Liebert Series 610 user manual Manual Controls

Page 28

Control Panel Description

Voltage Lockout

This light indicates the system voltages are too far apart to allow safe transfers and parallel operation of the UPS systems. To correct this condition, adjust the UPS system voltage to proper levels.

If both system voltages are adjusted correctly, and the PHASE LOCKOUT alarm is not present, then check the voltage detection circuitry. Contact Liebert Global Services for assistance.

Load Lockout

This light indicates insufficient UPS capacity to perform the selected operation. The control logic intelligently checks the UPS systems and the Loads based on the specific operation in progress.

Verify UPS capacity and shed load as necessary until UPS capacity is not being exceeded. If UPS capacity is sufficient, then check the load/capacity detection circuitry. Contact Liebert Global Services for assistance.

Logic Failure

This light indicates that a logic failure has occurred. No Tie operations are allowed while this condi- tion exists.

Check all tie control logic functions to determine the source of the fault. Contact Liebert Global Ser- vices for assistance.

Lamp Test

This button is pressed to check all indicators on the MIMIC and CONTROL PANEL.

3.5Manual Controls

These controls are located on a panel behind the Control Panel door. They are provided to assist in initial system start-up and provide emergency manual breaker trip capability. During normal opera- tions they should not need to be used.

Close Load 1

This button closes the Load 1 circuit breaker during start-up. It only functions if the Tie breaker is open.

Close Load 2

This button closes the Load 2 circuit breaker during start-up. It only functions if the Tie breaker is open.

Trip Load 1

This button is used to manually trip the Load 1 circuit breaker and is provided for emergency pur- poses.

The light on this push button will go out when load is being supplied through the breaker. Pressing this button when the light is out will result in loss of power to an on-line load.

Trip Load 2

This button is used to manually trip the Load 2 circuit breaker and is provided for emergency pur- poses.

The light on this push button will go out when load is being supplied through the breaker. Pressing this button when the light is out will result in loss of power to an on-line load.

Trip Tie

This button is used to manually trip the Tie circuit breaker and is provided for emergency purposes.

24

Image 28
Contents Continuous POWER-TIE Configuration Page Table of Contents Operating Instructions Initial System Start-Up 4.2 Basic OperationSystem Flexibility FunctionInter-System Isolation and Reliability Basic Dual-Bus Power-Tie one-line diagram Power-Tie systems fault isolation issues Power-Tie systems control interface diagram Control System Features Operational DescriptionIntersystem Synchronizing Momentary Tie OperationMomentary Tie Transfer Controls Intersystem Sync and Power Sharing Continuous TieContinuous Tie/Transfer/Parallel Control Tie System ComponentsModes of Operation Power-Tie system one-line diagram Continuous Power-Tie Checking for Phase, Voltage, and CapacitySelecting a Line Sync Source Synchronizing the UPS SystemsControl panel layout Separating Tied Systems Load Transfers Between UPS SystemsCombined Loads on One System to Continuous Tie Operation Combined Loads on One System from Continuous Tie OperationDesign Criteria Line Sync Signal Power-Tie system fault isolation issues Power-Tie systems fault tolerance Transfer Operation Improper User OperationTie Operation Tie Circuit Breaker or Logic Faults What Happens If a Failure Occurs During a Power TransferRecommendations Tie Circuit Breaker Selection Hardware FailuresMimic Panel Load Transfer Controls Transfer Control Disabled Transfer Function AvailableTransfer Function Available OK to Transfer Load 1 to System Transfer Function Available OK to Transfer Load 2 to SystemContinuous Tie Control Control InhibitsManual Controls Normal Transfer Operation Configurations Maintenance Procedures Isolating Each UPS SystemInitial System Start-Up Basic OperationTransfer of Load Between Two Systems Maintenance Procedures Maintaining Power-Tie Components Maintenance Procedures Tie Control Logic ComponentsTrouble Recovery Abnormal OperationsImproper Transfer Circuit Breaker FailureContinuous Tie-Systems Normal Operating ConfigurationTying the UPS Systems Continuous Parallel Operations Abnormal Operations Isolation for Maintenance Power-Tie system one-line diagram Operation Scenarios/Transfer Procedures Combined Loads Operation See 4.2.4 Isolating a UPS System for MaintenanceSee 4.2.5 Transfer of Load Between Two Systems See 4.2.11 Tying the UPS Systems Continuous Parallel OperationsSee 4.2.3 Maintenance Procedures Isolating Each UPS SystemOne system in bypass to Continuous Tie operation Option Operating Instructions Page Company Behind the Products Technical Support/ServiceLocations