Falcon SG3KRM-1TU, SG2KRM-1TU, SG1KRM-2TU Operation, UPS Front Panel Indicator and Function Keys

Page 12

CHAPTER 3

OPERATION

UPS FRONT PANEL INDICATOR AND FUNCTION KEYS

9

1

10

2 8

3

11

4

5

6

7

1.LOAD LEVEL INDICATOR LEDS

*The first or bottom LED is lit when the output load is greater than 25% of the rated output of the UPS.

*The second LED is lit when the output load is greater than 50% of the rated output of the UPS.

*The third LED is lit when the output load is greater than 75% of the rated output of the UPS.

2.BATTERY LEVEL INDICATOR LEDS

*The third or top LED is lit when the battery is fully charged.

*The Second LED is let when the battery level is above the low battery warning Level.

*The first LED is lit when the battery level is above the battery cutoff voltage.

3.LINE / SITE WIRING FAULT INDICATOR LED

For models configured for standard 120 volt domestic usage, this LED is lit to a steady on state when Utility voltage is present. However, should the LED flash on and off, it is an indication that the HOT and NEUTRAL wires are reversed some where in the building wiring. Typically at the wall outlet.

It is normal for this LED to flash with 208 and 240 volt domestic models as these voltages are normally LINE to LINE, without a neutral.

4.BATTERY MODE INDICATOR LED

This LED is lit when the unit is operating from battery.

10

Image 12
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Input Power Factor Correction Extended Battery Bank OptionTrue Regenerative On-Line Design Microprocessor ControlSG Rackmount Installation Instructions Rackmount UPS Mounting Instructions --- ImportantNo Battery Backup is Provided When in this Mode Green Mode Disabled Enabled100-120V 200-240V Models OnlyBattery Module Interconnect Wiring UPSPage Optional Slide Mounting KIT Sgrmkit Slide Mounting DetailsSG Rackmount Extended Battery Bank Selection Guide For 1KVA ModelsUPS Front Panel Indicator and Function Keys OperationInverter Indicator LED Audible Alarms Category one alarmsCategory two alarms Front & Rear Panel Details All modelsSG1KRM-1TU SG1KRM-2TUSG2KRM-1TU & SG3KRM-1TU Typical Rear Panel OverviewSG2KRM-2TU & SG3KRM-2TU Typical Rear Panel Overview Communications Interfaces LocationSupported Protocols RS-232 InterfaceDRY Contact & Opto Coupler Interface Board Options PIN & Jumper Assignment for the FalconUA88374 Relay Option Board UA88376 Relay Option BoardNo-bypass signal Typical Falcon Opto-coupler Interface CardPIN Assignment for the Falcon UA88373 OPTO-COUPLER Option BoardCare & Maintenance Battery Life vs. TemperatureBattery Replacement Storing the UPS and Batteries FCC ConsiderationsTechnical Support Requesting Technical Information or SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportLimited NEW Product Warranty Agreement General ProvisionsSG SeriesTM UPS Plus