Liebert 232 LGM Module Driver Parameters, BACnet Device Parameters, CMnet Parameters General

Page 16

If not connected,

and

with no alarms pending delivery, reset modem

every 5:00 (mm:ss).

Note: the minimum value for this is 5:00.

If connected, but

no activity has been detected for 20:00 (mm:ss),

hang up and reset

modem.

 

 

After dialing, wait

2:00 (mm:ss) for connection before hanging up.

After unsuccessful alarm delivery, wait 5:00 (mm:ss) before

trying again.

 

 

 

 

Escape (+++) guard time

1000

msec.

Post hangup delay

 

 

1000

msec.

Reset time (DTR low)

 

1000

msec.

Post DTR high delay

 

500

msec.

Post reset string

delay

1000

msec.

Enable daylight saving time changeover from this module NO .

Do not enable this if you have an XFG, XFR, XFT, or XFZ on this CMnet.

Module generated Alert alarms:

Module Halted:

Alarm ID: A250 Enable: YES Critical: YES Send RTN: YES

One or more GFBs stopped:

Alarm ID: A253 Enable: YES Critical: YES Send RTN: YES

Manual I/O Locked (for each GFB):

Alarm ID: A1 Enable: YES Critical: YES Send RTN: YES

GFB parameter or other error (for each GFB):

Alarm ID: M4 Enable: YES Critical: YES Send RTN: YES

LGM Module Driver Parameters

The SiteGate-232 is properly configured by altering the module driver parameter page values. The parameters are used for defining dialing information, modem control, and CMnet characteristics.

BACnet Device Parameters

Use default device object name? This is a character string that represents the unique internetwork- wide object. The minimum length of the string is one character. The default string of this parameter is LGxCMy.

xparent LANgate LG address in decimal

yPortal's CM address in decimal

Use default object ID? This is a numeric code that is used to identify the object. Choose NO to enter a custom object ID (range: 1-4194303). Otherwise a default string of 240zzz will be assigned.

zzz parent LANgate LG address in decimal plus CMnet address in decimal

APDU Timeout Indicates the amount of time between retransmissions of an APDU requiring acknowledgement for which no acknowledgement has been received. The default value of this parameter is 3000 milliseconds.

Number of APDU Retries Indicates the maximum number of times that an APDU is transmitted. The default value of this property is zero (0).

CMnet Parameters General

Generate dead module alarm after 10 minutes of no communications with a control module. If a module has not reported its color within this time, the SiteGate-232 will generate a "dead module" alarm.

Zero compression enabled? YES: Zero compression makes the CMnet more efficient. This parameter should always be set to YES. It should only be set to NO if there is a need to examine uncompressed CMnet traffic to diagnose a CMnet problem.

Rev. (08-JULY-98)

16

© 1996-98 Liebert Corporation

Image 16
Contents USER’ S Manual Contents Specifications IntroductionHardware Accessories Keypad display Network CommunicationsSystem Architecture MountingPower Wiring SiteGate-232 moduleAddressing, Baud Rates, and Console Settings DIP Switch Number FunctionCMnet Wiring Communication WiringProcedure Setgcm Command Transferring MemoryCable Diagrams for Console Port #1 CablesCable Diagrams for Console Port #2 Checkout & TroubleshootingTroubleshooting Procedure Common Problems Manually Formatting the ModuleRUN LED Error LED Condition LEDs LED IdentificationLED Power-up Sequence FusesLGM Module Driver ParameterBACnet Device Parameters LGM Module Driver ParametersCMnet Parameters General CMnet Tuning Parameters Console Port ParametersEnable daylight saving time changeover from SiteGate-232 Modem Control ParametersStatus LGM Module Driver Status Console 1 Module Driver Memory CMnetModule Driver World Leader in Computer Support Systems