This cutting-edge device is part of Omron’s commitment to enhancing healthcare solutions and promoting patient well-being through technology. The VARISPEEDF7 is particularly notable for its versatility and effectiveness in various therapeutic applications.

One of the main features of the VARISPEEDF7 is its adjustable speed settings. This allows healthcare professionals to customize the therapy according to the specific needs of each patient. The ability to vary speed enhances treatment effectiveness, as different conditions may require different intensities. The device is designed to accommodate a wide range of therapeutic needs, making it a valuable tool in clinical and home healthcare settings alike.

The VARISPEEDF7 integrates several advanced technologies, including its proprietary motor control system. This system provides smooth and consistent operation, minimizing disruptions during therapy sessions. The technology ensures precise speed control, enabling healthcare providers to maintain optimal conditions for therapy.

In addition to its speed control, the VARISPEEDF7 is equipped with a user-friendly interface. The display provides clear information about settings and progress, making it easy for both healthcare professionals and patients to monitor treatment sessions. The intuitive design reduces the learning curve and enhances the overall user experience.

Another significant characteristic of the VARISPEEDF7 is its portability. The compact design allows for easy transport and storage, making it ideal for patients who require therapy at home or on the go. This feature is particularly beneficial for individuals with mobility issues or those who enjoy an active lifestyle.

Durability is also a hallmark of the VARISPEEDF7. It is built with high-quality materials that ensure longevity and reliability, even with frequent use. This commitment to durability highlights Omron’s dedication to providing healthcare solutions that practitioners and patients can trust.

In summary, the Omron Healthcare VARISPEEDF7 represents a significant advancement in therapeutic technology. With its adjustable speed settings, advanced motor control system, user-friendly interface, portability, and durability, the VARISPEEDF7 is designed to meet the diverse needs of patients and healthcare providers. It stands out as a versatile solution that enhances patient care and promotes effective treatment outcomes. As healthcare continues to evolve, the VARISPEEDF7 exemplifies how innovative technologies can make a substantial impact on health and well-being.