Liebert 232 user manual LGM Module Driver Status

Page 20

LGM Module Driver Status

This is the overall module status.

Function Block Type: This the Module Driver's three-character filename.

Name: This is the name referring to the space or equipment used.

Line: The telephone line number used by the Function Block.

LG: Gateway module number used by the Function Block.

CM: Control Module number used by the Function Block.

FB: Function Block number used by the Function Block.

Flags: This identifies three flags which indicate the FB is "marked" because of certain conditions.

-Indicates that the FB is not marked.

PIndicates that there has been a change to the FBs parameter page which has not been transferred to the module.

MIndicates that memory transfer has failed for this Function Block.

ID: This is an identification of up to eight characters (the first of which must be an alphabetic character) assigned to each FB. Every FB in the system has a unique ID.

Tele: This indicates the telephone number for the FB's gateway module.

All Options: This is the only changeable parameter in the Header portion of the FB and toggles between Y and N.

YAll parameters become visible even if they have not been defined.

NOnly defined parameters are shown.

Type: This parameter indicates how often the Function Block has been made in Eikon. If this parameter does not match the corresponding parameter in the module, all parameters are displayed in yellow and cannot be changed. Also, parameters cannot be uploaded or transferred. Function Blocks having mismatched type do not have their parameter written to configuration text when the configuration text is updated. To correct this problem, download memory to the module. This parameter is checked when the FB is first displayed and after a successful memory transfer. This parameter is not related to the Version microblock in Eikon.

Ver: This is the parameter that indicates how many times the FB's parameters have been changed. If the FB file in the computer does not match the FB which is transferred in the module, the Ver parameter and the parameters which do not match are displayed in purple. To correct this problem, either upload or transfer the parameters. This parameter is not related to the Version microblock in Eikon.

Module Status

This is the overall module status and indicates if any of the following conditions exist:

Auto-Restart Delay: The system has just restarted after a System Error and the module will not start GFB execution until the auto-restart delay (5 minutes) has timed out. This prevents equipment from being short cycled in the event of repeated System Errors.

Rev. (08-JULY-98)

20

© 1996-98 Liebert Corporation

Image 20
Contents USER’ S Manual Contents Specifications IntroductionHardware Accessories Keypad display Network CommunicationsSystem Architecture MountingPower Wiring SiteGate-232 moduleAddressing, Baud Rates, and Console Settings DIP Switch Number FunctionProcedure Communication WiringCMnet Wiring Setgcm Command Transferring MemoryCable Diagrams for Console Port #1 CablesTroubleshooting Procedure Checkout & TroubleshootingCable Diagrams for Console Port #2 Common Problems Manually Formatting the ModuleRUN LED Error LED Condition LEDs LED IdentificationLED Power-up Sequence FusesLGM Module Driver ParameterCMnet Parameters General LGM Module Driver ParametersBACnet Device Parameters CMnet Tuning Parameters Console Port ParametersEnable daylight saving time changeover from SiteGate-232 Modem Control ParametersStatus LGM Module Driver Status Console 1 Module Driver CMnetModule Driver Memory World Leader in Computer Support Systems