STEP 4: CONNECT DEVICES TO THE SUB- NETWORK

APPLICATION EXAMPLE

The fourth step in the configuration wizard is to connect the configured device types to the sub-network. The PQMII and MM2 devices are connected in this step.

1.Click Next to proceed to create nodes on Modbus network as shown below.

Figure 9-11: Connect devices to sub-network

2.There are two nodes on the Modbus network: the PQMII meter and the MM2 relay. To insert a node, click the Create Node button.

3.Set the Node Name as “PQMII Meter”, the Slave Address to “20”, and the Device Type to “PQMII”.

Figure 9-12: Node for PQMII meter

4.Similarly create another node for the MM2. Set the Node Name as “MMII Relay”, the Slave Address to “4”, and the Device Type as “MM2-MM3”.

Figure 9-13: Node for MM2 relay

5.Click Next to proceed to step 5 of the configuration wizard.

P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

9–9

Image 65
Contents GE Multilin P485 Modbus to Profibus ConverterPage P485 Modbus to Profibus Converter Table of contentsSoftware Frame Miscellaneous Getting started IntroductionInput and output definition Document conventionsAbout the P485 Modbus to Profibus Converter FeaturesFeatures Mechanical Housing SpecificationsOrdering CommunicationsElectrical installation InstallationQuick install Pin Signal Description Profibus connector pin assignmentsPin Description Configuration cable pin assignments P485 endConfiguration cable PC end Indicators and switches Mechanical installationNumber Description State Status P485 status indicatorsInput/output bytes required Modules Profibus installation procedurePoor performance TroubleshootingOverview Data exchangeMemory Map Address Contents AccessBlocks Protocol configurationData Exchange Introduction Installation procedureSoftware overview Select Configuration Wizard and click on OK Using the EnerVista P485/D485 Setup softwareTypical network arrangement Sub-network data flow Address Command Software Overview P485 Modbus to Profibus Converter User Guide Software Overview Configurator main window Configuration main windowInformation window Function Description Fieldbus configurationP485/D485 configuration P485/D485 configurationParameter Description Range Modbus network configurationSoftware Overview PLC Communication modelP485 scan list Basic settingsMenu NodesCommunication Model P485 Modbus to Profibus Converter User Guide Communication Model Frame editor Frame and command editorsSelect command window Command editorQuery Column Select ‘Add Command’ as described earlierMain window Modbus network monitor Modbus network and node monitorsStart / Stop sub network scanning Node monitor Update OFF Update onCommand Area Control and status registers Advanced functionsCode Name Description Bits Name DescriptionHandshake bits themselves bits 14 Code Error DescriptionFieldbus control system Input/output data during startupMailbox command Advanced fieldbus configurationAdvanced Functions Overview Application exampleType Parameter Address Format Read/write For the MM2, we haveParameter User map data Address Modbus user map setupMM2 meter user map setting System configuration System configurationDB9 pin Description Setup Software Starting Configuration WizardModbus network properties Selecting the SUB-NETWORK PropertiesParameters configured for Pqmii 11 Connect devices to sub-network Connect Devices to the SUB- Network14 Select parameter window Select Parameters for Each Node17 Configuration report Queries 20 Save device file21 Expanding the tree 23 Changing configuration parameters for a query 25 Opening a saved configuration file Profibus network setup Miscellaneous WarrantyRevision history Release Dates10-2 6-3 P485 Modbus to Profibus Converter IndexPower Supply