APPLICATION EXAMPLE

INSTALLING THE ENERVISTA P485/D485

SETUP SOFTWARE

STARTING THE

CONFIGURATION

WIZARD

STEP 1: SELECTING THE FIELDBUS TYPE

The following procedure describes how to configure the EnerVista P485/D485 Setup software.

1.Install the EnerVista P485/D485 Setup software.

2.Connect the configuration port of P485 to the PC via the configuration cable.

3.Connect the devices (PQMII and MM2) to P485 through the DB-9 Modbus network connector using the proper RS485 connections shown below.

DB9 pin

Description

 

 

5

Ground

 

 

8

RS485 +

 

 

9

RS485 –

 

 

Start the P485 configuration wizard as follows.

1.Launch the Enervista P485/D485 Setup software.

2.A window for selecting a configuration will be displayed. Select the Configuration Wizard icon.

Figure 9-4: Select configuration wizard

3.Click OK to proceed to step 1 of the configuration wizard.

The first step in the configuration wizard is setting the fieldbus type.

1.Set the Fieldbus type to “Profibus-DP”.

Figure 9-5: Select fieldbus type

2.Click Next to proceed to step 2 of the configuration wizard.

9–6

P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

Image 62
Contents P485 Modbus to Profibus Converter GE MultilinPage Table of contents P485 Modbus to Profibus ConverterSoftware Frame Miscellaneous Introduction Getting startedDocument conventions Input and output definitionAbout the P485 Modbus to Profibus Converter FeaturesFeatures Ordering SpecificationsMechanical Housing CommunicationsElectrical installation InstallationQuick install Profibus connector pin assignments Pin Signal DescriptionConfiguration cable pin assignments P485 end Pin DescriptionConfiguration cable PC end Mechanical installation Indicators and switchesP485 status indicators Number Description State StatusProfibus installation procedure Input/output bytes required ModulesTroubleshooting Poor performanceData exchange OverviewAddress Contents Access Memory MapProtocol configuration BlocksData Exchange Introduction Installation procedureSoftware overview Using the EnerVista P485/D485 Setup software Select Configuration Wizard and click on OKTypical network arrangement Sub-network data flow Address Command Software Overview P485 Modbus to Profibus Converter User Guide Software Overview Configuration main window Configurator main windowInformation window Fieldbus configuration Function DescriptionP485/D485 configuration P485/D485 configurationModbus network configuration Parameter Description RangeSoftware Overview Communication model PLCBasic settings P485 scan listNodes MenuCommunication Model P485 Modbus to Profibus Converter User Guide Communication Model Frame and command editors Frame editorCommand editor Select command windowSelect ‘Add Command’ as described earlier Query ColumnMain window Modbus network and node monitors Modbus network monitorStart / Stop sub network scanning Update OFF Update on Node monitorCommand Area Advanced functions Control and status registersBits Name Description Code Name DescriptionCode Error Description Handshake bits themselves bits 14Input/output data during startup Fieldbus control systemAdvanced fieldbus configuration Mailbox commandAdvanced Functions Application example OverviewFor the MM2, we have Type Parameter Address Format Read/write Modbus user map setup Parameter User map data AddressMM2 meter user map setting System configuration System configurationSetup Software Starting Configuration Wizard DB9 pin DescriptionSelecting the SUB-NETWORK Properties Modbus network propertiesParameters configured for Pqmii Connect Devices to the SUB- Network 11 Connect devices to sub-networkSelect Parameters for Each Node 14 Select parameter window17 Configuration report 20 Save device file Queries21 Expanding the tree 23 Changing configuration parameters for a query 25 Opening a saved configuration file Profibus network setup Revision history WarrantyMiscellaneous Release Dates10-2 P485 Modbus to Profibus Converter Index 6-3Power Supply