Liebert 232 user manual LGM Module Driver, Parameter

Page 15

LGM Module Driver

Parameter Page

Function Block

Type: LGM (LGM Module Driver)

 

 

Name SiteGate-232

 

Line 1 LG

2 CM 1

FB 15 Flags —

ID ID14

Tele

NB

All Options Y

Type 67 Ver 1

Power Up Delay

0

(sec)

Demand Controller Address 0

,0

Update Time

0:00

(mm:ss)

 

 

 

BACnet

Device Parameters:

 

 

Use

default

device object name?

Y

Use

default

device object ID?

Y

APDU Timeout

3000

 

Number of APDU Retries ...

0

 

Device Name =

Device ID = (device object, 0) (milliseconds)

GFB performance tuning:

=======================

Time slice per GFB = 5000 milliseconds.

CMnet Parameters:

General:

Generate a “Dead Module” alarm after 10 minutes of no communications

with a control module.

 

 

 

Zero compression enabled? YES

 

 

 

Output character pacing? (reduces throughput by 50%)

NO

 

Delay before sending all replies (20 msec minimum) = 20

msec.

Interpacket delay .............. (20

msec minimum) = 20

msec.

Alternate interpacket delay .... (40

msec minimum) = 40

msec.

CMnet

Tuning Parameters: (Tech Support Only)

 

 

 

Time to wait

for

‘?’ before

attempting intrusive grab =

500

msec.

Maximum

number of intrusive

grab attempts per request =

3

 

Grab Silence

Time

 

=

600

msec.

Time to

hold

the

token when

the token wraps around

=

1

seconds

Time to wait for each module to acknowledge the token = 500

msec.

Maximum online time per successful grab =

0:50 (mm:ss)

 

Maximum monitor time per monitor request =

5:00 (mm:ss)

 

Console

Port #1 Parameters:

 

 

Modem

installed on this console port = NO

 

 

Modem control parameters:

 

 

Modem

Reset ATV0E0Q0S0=1S7=60

 

 

Dial Prefix ATDT

 

 

 

Phone

Number

 

 

 

Use This Number? NO

(NO = use number from

SETGCM )

 

If not connected, and

with no alarms pending delivery, reset modem

every

5:00 (mm:ss).

Note: the minimum value for this is 5:00.

If connected, but no activity has been detected for 20:00 (mm:ss),

hang up and reset modem.

 

 

After

dialing, wait

2:00 (mm:ss) for connection before hanging up.

After

unsuccessful alarm delivery, wait 5:00 (mm:ss) before

trying again.

 

 

 

Escape (+++) guard time

1000

msec.

Post hangup delay

 

1000

msec.

Reset

time (DTR low)

 

1000

msec.

Post DTR high delay

 

500

msec.

Post reset string delay

1000

msec.

Console

Port #2 Parameters:

 

Modem

installed on this

console port = NO

Modem control parameters:

 

 

Modem

Reset ATV0E0Q0S0=1S7=60

 

Dial Prefix ATDT

 

 

 

Phone

Number

 

 

 

Use This Number? NO

(NO = use number from SETGCM )

Rev. (08-JULY-98)

15

© 1996-98 Liebert Corporation

Image 15
Contents USER’ S Manual Contents Introduction SpecificationsNetwork Communications Hardware Accessories Keypad displayMounting System ArchitectureSiteGate-232 module Power WiringDIP Switch Number Function Addressing, Baud Rates, and Console SettingsCommunication Wiring CMnet WiringProcedure Transferring Memory Setgcm CommandCables Cable Diagrams for Console Port #1Checkout & Troubleshooting Cable Diagrams for Console Port #2Troubleshooting Procedure Manually Formatting the Module Common ProblemsLEDs LED Identification RUN LED Error LED ConditionFuses LED Power-up SequenceParameter LGM Module DriverLGM Module Driver Parameters BACnet Device ParametersCMnet Parameters General Console Port Parameters CMnet Tuning ParametersModem Control Parameters Enable daylight saving time changeover from SiteGate-232Status LGM Module Driver Status Console 1 CMnet Module Driver MemoryModule Driver World Leader in Computer Support Systems