Liebert 50 and 60 Hz, S3 user manual System, Physical Characteristics, AC Input, AC Output, Battery

Page 72

6.0

SPECIFICATIONS

 

6.1

System

 

 

 

 

 

Safety Agencies:

UL 1778 listed

 

 

CSA 22.2, No. 107.1 certified

 

 

 

 

Audible Noise:

57 dBA at one meter

 

 

 

 

Transient/Surge Protection:

Per IEEE 587/ANSI C62.41 Categories A & B

 

 

 

6.2Physical Characteristics

Operating Environment:

0° to 40°C

 

25° ±5°C for batteries

 

 

Relative Humidity:

0 to 95% relative humidity (non-condensing)

 

 

Altitude:

6600 feet (2,000 meters)

 

 

5HIHUýWRý7DEOH ìýðý6LWHý3ODQQLQJý'DWDýIRUýGLPHQVLRQVýDQGýZHLJKWVï

6.3

AC Input

 

 

 

 

 

Voltage Range:

170 to 264 VAC (See Table 1 - Site Planning Data)

 

 

 

 

Voltage Configuration

Three phase input, Wye configuration with 3 phases, ground and neutral.

 

and Connection:

Dual input if input and output voltages are not the same.

 

 

 

 

Frequency Range:

45 Hz to 65 Hz

 

 

 

 

Input Current THD:

25% - 30% THD maximum at full load

 

 

3% THD option available

 

 

 

 

Power Factor:

.95 Standard

 

 

.99 with 3% THD Option

 

 

 

6.4

AC Output

 

 

 

 

 

Voltage Regulation:

±1% for balanced loads

 

 

±1.5% for 100% unbalanced loads

 

 

 

 

Voltage Distortion:

Maximum 2% THD for linear loads at 208 VAC

 

 

Maximum 3.5% THD for full non-linear loads at 208 VAC

 

 

 

 

Transient Response:

±1% for 100% step load;

 

 

recovery to within 1% in one cycle

 

 

 

 

Frequency:

50 Hz or 60 Hz

 

 

 

 

Frequency Slew Rate:

1 Hz/sec (user-selectable 0.1 to 3 Hz/sec)

 

 

 

 

Frequency Sync Range:

±1 Hz (user-selectable ±0.1 Hz to 5 Hz)

 

 

 

 

Load Crest Factor:

3:1

 

 

 

 

Overload:

125% for 10 minutes, 150% for 10 seconds

 

 

 

 

Unbalanced Load Capability:

Up to 100% of the individual phase rating

 

 

 

6.5

Battery

 

 

 

 

 

Type:

Standard: Valve-regulated, lead acid

 

 

Optional: Flame retardant, valve-regulated, lead-acid (rated for computer

 

 

room operation)

 

 

 

 

Recharge Rate:

10 times discharge duration to 95% when “turbo” mode is selected

 

 

 

 

Battery Run-Time:

Varies with battery cabinet selection

 

 

 

 

Battery Voltage:

Nominal: 240 VDC

 

 

 

66 Specifications

Image 72
Contents UPStation S3 Page Table of Contents Êïéïì ÊïéïëÊïèïì ÊïèïëLJXUHýì LJXUHýëLJXUHýè LJXUHýçPage $ $7717,21ý,167$//56 8VHýDSSURSULDWHýZLUHýVLHVýDQGýDSSURYHGýZLULQJýWHFKQLTXHVâýSite Planning Data Additional NotesDescription Site Planning DataUPS Cabinet System Components Standard UPS UnitOptions ‡ %ROWðRQýEDWWHU\ýFDELQHWñýIDFWRU\ýFRQQHFWHGModes of Operation Safety Precautions ZRUNLQJýZLWKýWKHý836ï $ $51,1* 7+ý%$775ý,6ý$/$6ý15*,=ïýHFHVVýPRLVWXUHñýRUýGHEULVï UPS Installation Installation Considerations Unloading and External InspectionInternal Inspection of the UPS System Batteries Equipment Location167$//$7,21ý7,3 RQýLWVýFDVWHUýZKHHOVï$ð$&,ý%$775,6ý&$1ý35617ý$ý5,6.ý2ý,5ý Electrical Wiring UPS Wire Size GuidelinesPower & Control Wiring Battery Wiring Wiring Connections Wiring Inspection9HULI\ýWKHýIROORZLQJýFRQQHFWLRQVýKDYHýEHHQýPDGHã HUHGýIURPýWKHý836ýRXWSXWôñýSOXVýJURXQGïCopper Aluminum or Copper-Clad Aluminum Temp F10.7 28.9#6 350 MCM One Line Drawing Single Input Configuration 200/240V In/Out One Line Drawing Dual Input Configuration 200/240V In/Out Installation Installation Installation Installation Installation Installation Installation Installation Installation Installation Cabinet Dimensions Cabinet Dimensions With Transformer Cabinet Connecting Terminal Details Connecting Terminal Details With Transformer Cabinet Battery Option Details 12 Inch Cabinet Battery Option Details 24 Inch Cabinet Field Lug Wiring Terminations Unloading Instructions Unloading Instructions 24 Inch Battery Cabinet Battery Times Control / Display Panel LCD Display Description LCD DisplayInitial Start-Up Êï 836ý0HWHUV Éï $FFHSWý6HWWLQJVILJXUDWLRQýLVýRSWLRQDOï \VWHPï 7RýVWDUWýXQLWñýSXVKýWKHý21ýEXWWRQïConfiguration Screen Default Value Advanced Configuration Screen Default ValueSee 4.0 Features & Options Æï 3URJUDPPDEOHý,QSXWýFRQWDFWV1HXWUDOï System Start-Up Normal OperationBattery Operation UHVXPHýDQGýEDWWHU\ýUHFKDUJLQJýZLOOýEHJLQïRUýLIýWKHý532ýEXWWRQýLVýSUHVVHGï UHFKDUJHýUDWHñýLQýRUGHUýWRýRSWLPLHýEDWWHU\ýOLIHïStatic Transfer Switch Bypass OperationConfiguration Menu Tree Maintenance Bypass System ShutdownManual Off Automatic OffControl Switch Locations User Response to UPS Alarms Press ‘ON’ To start system Press -- to checkCheck Messages Time RemainingLoad on BypassAlarm Messages Alarm Message Meaning Corrective ActionRestart after Low Battery ShutdownProcedures in 3.0 Operation Liebert Global Services RS-232 Communication Feature IntroductionTerminal Operation Factory Installed Options Field Installable Options Battery CabinetsExternal Battery Cabinets Output Distribution PanelCommunication Options SiteNet 1 Shutdown Interface KitsSiteNet Snmp Simple Network Management Protocol Internal ModemDelayed Battery Recharge Optional DC Ground Fault AlarmInput Contact Isolator Optional Remote Status PanelOptional Power Supply Floor AnchorsDFFRUGDQFHýZLWKýORFDOýDQGýQDWLRQDOýFRGHýUHTXLUHPHQWVï RS-232 Connections Output Distribution Panel Board Routine Maintenance Requirements Battery MaintenanceËï ,ý/&752/7ý&217$&76ý7+ý6.,1ñý$6+ý,7ý2ý ,00,$7/ý,7+ý$75ï Physical Characteristics BatterySystem AC InputSDFNDJHï XVWRPHUý5HVSRQVHý&HQWHUï5HYLVHGãý-XO\ýìääæ