APPLICATION EXAMPLE
3.Select the PQMII.D01 file from the list and click on Open.
4.The software will display a list of the most commonly used parameters configured for the PQMII.
Figure 9-9: Parameters configured for PQMII
5.The Modbus User Map values are already present in the configuration file; as such, it is not required to create the new parameters. However, it is necessary to save number of registers to be read. Change the data length to 7 words as required.
6.Similarly, load the configuration file for MM2 by clicking the Load Device button and selecting the
Figure 9-10: Parameters configured for the MM2
7.The software will display a list of the most commonly used parameters configured for the MM2. The Modbus User Map values are already present in the configuration file; as such, it is not required to create the new parameters. However, it is necessary to save number of registers to be read. Change the data length to 5 words as required.
8.The Motor Start A command and Motor Stop command can be executed using command function + operation code.
9.Save this device configuration by clicking the Save Device button.
10.Click Next to proceed to step 4 of the configuration wizard.