Falcon SG3KRM-1TU DRY Contact & Opto Coupler Interface Board Options, UA88374 Relay Option Board

Page 18

DRY CONTACT & OPTO COUPLER INTERFACE BOARD OPTIONS

Typical Falcon Dry Contact Relay Board

DB-9

JP1

J1

JP2

J2

JP3

J3

 

 

 

 

PIN & JUMPER ASSIGNMENT FOR THE FALCON

 

 

 

 

 

 

UA88374 RELAY OPTION BOARD

 

 

 

 

 

 

 

(no on-bypass signal)

 

 

 

 

 

 

 

 

 

 

PIN

 

 

 

 

DESCRIPTION

 

 

1

 

 

 

Low Battery ( When UPS reaches low battery, contact activates)

 

 

 

 

 

 

(J1, 1-2 short = N.O) (J1, 2-3 short = N.C)

 

 

2

 

 

 

JP2 shorted = Low Battery common & all other shorted JP commons

 

 

 

 

 

 

JP2 open = common for low battery only

 

 

3

 

 

 

Utility Loss N.O. ( At loss of utility voltage, contact activates)

 

 

4

 

 

 

Utility Loss N.C. ( At loss of utility voltage, contact activates)

 

 

5

 

 

 

JP1 shorted = Utility Loss common & all other shorted JP commons

 

 

 

 

 

 

JP1 open = Utility Loss common only

 

 

6

 

 

 

Remote Shutdown common

 

 

7

 

 

 

Remote Shutdown

 

 

 

 

 

 

(J2, 1-2 short = outside power) (J2, 2-3 short = inside power)

 

 

 

 

 

 

1-2 shorted. Applying an external 12V signal across the DB-9, pins six

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and seven, while the UPS is on battery, will turn the UPS off.

 

 

 

 

 

 

2-3 shorted. Applying a short directly across the DB-9, pins six and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

seven, while the UPS is on battery, will turn the UPS off.

 

 

8

 

 

 

Alarm (Upon a UPS fault or failure the contact activates)

 

 

 

 

 

 

(J3, 1-2 short = N.O.) (J3, 2-3 short = N.C.)

 

 

9

 

 

 

JP3 shorted = Alarm common & all other shorted JP commons

 

 

 

 

 

 

JP3 open = Alarm common only

 

 

 

 

 

 

PIN & JUMPER ASSIGNMENT FOR THE FALCON

 

 

 

 

 

 

UA88376 RELAY OPTION BOARD

 

 

 

 

 

 

 

(with on-bypass signal)

 

 

 

 

 

 

 

 

 

 

 

 

 

DB-9F PIN & JUMPER ASSIGNMENTS

 

 

PIN

 

 

 

 

 

DESCRIPTION

 

 

1

 

Low Battery ( When UPS reaches low battery, contact activates)

 

 

 

 

(J1, 1-2 short = N.O) (J1, 2-3 short = N.C)

 

 

2

 

JP2 shorted = Low Battery common & all other shorted JP commons

 

 

 

 

JP2 open = common for low battery only

 

 

3

 

Utility Loss N.O. ( At loss of utility voltage, contact activates)

 

 

4

 

Utility Loss N.C. ( At loss of utility voltage, contact activates)

 

 

5

 

JP1 shorted = Utility Loss common & all other shorted JP commons

 

 

 

 

JP1 open = Utility Loss common only

 

 

6

 

Remote Shutdown common

 

 

7

 

Remote Shutdown

 

 

 

 

(J2, 1-2 short = outside power) (J2, 2-3 short = inside power)

 

 

 

 

1-2 shorted. Applying an external 12V signal across the DB-9, pins six

 

 

 

 

 

 

 

 

 

 

and seven, while the UPS is on battery, will turn the UPS off.

 

 

 

 

2-3 shorted. Applying a short directly across the DB-9, pins six and

 

 

 

 

 

 

 

 

 

 

seven, while the UPS is on battery, will turn the UPS off.

 

 

8

 

On Bypass or Alarm (Upon the UPS going to bypass or a UPS failure

 

 

 

 

the contact activates)

 

 

 

 

(J3, 1-2 short = N.O.) (J3, 2-3 short = N.C.)

 

 

9

 

JP3 shorted = On bypass, Alarm common & all other shorted JP

 

 

 

 

commons

 

 

 

 

JP3 open = On bypass, Alarm common only

 

16

Image 18
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions True Regenerative On-Line Design Input Power Factor CorrectionExtended Battery Bank Option Microprocessor ControlSG Rackmount Installation Instructions Rackmount UPS Mounting Instructions --- Important100-120V 200-240V No Battery Backup is Provided When in this ModeGreen Mode Disabled Enabled Models OnlyBattery Module Interconnect Wiring UPSPage Optional Slide Mounting KIT Sgrmkit Slide Mounting DetailsSG Rackmount Extended Battery Bank Selection Guide For 1KVA ModelsUPS Front Panel Indicator and Function Keys OperationInverter Indicator LED Audible Alarms Category one alarmsCategory two alarms SG1KRM-1TU Front & Rear Panel DetailsAll models SG1KRM-2TUSG2KRM-1TU & SG3KRM-1TU Typical Rear Panel OverviewSG2KRM-2TU & SG3KRM-2TU Typical Rear Panel Overview Supported Protocols Communications InterfacesLocation RS-232 InterfaceUA88374 Relay Option Board DRY Contact & Opto Coupler Interface Board OptionsPIN & Jumper Assignment for the Falcon UA88376 Relay Option BoardPIN Assignment for the Falcon No-bypass signalTypical Falcon Opto-coupler Interface Card UA88373 OPTO-COUPLER Option BoardCare & Maintenance Battery Life vs. TemperatureBattery Replacement Storing the UPS and Batteries FCC ConsiderationsSUPPORT@FALCONUPS.COM Technical SupportRequesting Technical Information or Support 800.842.6940 Falcon Web SupportLimited NEW Product Warranty Agreement General ProvisionsSG SeriesTM UPS Plus