Liebert 232 user manual System Architecture, Mounting

Page 5

segment. A segment is defined as the network of modules between main nodes. Main nodes can be represented by a gateway module, or a repeater (part no. REPOPT). A repeater can be used to end one segment and begin another, all on the same CMnet.

It is recommended that only a dedicated, 22AWG to 18AWG twisted pair copper wire be used for CMnet (EIA-485) wiring. Wire sizes smaller than 22 gauge or wires that are not twisted may cause intermittent communication problems.

NOTE: For further explanation of communications wiring, see the Technical Handbook.

System Architecture

The Liebert Architecture is designed to support both large and small systems. Small systems (those using less than 50 control modules) require only a single SiteGate-232 which serves the entire Control Module Network, or CMnet (see Figure 2). The SiteGate-232 communicates with the workstation via a EIA-232 serial communication port. A second EIA-232 port can be used for communication with another operator workstation or a portable field computer via modem or direct EIA-232 connection.

The SiteGate-232 communicates with the CMnet through a EIA-485 port. This CMnet is a peer-to-peer local area network which uses a "token-passing" protocol to allow all control modules to communicate with one another with equal authority. Each control module is capable of stand-alone DDC (Direct Digital Control), thus increasing system reliability and performance.

Mounting

Mount the SiteGate-232 in an enclosure using the four holes provided on the module's cover plate (see Figure 3). Recommended screw size is 8. Make sure that nothing comes in contact with the back of the printed circuit board, and leave approximately 2 inches on each side for wiring.

The SiteGate-232 is designed to be mounted inside the building envelope. All warranties are void if mounted outside.

 

 

 

2

 

 

 

-23

 

 

 

te

 

 

Ga

 

e

 

it

 

 

S

 

 

 

Figure 3: Mounting the SiteGate-232

Rev. (08-JULY-98)

5

© 1996-98 Liebert Corporation

Image 5
Contents USER’ S Manual Contents Introduction SpecificationsNetwork Communications Hardware Accessories Keypad displayMounting System ArchitectureSiteGate-232 module Power WiringDIP Switch Number Function Addressing, Baud Rates, and Console SettingsProcedure Communication WiringCMnet Wiring Transferring Memory Setgcm CommandCables Cable Diagrams for Console Port #1Troubleshooting Procedure Checkout & TroubleshootingCable Diagrams for Console Port #2 Manually Formatting the Module Common ProblemsLEDs LED Identification RUN LED Error LED ConditionFuses LED Power-up SequenceParameter LGM Module DriverCMnet Parameters General LGM Module Driver ParametersBACnet Device Parameters Console Port Parameters CMnet Tuning ParametersModem Control Parameters Enable daylight saving time changeover from SiteGate-232Status LGM Module Driver Status Console 1 Module Driver CMnetModule Driver Memory World Leader in Computer Support Systems