GE P485 instruction manual For the MM2, we have, Type Parameter Address Format Read/write

Page 58

APPLICATION EXAMPLE

SYSTEM SETUP This chapter describes how to set up the P485 with MM2 relay and PQMII meter to read and write parameters. It can also be used as a guideline to setup the P485 Modbus to Profibus Converter for communication with any GE Multilin relays.

The PQMII and MM2 devices are serially connected (daisy-chained) through RS485. The following data is set up for the PQMII:

Read phase current Ia, Ib, and Ic actual values from memory locations 0240h to 0242h

Read average current from memory location 0244h

Read neutral current from memory location 0245h

Read average phase voltage from memory location 0286h to 0287h

The following data is set up for the MM2:

Read motor status from memory location 0023h

Read switch input status from memory location 0010h

Read motor load from memory location 0035h

Read thermal capacity from memory location 0036h

Read metered voltage from memory location 0040h

The START A (command code 0x0005) and STOP (command code 0x0004) commands using Modbus function 10h: Preset multiple registers.

The memory addresses below are taken from the PQMII and MM2 instruction manuals available at http://www.GEmultilin.com. For the PQMII, we have:

Type

Parameter

Address

Format

Read/write

 

 

 

 

 

Actual values

Phase current Ia

0x0240

F1

Read only

 

 

 

 

 

Actual values

Phase current Ib

0x0241

F1

Read only

 

 

 

 

 

Actual values

Phase current Ic

0x0242

F1

Read only

 

 

 

 

 

Actual values

Average phase current

0x0244

F1

Read only

 

 

 

 

 

Actual values

Neutral current

0x0245

F1

Read only

 

 

 

 

 

Actual values

Average phase voltage (2 words)

0x0286

F3

Read only

 

 

 

 

 

For the MM2, we have:

 

 

 

Type

Parameter

Address

Format

Read/write

 

 

 

 

 

Actual values

Motor status

0x0023

F7

Read only

 

 

 

 

 

Actual values

Switch input status

0x0010

F100

Read only

 

 

 

 

 

Actual values

Motor Load

0x0035

F1

Read only

 

 

 

 

 

Actual values

Thermal Capacity

0x0036

F1

Read only

 

 

 

 

 

Actual values

Voltage

0x0040

F1

Read only

 

 

 

 

 

Commands

Command function code

0x1160

F1

Read/write

 

 

 

 

 

Commands

Command operation code

0x1161

F22

Read/write

 

 

 

 

 

The write command returns data in the response that should not be visible from the Fieldbus. Also, the write commands should only be sent if the data from the Profibus master has changed.

If the P485 detects a timeout while talking to the devices (PQMII and/or MM2), it should try to re-establish communications before it considers the device in subnet is missing (Number of retries), and then try again after some time (Reconnect time).

The serial communication parameters are set to 19200 bps, with no parity, 1 stop bit, and 8 data bits. The physical interface is set to RS485.

9–2

P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

Image 58
Contents P485 Modbus to Profibus Converter GE MultilinPage Table of contents P485 Modbus to Profibus ConverterSoftware Frame Miscellaneous Introduction Getting startedDocument conventions Input and output definitionFeatures FeaturesAbout the P485 Modbus to Profibus Converter Ordering SpecificationsMechanical Housing CommunicationsQuick install InstallationElectrical installation Profibus connector pin assignments Pin Signal DescriptionConfiguration cable pin assignments P485 end Pin DescriptionConfiguration cable PC end Mechanical installation Indicators and switchesP485 status indicators Number Description State StatusProfibus installation procedure Input/output bytes required ModulesTroubleshooting Poor performanceData exchange OverviewAddress Contents Access Memory MapProtocol configuration BlocksData Exchange Software overview Installation procedureIntroduction Using the EnerVista P485/D485 Setup software Select Configuration Wizard and click on OKTypical network arrangement Sub-network data flow Address Command Software Overview P485 Modbus to Profibus Converter User Guide Software Overview Configuration main window Configurator main windowInformation window Fieldbus configuration Function DescriptionP485/D485 configuration P485/D485 configurationModbus network configuration Parameter Description RangeSoftware Overview Communication model PLCBasic settings P485 scan listNodes MenuCommunication Model P485 Modbus to Profibus Converter User Guide Communication Model Frame and command editors Frame editorCommand editor Select command windowSelect ‘Add Command’ as described earlier Query ColumnMain window Modbus network and node monitors Modbus network monitorStart / Stop sub network scanning Update OFF Update on Node monitorCommand Area Advanced functions Control and status registersBits Name Description Code Name DescriptionCode Error Description Handshake bits themselves bits 14Input/output data during startup Fieldbus control systemAdvanced fieldbus configuration Mailbox commandAdvanced Functions Application example OverviewFor the MM2, we have Type Parameter Address Format Read/writeModbus user map setup Parameter User map data AddressMM2 meter user map setting System configuration System configurationSetup Software Starting Configuration Wizard DB9 pin DescriptionSelecting the SUB-NETWORK Properties Modbus network propertiesParameters configured for Pqmii Connect Devices to the SUB- Network 11 Connect devices to sub-networkSelect Parameters for Each Node 14 Select parameter window17 Configuration report 20 Save device file Queries21 Expanding the tree 23 Changing configuration parameters for a query 25 Opening a saved configuration file Profibus network setup Revision history WarrantyMiscellaneous Release Dates10-2 P485 Modbus to Profibus Converter Index 6-3Power Supply