Liebert 50 and 60 Hz, S3 user manual 10.7, 28.9, #6 350 MCM

Page 22

Table 3

UPS Module Power Wiring Termination - Factory Supplied

 

 

 

 

 

 

 

Connection Type / Wire Size Range

 

 

 

UPS Module

 

 

 

 

 

Rating

 

AC Input

Battery

AC Output

Neutral

Ground

kVA

 

12 - 24

 

Compression

Studs

Compression

Compression

Copper Busbar

 

 

lug

3/8 - 16 x 2

lug

lug

3.75 x 3.75 x

 

 

#14 to #2/0

Lugs Required

#14 to #2/0

#14 to #2/0

0.25

 

 

 

 

 

 

 

Use factory supplied connections for terminations where they are provided. Refer to Figure 19 for field- supplied wiring termination details. Use commercially available UL listed solderless lugs for the wire size required for your application. Connect wire to the lug using tool and procedure specified by the lug manufacturer.

Table 4

Torque Specifications (Unless Otherwise Labeled)

 

 

 

 

 

 

 

 

 

Nut and Bolt Combinations

 

 

 

 

 

 

 

 

 

Grade 2

Electrical Connections

 

Bolt Shaft Size

 

 

Standard

with Belleville Washers

 

 

 

 

 

 

 

 

Inches

 

Lb-in

 

N-m

Lb-in

N-m

 

1/4

 

70

 

8.0

46

5.2

 

 

 

 

 

 

 

 

 

5/16

 

132

 

15

60

6.8

 

 

 

 

 

 

 

 

 

3/8

 

229

 

26

95

10.7

 

 

 

 

 

 

 

 

 

1/2

 

476

 

54

256

28.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Block Compression Lugs

 

 

 

 

 

 

UPS Module

 

 

 

Wire Size or

 

 

 

Rating

 

Wiring

 

Lb-in

N-m

 

kVA

 

 

Range

 

12 - 24

 

Control

 

#22 - #14

3.5 to 5.3

0.4 to 0.6

 

 

 

 

 

 

 

 

 

12 - 24

 

Power

 

#6 - 350 MCM

50

5.6

 

 

 

 

 

 

 

 

16 Installation

Image 22
Contents UPStation S3 Page Table of Contents Êïèïì ÊïéïìÊïéïë ÊïèïëLJXUHýè LJXUHýìLJXUHýë LJXUHýçPage $ $7717,21ý,167$//56 8VHýDSSURSULDWHýZLUHýVLHVýDQGýDSSURYHGýZLULQJýWHFKQLTXHVâýSite Planning Data Additional NotesSite Planning Data DescriptionUPS Cabinet Options System ComponentsStandard UPS Unit ‡ %ROWðRQýEDWWHU\ýFDELQHWñýIDFWRU\ýFRQQHFWHGModes of Operation ZRUNLQJýZLWKýWKHý836ï $ $51,1* 7+ý%$775ý,6ý$/$6ý15*,=ïý Safety PrecautionsHFHVVýPRLVWXUHñýRUýGHEULVï UPS Installation Unloading and External Inspection Installation ConsiderationsInternal Inspection of the UPS System 167$//$7,21ý7,3 BatteriesEquipment Location RQýLWVýFDVWHUýZKHHOVï$ð$&,ý%$775,6ý&$1ý35617ý$ý5,6.ý2ý,5ý Electrical Wiring UPS Wire Size GuidelinesPower & Control Wiring Battery Wiring 9HULI\ýWKHýIROORZLQJýFRQQHFWLRQVýKDYHýEHHQýPDGHã Wiring ConnectionsWiring Inspection HUHGýIURPýWKHý836ýRXWSXWôñýSOXVýJURXQGïCopper Aluminum or Copper-Clad Aluminum Temp F28.9 10.7#6 350 MCM One Line Drawing Single Input Configuration 200/240V In/Out One Line Drawing Dual Input Configuration 200/240V In/Out Installation Installation Installation Installation Installation Installation Installation Installation Installation Installation Cabinet Dimensions Cabinet Dimensions With Transformer Cabinet Connecting Terminal Details Connecting Terminal Details With Transformer Cabinet Battery Option Details 12 Inch Cabinet Battery Option Details 24 Inch Cabinet Field Lug Wiring Terminations Unloading Instructions Unloading Instructions 24 Inch Battery Cabinet Battery Times Control / Display Panel LCD Display Description LCD DisplayILJXUDWLRQýLVýRSWLRQDOï Initial Start-UpÊï 836ý0HWHUV Éï $FFHSWý6HWWLQJV \VWHPï 7RýVWDUWýXQLWñýSXVKýWKHý21ýEXWWRQïSee 4.0 Features & Options Configuration Screen Default ValueAdvanced Configuration Screen Default Value Æï 3URJUDPPDEOHý,QSXWýFRQWDFWV1HXWUDOï System Start-Up Normal OperationRUýLIýWKHý532ýEXWWRQýLVýSUHVVHGï Battery OperationUHVXPHýDQGýEDWWHU\ýUHFKDUJLQJýZLOOýEHJLQï UHFKDUJHýUDWHñýLQýRUGHUýWRýRSWLPLHýEDWWHU\ýOLIHïStatic Transfer Switch Bypass OperationConfiguration Menu Tree Manual Off Maintenance BypassSystem Shutdown Automatic OffControl Switch Locations Check Messages User Response to UPS AlarmsPress ‘ON’ To start system Press -- to check Time RemainingLoad on BypassAlarm Messages Alarm Message Meaning Corrective ActionRestart after Low Battery ShutdownProcedures in 3.0 Operation Liebert Global Services Introduction RS-232 Communication FeatureTerminal Operation Factory Installed Options External Battery Cabinets Field Installable OptionsBattery Cabinets Output Distribution PanelSiteNet Snmp Simple Network Management Protocol Communication OptionsSiteNet 1 Shutdown Interface Kits Internal ModemInput Contact Isolator Delayed Battery RechargeOptional DC Ground Fault Alarm Optional Remote Status PanelFloor Anchors Optional Power SupplyDFFRUGDQFHýZLWKýORFDOýDQGýQDWLRQDOýFRGHýUHTXLUHPHQWVï RS-232 Connections Output Distribution Panel Board Routine Maintenance Requirements Battery MaintenanceËï ,ý/&752/7ý&217$&76ý7+ý6.,1ñý$6+ý,7ý2ý ,00,$7/ý,7+ý$75ï System Physical CharacteristicsBattery AC InputXVWRPHUý5HVSRQVHý&HQWHUï SDFNDJHï5HYLVHGãý-XO\ýìääæ