Operating Instructions
4.2.6Returning an Isolated System to Normal Operation - End Combined Loads Operation
One Load circuit breaker and the Tie circuit breaker are closed. The Load circuit breaker of the iso- lated system which was being serviced will be opened.
1.Select the UPS system to accept the load. Press the TRANSFER LOAD TO SYSTEM (#). If System 2 had been isolated then press the SYSTEM 2 button. Load 2 will be returned to System 2.
2.Wait for the OK TO TRANSFER LOAD light to turn on. If System 2 was isolated then the OK TO TRANSFER LOAD 2 TO SYSTEM 2 light should turn on when it is safe to perform the transfer.
3.After the OK TO TRANSFER LOAD 2 TO SYSTEM 2 light turns on, press the PUSH TO TRANSFER AFTER OK button. The transfer will be performed. If System 2 was isolated then the Load 2 breaker will close and the Tie circuit breaker opens after the overlap period times out.
4.Both UPS systems will now be supplying their normal Load and operating independent of each other.
4.2.7Maintenance Procedures - Maintaining Power-Tie Components
Refer to the procedures in 4.2.3 - Maintenance Procedures - Isolating Each UPS System to iso- late the UPS’s load circuit breaker and the associated downstream feeders for service.
By using downstream switchover devices for the individual critical loads, such as ATSs or dual input PDUs, the load feeder components to be maintained are
There are three approaches to maintaining the Tie circuit breaker and its associated circuit compo- nents depending on the convenience and isolation desired.
1.Single
Complete UPS system and critical loads must be placed on a reliable maintenance bypass source (e.g., standby
Using appropriate safety equipment and procedures, the Tie circuit breaker can be serviced while one or both systems remain energized (depending on isolation breaker usage).
2.Single drawout Tie circuit breaker
Drawout mechanism permits servicing the Tie circuit breaker and associated circuitry while the
To
Using appropriate safety equipment and procedures, these components can be serviced while one or both systems remain energized (depending on isolation breaker usage).
3.Two Tie circuit breakers in
By using two Tie circuit breakers in series, each circuit breaker and its associated buswork can be conveniently and completely
Using appropriate safety equipment and procedures, these components can be serviced while one of the two systems remains energized.
4.2.8Maintenance Procedures - Tie Control Logic Components
Unless the controls are in a continuous parallel mode or currently in the process of transferring a load, it is possible to service the Tie controls by taking a few precautions. Since all control signals are isolated, they can be safely
27