motor parameters will be set automatically. The remaining motor parameters will be set automati- cally during the first time operation.
Non-rotating Autotuning for Line-to-Line Resistance (T1-01 = 2)
It can be used to improve the performance when the motor cable is long, the cable length has changed or when the motor and inverter have different capacities.
To perform autotuning in V/f control or V/f control with PG, set
|
| 1. | Power will be supplied to the motor during autotuning but the motor will not turn. Do not touch the motor |
|
|
| until autotuning has been completed. |
IMPORTANT |
| 2. | Ensure that all motor contactors are closed before the autotuning is started. |
| 3. | To cancel autotuning press the STOP key on the Digital Operator. | |
|
| ||
|
|
|
|
Other Alarms and Faults During Autotuning
For an overview of possible autotuning alarms or faults and corrective actions refer to page 24, Auto-
tuning Faults.