Liebert 232 user manual Common Problems, Manually Formatting the Module

Page 12

Common Problems

Modem connected to the SiteGate-232 will not answer.

Make sure the TR light on the modem is ON; if it is OFF check the modem cables. Verify connection and baud rate with the SiteGate-232.

Modem connect to SiteGate-232 will not dial out.

Make sure the modem installed on this port is set to "yes" in the LGM Parameter page under Console Port # and a valid phone number has been set using SETGCM or by manually entering a phone number.

WRU Failure.

WRU failures occur when there is a problem between the SiteGate-232 and the modem. Verify correct speed on the modem and SiteGate-232. Verify the correct cable is used and be sure it follows the ATAD cable pinout.

Manually Formatting the Module

Manually formatting the module does not require communication with the module. Use this procedure as a last resort when there is no communication with the module. Although transferring memory overwrites all existing memory, it requires communication in order to initiate the transfer.

WARNING: Formatting the module erases all transferred memory. The Transferring Memory procedure must be followed after formatting.

1.Turn the SiteGate-232's power switch OFF.

2.Press and hold the manual format button (see Figure 1).

3.Turn the SiteGate-232 module's power ON.

4.Wait a few seconds.

5.Release the manual format button.

The module is now formatted.

Rev. (08-JULY-98)

12

© 1996-98 Liebert Corporation

Image 12
Contents USER’ S Manual Contents Specifications IntroductionHardware Accessories Keypad display Network CommunicationsSystem Architecture MountingPower Wiring SiteGate-232 moduleAddressing, Baud Rates, and Console Settings DIP Switch Number FunctionCommunication Wiring CMnet WiringProcedure Setgcm Command Transferring MemoryCable Diagrams for Console Port #1 CablesCheckout & Troubleshooting Cable Diagrams for Console Port #2Troubleshooting Procedure Common Problems Manually Formatting the ModuleRUN LED Error LED Condition LEDs LED IdentificationLED Power-up Sequence FusesLGM Module Driver ParameterLGM Module Driver Parameters BACnet Device ParametersCMnet Parameters General CMnet Tuning Parameters Console Port ParametersEnable daylight saving time changeover from SiteGate-232 Modem Control ParametersStatus LGM Module Driver Status Console 1 CMnet Module Driver MemoryModule Driver World Leader in Computer Support Systems