9  | HX93A, HX93DA SERIES | 
RH/Temperature Transmitter | |
  | 
  | 
9. RH Measured Vs Output Reading
% Relative  | Output  | |
Humidity  | Current (mA)  | Voltage (Vdc)  | 
5 4  | 0.8  | .05  | 
10  | 5.6  | .10  | 
15  | 6.4  | .15  | 
20  | 7.2  | .20  | 
25  | 8.0  | .25  | 
30  | 8.8  | .30  | 
35  | 9.6  | .35  | 
40  | 10.4  | .40  | 
45  | 11.2  | .45  | 
50  | 12.0  | .50  | 
55  | 12.8  | .55  | 
60  | 13.6  | .60  | 
65  | 14.4  | .65  | 
70  | 15.2  | .70  | 
75  | 16.0  | .75  | 
80  | 16.8  | .80  | 
85  | 17.6  | .85  | 
90  | 18.4  | .90  | 
95  | 19.2  | .95  | 
10. Temperature Output Calculations
To calculate Temperature by measuring the current or voltage output use the following formulas.
For Current output in ºC (-20  to 75ºC)
ºC = (Output measured in miliamps – 4) ÷ .1684 - 20 = ºC
EXAMPLE:(12.0 mA – 4) ÷ .1684 - 20 = 27.5ºC
For Current output ºF 
ºF = (Output measured in miliamps – 4) ÷ .0935 - 4 = ºF
EXAMPLE:(12.0 mA – 4) ÷ .0935 - 4 = 81.6ºF
For Voltage output in ºC 
ºC = (Output measured in volts ÷ .010526) - 20 = ºC
EXAMPLE:(0.50 Vdc ÷ .010526) - 20 = 27.5ºC
For Voltage output ºF 
ºF = (Output measured in volts ÷ .005848) - 4 = ºF
EXAMPLE:  | (0.50 Vdc ÷ .005848) - 4 = 81.5ºF | 
6