Liebert Modem Control Parameters, Enable daylight saving time changeover from SiteGate-232

Page 18

Modem Control Parameters

Modem Reset: This is a user definable parameter that sends a reset string to the modem.

Dial Prefix: This parameter sets the dial prefix used for dialing out alarms.

Phone Number: This parameter sets the number to be dialed out for alarms.

Use This Number? NO: If "YES", the phone number above will be used for dialing out to deliver alarms. If "NO", the phone number on the workstation will be used for dialing out to deliver alarms. The phone number that is currently selected will appear on the status page.

If not connected, and with no alarms pending delivery, reset modem every 5:00 (mm:ss): This parameter sets how often the SiteGate-232 will send the modem reset string.

If connected, but no activity has been detected for 20:00 (mm:ss), hang up and reset modem: This parameter sets the amount of time before the modem hangs up when there has been no data flow between the SiteGate-232 and the Workstation. It also sends the modem reset string after it hangs up. After dialing, wait 2:00 (mm:ss) for connection before hanging up: This parameter sets how long the SiteGate-232 will wait for a carrier detect before it hangs up the modem.

After unsuccessful alarm delivery: This parameter sets how long the SiteGate-232 will wait before dialing back alarms after an unsuccessful alarms delivery.

Escape (+++) guard time: This parameter determines the time delay before and after the escape sequence to allow the modem to receive and acknowledge it.

Post hangup delay: This parameter determines how long the SiteGate-232 waits after sending the modem hangup command.

Reset time (DTR Low): This parameter determines how long the SiteGate-232 holds the DTR line low for disconnecting the modem.

Post DTR high delay: This parameter determines how long the SiteGate-232 waits after returning DTR to its active (high) state after a modem reset.

Post reset string delay: This parameter determines how long the SiteGate-232 waits after sending the reset string to the modem.

Enable daylight saving time changeover from SiteGate-232

When set to "YES", the SiteGate-232 will make daylight saving time adjustments to its own clock and the clock of all modules on its CMnet. Do not enable this if you have an XFG, XFR, XFT, or XFZ Function Block on this CMnet.

Rev. (08-JULY-98)

18

© 1996-98 Liebert Corporation

Image 18
Contents USER’ S Manual Contents Specifications IntroductionHardware Accessories Keypad display Network CommunicationsSystem Architecture MountingPower Wiring SiteGate-232 moduleAddressing, Baud Rates, and Console Settings DIP Switch Number FunctionCommunication Wiring CMnet WiringProcedure Setgcm Command Transferring MemoryCable Diagrams for Console Port #1 CablesCheckout & Troubleshooting Cable Diagrams for Console Port #2Troubleshooting Procedure Common Problems Manually Formatting the ModuleRUN LED Error LED Condition LEDs LED IdentificationLED Power-up Sequence FusesLGM Module Driver ParameterLGM Module Driver Parameters BACnet Device ParametersCMnet Parameters General CMnet Tuning Parameters Console Port ParametersEnable daylight saving time changeover from SiteGate-232 Modem Control ParametersStatus LGM Module Driver Status Console 1 CMnet Module Driver MemoryModule Driver World Leader in Computer Support Systems