GE P485 instruction manual Opening a saved configuration file

Page 71

APPLICATION EXAMPLE

DOWNLOADING THE Save the configuration file for future use. The save command is available in File menu. The CONFIGURATION FILE following procedure demonstrates how to save the configuration file to the P485.

1.To open the saved configuration file, select the File > Open menu item. The following window will appear.

Figure 9-25: Opening a saved configuration file

2.To connect to the P485, select the Tools > Port menu item, then select the port connected to P485.

3.Click on the Connect icon.

4.Verify that the green LED is shown in the right corner of the configuration tool, then click the download icon in the toolbar. The download in progress bar will appear.

Figure 9-26: Download in progress

5.If the P485 does not respond to the download, ensure all connections are OK and that the port selection is valid. On some laptop computers, it might be worth trying the other serial ports. Also ensure that no other software (such as any PLC communication drivers) are blocking access to the serial ports.

P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

9–15

Image 71
Contents GE Multilin P485 Modbus to Profibus ConverterPage P485 Modbus to Profibus Converter Table of contentsSoftware Frame Miscellaneous Getting started IntroductionInput and output definition Document conventionsAbout the P485 Modbus to Profibus Converter FeaturesFeatures Communications SpecificationsMechanical Housing OrderingElectrical installation InstallationQuick install Pin Signal Description Profibus connector pin assignmentsPin Description Configuration cable pin assignments P485 endConfiguration cable PC end Indicators and switches Mechanical installationNumber Description State Status P485 status indicatorsInput/output bytes required Modules Profibus installation procedurePoor performance TroubleshootingOverview Data exchangeMemory Map Address Contents AccessBlocks Protocol configurationData Exchange Introduction Installation procedureSoftware overview Select Configuration Wizard and click on OK Using the EnerVista P485/D485 Setup softwareTypical network arrangement Sub-network data flow Address Command Software Overview P485 Modbus to Profibus Converter User Guide Software Overview Configurator main window Configuration main windowInformation window Function Description Fieldbus configurationP485/D485 configuration P485/D485 configurationParameter Description Range Modbus network configurationSoftware Overview PLC Communication modelP485 scan list Basic settingsMenu NodesCommunication Model P485 Modbus to Profibus Converter User Guide Communication Model Frame editor Frame and command editorsSelect command window Command editorQuery Column Select ‘Add Command’ as described earlierMain window Modbus network monitor Modbus network and node monitorsStart / Stop sub network scanning Node monitor Update OFF Update onCommand Area Control and status registers Advanced functionsCode Name Description Bits Name DescriptionHandshake bits themselves bits 14 Code Error DescriptionFieldbus control system Input/output data during startupMailbox command Advanced fieldbus configurationAdvanced Functions Overview Application exampleType Parameter Address Format Read/write For the MM2, we haveParameter User map data Address Modbus user map setupMM2 meter user map setting System configuration System configurationDB9 pin Description Setup Software Starting Configuration WizardModbus network properties Selecting the SUB-NETWORK PropertiesParameters configured for Pqmii 11 Connect devices to sub-network Connect Devices to the SUB- Network14 Select parameter window Select Parameters for Each Node17 Configuration report Queries 20 Save device file21 Expanding the tree 23 Changing configuration parameters for a query 25 Opening a saved configuration file Profibus network setup Release Dates WarrantyMiscellaneous Revision history10-2 6-3 P485 Modbus to Profibus Converter IndexPower Supply