Table 5 | Alarm Messages (continued) |
| |
|
|
| |
Alarm Message | Meaning | Corrective Action | |
|
|
| |
LAN Interface Shutdown | This alarm indicates the LAN is being | This should activate the automatic | |
Initiated |
| shut down for a programmed action | shutdown sequence programmed |
|
| due to the activation of one or more | into your LAN operating system. |
|
| alarms. |
|
|
|
| |
Load on Manual Bypass | The Maintenance Bypass switch is in | When the maintenance activity has | |
|
| the Maintenance position. | been completed, return the unit to |
|
|
| normal operation. |
|
|
|
|
Logic Error |
| Automatic diagnostic testing has | Record the alarm condition and |
|
| detected a failure (of hardware or | contact Liebert Global Services. |
|
| software) in the UPS internal control |
|
|
| system. A second message may |
|
|
| indicate internal test or software |
|
|
|
| |
|
| automatically transferred to bypass. |
|
|
|
| |
Low Battery Shutdown | Battery has discharged to the | When the battery has recharged and | |
|
| minimum allowable voltage. If the | if there is not fault, the unit will |
|
| bypass is available the unit will | retransfer from bypass. If bypass |
|
| transfer to bypass. If the bypass is | was not available, when input power |
|
| not available, the UPS is shut down. | becomes available, perform a UPS |
|
| No power is being supplied to the | |
|
| critical load. | by itself if |
|
|
| |
Low Battery Warning Issued | The battery voltage measurement | User should take appropriate | |
|
| has reached the | measures to insure an orderly |
|
| warning value. The unit will shut | shutdown of the system. If the user |
|
| down at the specified time if input | has set the warning level above 2 |
|
| power is not restored. | minutes, you may also take action to |
|
|
| shed load and increase battery time |
|
|
| to complete discharge. |
|
|
| |
Manual Off Activated | The UPS has been shut down | To restart the UPS follow the | |
(Alarm History Only) | remotely through the | procedures in 3.0 - Operation. | |
|
| interface or through the advanced |
|
|
| configuration menu. |
|
|
|
| |
Manual On Activated | The UPS has been turned on | This is an information alarm only. | |
(Alarm History Only) | remotely through the | Make sure it is OK that the UPS is | |
|
| interface or through the advanced | energized. |
|
| configuration menu. |
|
|
|
| |
Manual | The UPS has been transferred to | Determine why the UPS was | |
Activated |
| bypass remotely through the | transferred to bypass. Clear the fault |
(Alarm History only) | interface or through the advanced | or problem and retransfer to normal | |
|
| configuration menu. The UPS stays | operation. If the problem cannot be |
|
| on Bypass until the retransfer is | corrected, contact Liebert Global |
|
| activated and all required conditions | Services. |
|
| for retransfer are satisfied. |
|
|
|
| |
Memory Failure ROM or | The microprocessor has failed a self | Contact Liebert Global Services. | |
Memory Failure RAM | diagnostic test during the |
| |
|
| process. Start up will not be allowed. |
|
|
|
| |
Neutral SCR Short | On units equipped with the isolated | Contact Liebert Global Services. | |
|
| neutral option, the SCR that transfers |
|
|
| the neutral has failed short. |
|
|
|
| |
Non Volatile Ram U88 | Non Volatile ram has a long life | Contact Liebert Global Services. | |
Corrupted |
| (10 year) back up battery, either the |
|
|
| battery is near end or life or the |
|
|
| memory has been corrupted. |
|
|
|
| |
Non Volatile Ram U88 Failed | Non Volatile ram back up battery has | Contact Liebert Global Services. | |
|
| reached end of life or the Main |
|
|
| control board memory has had a |
|
|
| failure. |
|
|
|
|
|
54 Operation