Table 5

Alarm Messages (continued)

 

 

 

 

Alarm Message

Meaning

Corrective Action

 

 

 

Output Overload

The units total output power (the sum

Determine cause of the overload and

 

 

of all three phases) has exceeded

reduce the load.

 

 

the overload capacity of the unit. The

 

 

 

load will be automatically transferred

 

 

 

to bypass (if available).

 

 

 

 

Output Undervoltage

UPS output voltage or current is not

Contact Liebert Global Services if the

Output Overvoltage

within the acceptable range. The

UPS is not able to correct any one of

Overload Phase A

load has been automatically

these conditions.

Overload Phase B

transferred to bypass (if available).

 

Overload Phase C

An automatic retransfer will be

 

 

 

attempted when the output voltage

 

 

 

and current are within tolerance.

 

 

 

 

PFC Bus Voltage High

The inverter bus voltage is either

Contact Liebert Global Services.

PFC Bus Voltage Low

high or low or exceeded acceptable

 

PFC Hardware Shutdown

limits. The unit will transfer to bypass.

 

 

 

 

Site Wiring Error

Warning Alarm: The power

Disconnect power from the UPS

 

 

conductors are not wired to the UPS

input and correct the wiring. Wiring

 

 

input in the desired sequence.

should be verified or corrected by a

 

 

 

qualified electrician.

 

 

 

System shutdown impending

The input filter may be clogged or 1

Check input air filter. Reduce the

due to over-temperature

or more cooling fans may have failed

system load as much as possible.

 

 

and the internal temperatures are

Contact Liebert Global Services.

 

 

approaching the automatic shutdown

 

 

 

level.

 

 

 

 

System shutdown due to

The UPS system has shut down and

Contact Liebert Global Services.

internal over-temperature

transferred to Bypass as a result of a

 

 

 

clogged input filter or failure of 1 or

 

 

 

more fans.

 

 

 

 

Temporary Overload

The output waveform is distorted. If

Normally the condition will correct

 

 

available, the UPS will transfer to

itself. If the unit has not corrected this

 

 

bypass until the waveform distortion

condition within 30 minutes, contact

 

 

is corrected.

Liebert Global Services.

 

 

 

UPS Overtemp

System shutdown impending due to

An over-temperature condition is

 

 

over-temperature.

present in the UPS cabinet. The UPS

 

 

This is a two-stage alarm. The same

will automatically transfer to bypass if

 

 

message will occur if the system has

the over-temperature continues.

 

 

reached over-temp and has

Determine the cause of the condition

 

 

transferred to bypass as a result of

and correct it if possible. Check for

 

 

the over-temp condition.

restricted air flow or fan failure.

 

 

Other alarms will signal the transfer

 

 

 

to bypass.

 

 

 

 

UPS Shutdown

The UPS has detected a fault and

Review and record alarm messages.

 

 

has shut down, resulting in loss of

Contact Liebert Global Services.

 

 

power to the critical load.

 

 

 

 

 

Liebert Global Services 1-800-543-2378

Operation 55

Image 61
Contents UPStation S3 Page Table of Contents Êïéïë ÊïéïìÊïèïì ÊïèïëLJXUHýë LJXUHýìLJXUHýè LJXUHýçPage 8VHýDSSURSULDWHýZLUHýVLHVýDQGýDSSURYHGýZLULQJýWHFKQLTXHVâý $ $7717,21ý,167$//56Additional Notes Site Planning DataSite Planning Data DescriptionUPS Cabinet Standard UPS Unit System ComponentsOptions ‡ %ROWðRQýEDWWHU\ýFDELQHWñýIDFWRU\ýFRQQHFWHGModes of Operation ZRUNLQJýZLWKýWKHý836ï $ $51,1* 7+ý%$775ý,6ý$/$6ý15*,=ïý Safety PrecautionsHFHVVýPRLVWXUHñýRUýGHEULVï UPS Installation Unloading and External Inspection Installation ConsiderationsInternal Inspection of the UPS System Equipment Location Batteries167$//$7,21ý7,3 RQýLWVýFDVWHUýZKHHOVï$ð$&,ý%$775,6ý&$1ý35617ý$ý5,6.ý2ý,5ý UPS Wire Size Guidelines Electrical WiringPower & Control Wiring Battery Wiring Wiring Inspection Wiring Connections9HULI\ýWKHýIROORZLQJýFRQQHFWLRQVýKDYHýEHHQýPDGHã HUHGýIURPýWKHý836ýRXWSXWôñýSOXVýJURXQGïTemp F Copper Aluminum or Copper-Clad Aluminum28.9 10.7#6 350 MCM One Line Drawing Single Input Configuration 200/240V In/Out One Line Drawing Dual Input Configuration 200/240V In/Out Installation Installation Installation Installation Installation Installation Installation Installation Installation Installation Cabinet Dimensions Cabinet Dimensions With Transformer Cabinet Connecting Terminal Details Connecting Terminal Details With Transformer Cabinet Battery Option Details 12 Inch Cabinet Battery Option Details 24 Inch Cabinet Field Lug Wiring Terminations Unloading Instructions Unloading Instructions 24 Inch Battery Cabinet Battery Times Control / Display Panel LCD Display LCD Display DescriptionÊï 836ý0HWHUV Éï $FFHSWý6HWWLQJV Initial Start-UpILJXUDWLRQýLVýRSWLRQDOï \VWHPï 7RýVWDUWýXQLWñýSXVKýWKHý21ýEXWWRQïAdvanced Configuration Screen Default Value Configuration Screen Default ValueSee 4.0 Features & Options Æï 3URJUDPPDEOHý,QSXWýFRQWDFWV1HXWUDOï Normal Operation System Start-UpUHVXPHýDQGýEDWWHU\ýUHFKDUJLQJýZLOOýEHJLQï Battery OperationRUýLIýWKHý532ýEXWWRQýLVýSUHVVHGï UHFKDUJHýUDWHñýLQýRUGHUýWRýRSWLPLHýEDWWHU\ýOLIHïBypass Operation Static Transfer SwitchConfiguration Menu Tree System Shutdown Maintenance BypassManual Off Automatic OffControl Switch Locations Press ‘ON’ To start system Press -- to check User Response to UPS AlarmsCheck Messages Time RemainingBypass Load onAlarm Message Meaning Corrective Action Alarm MessagesShutdown Restart after Low BatteryProcedures in 3.0 Operation Liebert Global Services Introduction RS-232 Communication FeatureTerminal Operation Factory Installed Options Battery Cabinets Field Installable OptionsExternal Battery Cabinets Output Distribution PanelSiteNet 1 Shutdown Interface Kits Communication OptionsSiteNet Snmp Simple Network Management Protocol Internal ModemOptional DC Ground Fault Alarm Delayed Battery RechargeInput Contact Isolator Optional Remote Status PanelFloor Anchors Optional Power SupplyDFFRUGDQFHýZLWKýORFDOýDQGýQDWLRQDOýFRGHýUHTXLUHPHQWVï RS-232 Connections Output Distribution Panel Board Battery Maintenance Routine Maintenance RequirementsËï ,ý/&752/7ý&217$&76ý7+ý6.,1ñý$6+ý,7ý2ý ,00,$7/ý,7+ý$75ï Battery Physical CharacteristicsSystem AC InputXVWRPHUý5HVSRQVHý&HQWHUï SDFNDJHï5HYLVHGãý-XO\ýìääæ