Non-rotating Autotuning for Line-to-Line Resistance (T1-01 = 2)

Non-rotating autotuning for line-to-line resistance can be used in any control mode. This is the only possible autotuning for V/f control and V/f control with PG.

It can be used to improve the performance when the motor cable is long, the cable length has changed or when the motor and inverter have different capacities.

To perform autotuning in V/f control or V/f control with PG, set T1-02 (Motor rated power) and T1-04 (Motor rated current) and then press the RUN key on the Digital Operator. The Inverter will supply power to the non-rotating motor for approximately 20 seconds and the Motor line-to-line resistance and cable resistance will be automatically measured.

 

 

1.

Power will be supplied to the motor during autotuning but the motor will not turn. Do not touch the motor

 

 

 

until autotuning has been completed.

IMPORTANT

 

2.

Ensure that all motor contactors are closed before the autotuning is started.

 

3.

To cancel autotuning press the STOP key on the Digital Operator.

 

 

 

 

 

 

„Other Alarms and Faults During Autotuning

For an overview of possible autotuning alarms or faults and corrective actions refer to page 24, Auto-

tuning Faults.

EN-17

Image 18
Contents VARISPEED F7 F7Z Quick Start Guide Table of Contents EN-2 ‹ Safety Precautions and Instructions EN-3„ Electrical Connection EN-4‹ EMC Compatibility „ NotesEN-5 „ Laying CablesEarthing the cable shield with metal clips EN-6 ‹ Mechanical Installation„ Checking the Installation Site „ Unpacking the Inverter„ Installation Orientation „ Installation of Inverters and EMC filtersEN-7 ‹ Electrical Connection „Wiring the Inverter Wiring DiagramEN-8 EN-9 „Main Circuit Terminals„Control Circuit Terminals EN-10 During run no Closed during Run FunctionFlywheel Diode Connection External Power Source Sinking Mode NPN „ Sinking/Sourcing Mode NPN/PNP SelectionSinking / Sourcing Mode and Input Signals EN-11‹ Wiring Main Circuit Inputs EN-12Input Fuse Selection Ground Wiring „Wiring the Output Side of the Main Circuit„Control Circuit Wiring Precautions EN-13 EN-14 ‹ Digital Operator Display optional „Digital Operator Keys ‹ Start Up Procedure EN-15‹ Autotuning ‹ Before Power Up‹ Display after Power Up „ Setting the Autotuning Mode„Other Alarms and Faults During Autotuning EN-17User Parameter EN-18Vmax EN-19Fmax VbaseEN-20 Limit only OLV and CLV‹ General Faults and Alarms EN-21OL1 EN-22OH1 OL2‹ Operator Programming Errors EN-23‹ Autotuning Faults EN-24OPE08